XSol Diagnostic System

Interactive Test Sequence Navigator

Welcome to the XSol Diagnostic System

This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.

Start Diagnostic Sequence

or choose a specific test below:

BAXI PRECISION + ERP

GLOBALLY REPLACED

Next: &1, *

NO FAULT FOUND

Next: nff

CASE REMOVAL


Next: &1253, !f2

POWER UP SELF TEST

CH TEMPERATURE CONTROL SET TO OFF POSITION
ENSURE APPLIANCE IS COOL

Next: &513, ?7, ?9, ?12, ?1255

OBSERVATION FAN RUNS

ENSURE APPLIANCE IS COOL

Next: &269, ?443, ?445

CH OPERATION

CH TEMPERATURE CONTROL SET TO MAX

Next: &1108, ?538, ?540, ?542, ?729

DHW OPERATION

HOT WATER DEMAND

Next: &nff, ?609, ?611

OBSERVATION BURNER IGNITION & ESTABLISH

ENSURE APPLIANCE IS COOL

Next: &44, ?270, ?276, ?516

FAULT CODE - SENSORS

NOT USED

Next: &nff, f386

FAULT CODE - MISCELLANEOUS

NOT USED

Next: &nff, f506

FAULT CODE FAN FAULT

NOT USED

Next: &nff, f400

TYPE OF DIAGNOSTIC PROCEDURE

PLEASE SELECT FROM O

Next: &1116, !f514

STATUS CODE - TEMPERATURE PROTECTION

NOT USED

Next: &nff, f685

STATUS CODE - SHUTDOWN INPUT

NOT USED

Next: &nff, f657

STATUS CODE - COMMUNICATION FAULT

NOT USED

Next: &nff, f670

STATUS CODE - MISCELLANEOUS

NOT USED

Next: &nff, f675

& FUSE PCB FURTHER INVESTIGATION

NOT USED

Next: &nff, f797

FAULT CODE - OVERHEAT

NOT USED

Next: &nff, f869

OBSERVATION EXTERNAL FROST PROTECTION

ENSURE THERE ARE NO DEMANDS FOR HEATING OR HOT WATER

Next: &29, !f1103

OBSERVATION BOILER MODULATION

ATTACH TEMPERATURE CLAMP TO FLOW PIPE JUST ABOVE HEAT EXCHANGER

Next: &45, f1109

OBSERVATION SYSTEM PUMP RUNNING

CH TEMPERATURE CONTROL SET TO OFF POSITION
LOCATE & GAIN ACCESS TO SYSTEM PUMP

Next: &1102, f1117

FAULT CODE - PARAMETER FAULT

NOT USED

Next: &nff, f1234

PARAMETER UNIT REPLACEMENT

Next: &nff, !f1250

SET UP FOR NEW PARAMETER UNIT

IF A NEW PARAMETER U

Next: &nff, !f1252

BOILER NOISY

FLUE

Next: End

BOILER NOISY

COMBUSTION SEALS

Next: End

BOILER NOISY

BURNER MESH C/W GASKET

Next: End

BOILER NOISY

GAS VALVE ASSEMBLY

Next: End

BOILER NOISY

GAS VALVE ADJUSTMENT

Next: End

BURNER IGNITION 2

COMBUSTION CONTROL UNIT

Next: End

BURNER IGNITION

FLUE

Next: End

BURNER IGNITION

SET - ELECTRODES C/W SCREW & GASKET

Next: End

BURNER IGNITION 2

BURNER MESH C/W GASKET

Next: End

BOILER SYS COOL

KIT - SENSOR

Next: End

BOILER SYS COOL 2

KIT - SENSOR

Next: End

BOILER SYS COOL

CONTROLLER - USER INTERACTION

Next: End

BOILER SYS COOL

FLUE

Next: End

FROST PROTECTION

Next: End

MODULATION

KIT - SENSOR

Next: End

MODULATION 2

KIT - SENSOR

Next: End

MODULATION

CONTROLLER - USER INTERACTION

Next: End

BURNER DOES NOT IGNITE AND EST

COMBUSTION CONTROL UNIT

Next: End

BURNER DOES NOT IGNITE & EST 2

SET - ELECTRODES C/W SCREW & GASKET

Next: End

BURNER DOES NOT IGNITE & EST

BURNER MESH C/W GASKET

Next: End

BURNER DOES NOT IGNITE & EST

AIR INTAKE

Next: End

PUMP DOES NOT RUN

Next: End

FAULT CODE PARAMETER

UNIT - PARAMETER

Next: End

FAULT CODE PARAMETER

HARNESS - CABLE 24V HE

Next: End

FAULT CODE PARAMETER 2

