Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Gain access to PCB (use Insulation Mat as required)
Main On/Off Control in the On position
Disconnect connector X10
Main On/Off Control in the On position
Disconnect connector X10
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
If a fault code is displayed press boiler 'Reset' button.
Test 1:
Measure between 8 and 12 V AC across connections 1 and 2 of plug X10.
Test 2:
Measure between 18 and 22 V AC across connections 3 and 4 of plug X10.
Note.
All voltages are made on the end of the plug and not on the Motherboard.
Test 1:
Measure between 8 and 12 V AC across connections 1 and 2 of plug X10.
Test 2:
Measure between 18 and 22 V AC across connections 3 and 4 of plug X10.
Note.
All voltages are made on the end of the plug and not on the Motherboard.

Isolate as per TOPs P4
and refit as necessary