UNIT - PARAMETER

Next: End

BLANK FOR PARAMETER UNIT REPLACEMENT

Z REDIRECTION

Next: End

BLANK FOR PARAMETER UNIT SETUP

Z REDIRECTION

Next: End

INFORMATION RESETTING APPLIANCE

Z REDIRECTION

Next: End

CHIMNEY SWEEP ILLUMINATED SOLID

BUTTONS STUCK IN

Next: End

FAN RUNS

KIT - SENSOR

Next: End

FAN RUNS 2

KIT - SENSOR

Next: End

FAN RUNS 2

CONTROLLER - USER INTERACTION

Next: End

FUSE INVESTIGATION

FAN OR COMBUSTION CONTROL UNIT

Next: End

FAULT CODES

Z REDIRECTION

Next: End

POWER UP SELF TEST

Next: End

CASE OFF

DIRECTION CHOICE OR CONTINUE

Next: End

HARNESS DTP - MAINS

HARNESS DTP - MAINS

Next: End

POWER UP SELF TEST

COVER - CONTROL AND FUSE

Next: End

BURNER IGNITION

TRAP - C/W ELBOW - CONDENSATE

Next: End

BURNER IGNITION

GAS INLET PRESSURE

Next: End

NO BURNER IGNITION

COMBUSTION CONTROL UNIT

Next: End

AIR INTAKE

AIR INTAKE

Next: End

BURNER IGNITION

COMBUSTION CONTROL UNIT

Next: End

BOILER NOISY

GAS INLET PRESSURE

Next: End

BOILER NOISY

TRAP - C/W ELBOW - CONDENSATE

Next: End

BOILER NOISEY

AIR INTAKE

Next: End

FAULT CODE SENSORS

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE 2

KIT - SENSOR

Next: End

FAULT CODE

KIT - SENSOR

Next: End

STATUS CODE

Z REDIRECTION

Next: End

FAULT CODE FAN

FAULT CODE RESET

Next: End

FAN DOES NOT RUN 3

FAN

Next: End

FAN FAULT CODE 4

FAN

Next: End

FAULT CODE MISCELLANEOUS

UNIT - PARAMETER

Next: End

DIAGNOSTIC PROCEDURE

DIRECTION CHOICE OR CONTINUE

Next: End

BURNER IGNITION

KIT - SENSOR

Next: End

BURNER IGNITION

SWITCH - PRESSURE C/W O-RING

Next: End

BURNER IGNITION

FAULT CODE RESET - OVERHEAT - FLUE STAT

Next: End

BOILER SYS COOL

UNIT - PARAMETER

Next: End

BOILER SYS COOL

GAS INLET PRESSURE

Next: End

FAULT CODE MISC

FAULT/STATUS CODE MISCELLANEOUS

Next: End

STATUS CODE SHUTDWN 2

CONTROLLER - USER INTERACTION

Next: End

STAUS CODE COMMS

FAULT/STATUS CODE MISCELLANEOUS

Next: End

STATUS CODE MISC

COMBUSTION CONTROL UNIT

Next: End

BURNER IGNITION 2

SWITCH - PRESSURE C/W O-RING

Next: End

STATUS CODE TEMP

Next: End

STATUS CODE TEMP 2

PUMP

Next: End

STATUS CODE TEMP 5

KIT - SENSOR

Next: End

STATUS CODE TEMP 3

KIT - SENSOR

Next: End

STATUS CODE TEMP

KIT - SENSOR

Next: End

STATUS CODE TEMP 2

KIT - SENSOR

Next: End

STATUS CODE TEMP 2

Next: End

STATUS CODE TEMP 4

KIT - SENSOR

Next: End

STATUS CODE TEMP 6

KIT - SENSOR

Next: End

STATUS CODE TEMP 3

Next: End

PWR UP SELF TEST

COMBUSTION CONTROL UNIT

Next: End

LIMPET TEST

PUMP

Next: End

FAULT CODE OVERHEAT 2

PUMP

Next: End

FAULT CODE OVERHEAT

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT

SWITCH - PRESSURE C/W O-RING

Next: End

FAULT CODE OVERHEAT 4

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT 3

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT 2

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT

FLUE

Next: End

FAULT CODE OVERHEAT 2

SWITCH - PRESSURE C/W O-RING

Next: End

STATUS CODE TEMP 4

PUMP

Next: End

STATUS CODE TEMP 7

KIT - SENSOR

Next: End

STATUS CODE TEMP 11

KIT - SENSOR

Next: End

STATUS CODE TEMP 8

KIT - SENSOR

Next: End

STATUS CODE TEMP 10

KIT - SENSOR

Next: End

STATUS CODE TEMP 4

Next: End

STATUS CODE TEMP 9

KIT - SENSOR

Next: End

STATUS CODE TEMP 12

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT

PUMP

Next: End

FAULT CODE OVERHEAT 8

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT 4

SWITCH - PRESSURE C/W O-RING

Next: End

FAULT CODE OVERHEAT 7

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT 6

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT 5

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT 2

FLUE

Next: End

FAULT CODE OVERHEAT 3

SWITCH - PRESSURE C/W O-RING

Next: End

BOILER NOISY 2

GAS VALVE ASSEMBLY

Next: End

BOILER NOISY

HEAT ENGINE FLUEWAYS

Next: End

BOILER NOISY

FAN

Next: End

GAS VALVE ADJUSTMENT

Z REDIRECTION

Next: End

BOILER NOISY

INTERFACE - FLUE C/W SEAL

Next: End

BOILER NOISY

INTERFACE SUMP

Next: End

BURNER IGNITION

INTERFACE - FLUE C/W SEAL

Next: End

BURNER IGNITION

INTERFACE SUMP

Next: End

BURNER IGNITION

HEAT ENGINE FLUEWAYS

Next: End

BURNER IGNITION 2

FAN

Next: End

BURNER IGNITION 2

GAS VALVE ASSEMBLY

Next: End

BOILER SYS COOL

COMBUSTION CONTROL UNIT

Next: End

BOILER SYS COOL

INTERFACE - FLUE C/W SEAL

Next: End

BOILER SYS COOL

INTERFACE SUMP

Next: End

BOILER SYS COOL 2

COMBUSTION CONTROL UNIT

Next: End

BOILER SYS COOL

HEAT ENGINE FLUEWAYS

Next: End

BOILER SYS COOL

FAN

Next: End

MODULATION

COMBUSTION CONTROL UNIT

Next: End

PUMP DOES NOT RUN

PUMP

Next: End

BURNER DOES NOT IGNITE & EST 2

COMBUSTION CONTROL UNIT

Next: End

BURNER DOES NOT IGNITE & EST

SET - ELECTRODES C/W SCREW & GASKET

Next: End

BURNER DOES NOT IGNITE & EST

INTERFACE - FLUE C/W SEAL

Next: End

BURNER DOES NOT IGNITE & EST

INTERFACE SUMP

Next: End

BURNER DOES NOT IGNITE & EST

HEAT ENGINE FLUEWAYS

Next: End

BURNER DOES NOT IGNITE & EST

GAS VALVE ASSEMBLY

Next: End

PARAMETER FAULT

FAULT CODE RESET

Next: End

FAN DOES NOT RUN

FAN ELECTRICAL CONNECTIONS

Next: End

FAN FAULT CODE

FAN ELECTRICAL CONNECTIONS

Next: End

CHIMNEY ILLUMINATED SOLID

CONTROLLER - USER INTERACTION

Next: End

FAN DOES NOT RUN

FAN OR COMBUSTION CONTROL UNIT

Next: End

FAN RUNS

COMBUSTION CONTROL UNIT

Next: End

FAN FAULT CODE

FAN OR COMBUSTION CONTROL UNIT

Next: End

FAN FAULT CODE 2

COMBUSTION CONTROL UNIT

Next: End

FUSE INVESTIGATION

COMBUSTION CONTROL UNIT FUSE INVESTIGATION

Next: End

FAULT CODES

DIRECTION CHOICE OR CONTINUE

Next: End

FUSE FURTHER INVESTIGATION

Z REDIRECTION

Next: End

PWR UP SELF TEST

CONTROLLER - USER INTERACTION

Next: End

BURNER IGNITION 3

GAS VALVE ASSEMBLY

Next: End

FAULT CODE SENSOR

FAULT CODE RESET

Next: End

FAULT CODE

HARNESS - CABLE 24V HE

Next: End

FAULT CODE 2

HARNESS - CABLE 24V HE

Next: End

STATUS CODE

DIRECTION CHOICE OR CONTINUE

Next: End

FAN ROTATION

FAN

Next: End

FAN FAULT CODE 2

FAN

Next: End

FAN FAULT CODE 4

COMBUSTION CONTROL UNIT

Next: End

FAN FAULT CODE 3

COMBUSTION CONTROL UNIT

Next: End

FAN FAULT CODE

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE MISCELLANEOUS

FAULT CODE RESET

Next: End

FAULT CODE MISCELLANEOUS

COMBUSTION CONTROL UNIT

Next: End

BURNER IGNITION

HARNESS - CABLE 24V HE

Next: End

DHW OPERATION

Next: End

DHW OPERATION

Next: End

STATUS CODE SHUT DWN

FAULT CODE RESET

Next: End

STATUS CODE SHUTDWN

CONTROLLER - USER INTERACTION

Next: End

STATUS CODE SHUTDWN

BL TERMINALS - LINK

Next: End

STATUS CODE COMS

FAULT CODE RESET

Next: End

STATUS CODE COMMS

COMBUSTION CONTROL UNIT

Next: End

STATUS CODE MISC

FAULT CODE RESET

Next: End

BURNER IGNITION 2

FLUE

Next: End

STATUS CODE TEMP 2

COMBUSTION CONTROL UNIT

Next: End

STATUS CODE TEMP

COMBUSTION CONTROL UNIT

Next: End

STATUS CODE TEMP

STATUS CODE RESET - TEMP PROTECTION

Next: End

STATUS CODE TEMP 3

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE OVERHEAT

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE OVERHEAT

HARNESS - CABLE 24V HE

Next: End

FAULT CODE OVERHEAT

FAULT CODE RESET - OVERHEAT - FLUE STAT

Next: End

FAULT CODE OVERHEAT 3

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE OVERHEAT 2

COMBUSTION CONTROL UNIT

Next: End

STATUS CODE TEMP 4

COMBUSTION CONTROL UNIT

Next: End

STATUS CODE TEMP 2

STATUS CODE RESET - TEMP PROTECTION

Next: End

STATUS CODE TEMP 6

COMBUSTION CONTROL UNIT

Next: End

STATUS CODE TEMP 5

COMBUSTION CONTROL UNIT

Next: End

STATUS CODE TEMP

PUMP

Next: End

FAULT CODE OVERHEAT 6

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE OVERHEAT 2

HARNESS - CABLE 24V HE

Next: End

FAULT CODE OVERHEAT 2

FAULT CODE RESET - OVERHEAT - FLUE STAT

Next: End

FAULT CODE OVERHEAT 5

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE OVERHEAT 4

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE OVERHEAT 3

PUMP

Next: End

HEAT EXCHANGER FLUEWAYS RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION HEAT EXCHANGER FLUEWAYS

Next: !p1010

FAN BEARING PLATE FAILURE

CHARACTERISTIC TEST FROM INSPECTION HEAT EXCHANGER FLUEWAYS

Next: !p1012

HEAT EXCHANGER FLUEWAYS RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION HEAT EXCHANGER FLUEWAYS

Next: !p1060

FAN BEARING PLATE FAILURE

CHARACTERISTIC TEST FROM INSPECTION HEAT EXCHANGER FLUEWAYS

Next: !p1062

HEAT EXCHANGER FLUEWAYS RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION HEAT EXCHANGER FLUEWAYS

Next: !p1086

FAN BEARING PLATE FAILURE

CHARACTERISTIC TEST FROM INSPECTION HEAT EXCHANGER FLUEWAYS

Next: !p1088

FAULT CODE (CHIMNEY SWEEP LED FLASHING RED)

CHARACTERISTIC TEST FROM POWER UP SELF TEST

Next: p13

HEAT EXCHANGER FLUEWAYS RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION HEAT EXCHANGER FLUEWAYS

Next: !p1224

FAN BEARING PLATE FAILURE

CHARACTERISTIC TEST FROM INSPECTION HEAT EXCHANGER FLUEWAYS

Next: !p1226

ELECTRICAL CONNECTION - FAN MOTOR TO PCB POOR

CHARACTERISTIC TEST FROM OBSERVATION FAN ROTATION & RESISTANCE

Next: !p1245

ELECTRICAL CONNECTION - FAN MOTOR TO PCB POOR

CHARACTERISTIC TEST FROM OBSERVATION FAN ROTATION & RESISTANCE

Next: !p1247

CHIMNEY SWEEP LED ILLUMINATED (SOLID RED OR GREEN)

CHARACTERISTIC TEST FROM POWER UP SELF TEST

Next: p1257

BURNER DOES NOT IGNITE & ESTABLISH

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH

Next: p271

BURNER IGNITES BUT IS BAFFLING AND/OR NOISY

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH

Next: p277

FAN PULSES

CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS

Next: p484

FAN DOES NOT RUN

CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS

Next: p447

FAN SEIZED AND/OR ROTATION RESTRICTED

CHARACTERISTIC TEST FROM OBSERVATION FAN ROTATION & RESISTANCE

Next: !p450

FAN RESISTANCE NOT AS EXPECTED

CHARACTERISTIC TEST FROM OBSERVATION FAN ROTATION & RESISTANCE

Next: !p1261

FAN DOES NOT RUN

CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS

Next: p467

FAN SEIZED AND/OR RESTRICTED

CHARACTERISTIC TEST FROM OBSERVATION FAN ROTATION & RESISTANCE

Next: !p470

FAN RESISTANCE NOT AS EXPECTED

CHARACTERISTIC TEST FROM OBSERVATION FAN ROTATION & RESISTANCE

Next: !p1271

FAN RUNS

CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS - FAULT CODE

Next: p478

FAULT CODE 2 FLASHES RED OCCURS

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH

Next: p517

BOILER AND RADIATORS DO NOT REACH TEMPERATURE

CHARACTERISTIC TEST FROM CH OPERATION

Next: p561

BOILER UP TO TEMPERATURE, RADIATORS DO NOT HEAT SUFFICIENTLY

CHARACTERISTIC TEST FROM CH OPERATION

Next: p550

BOILER SHUTS DOWN OVERHEAT FAULT - 2 FLASHES RED OCCURS

CHARACTERISTIC TEST FROM CH OPERATION

Next: p543

DHW OPERATION UNSATISFACTORY

CHARACTERISTIC TEST FROM DHW OPERATION

Next: !p610

DHW DEMAND NOT RECOGNISED

CHARACTERISTIC TEST FROM DHW OPERATION

Next: !p612

NO CONNECTIONS - BL TERMINALS

CHARACTERISTIC TEST FROM INSPECTION BL TERMINALS - USER INTERFACE

Next: !p665

EXTERNAL CONNECTIONS - BL TERMINALS

CHARACTERISTIC TEST FROM INSPECTION BL TERMINALS - USER INTERFACE

Next: p667

CONTROL PANEL LEDS DO NOT ILLUMINATE

CHARACTERISTIC TEST FROM POWER UP SELF TEST

Next: p8

BOILER GOES TO TEMPERATURE PROTECTION - FLOW TEMPERATURE BELOW 80°C

CHARACTERISTIC TEST FROM TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

Next: p722

BOILER FLOW TEMPERATURE EXCEEDS 85°C AND STILL FIRED

CHARACTERISTIC TEST FROM TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

Next: p705

BOILER SHUTS DOWN TEMP PROTECTION - 1 FLASH GREEN OCCURS EVERY 3 SECONDS

CHARACTERISTIC TEST FROM CH OPERATION

Next: p762

BOILER GOES TO OVERHEAT - FLOW TEMPERATURE BELOW 80°C

CHARACTERISTIC TEST FROM TEMPERATURE - RUN BOILER TO MAXIMUM

Next: p826

BOILER FLOW TEMPERATURE EXCEEDS 85°C AND STILL FIRED

CHARACTERISTIC TEST FROM TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

Next: p828

BOILER GOES TO TEMPERATURE PROTECTION - FLOW TEMPERATURE BELOW 80°C

CHARACTERISTIC TEST FROM TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

Next: p851

BOILER FLOW TEMPERATURE EXCEEDS 85°C AND STILL FIRED

CHARACTERISTIC TEST FROM TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

Next: p853

STATUS CODE (CHIMNEY SWEEP LED FLASHING GREEN)

CHARACTERISTIC TEST FROM POWER UP SELF TEST

Next: p10

BOILER GOES TO OVERHEAT - FLOW TEMPERATURE BELOW 80°C

CHARACTERISTIC TEST FROM TEMPERATURE - RUN BOILER TO MAXIMUM

Next: p913

BOILER FLOW TEMPERATURE EXCEEDS 85°C AND STILL FIRED

CHARACTERISTIC TEST FROM TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

Next: p915

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p1110, !f1111

VOLTAGE PUMP AT PUMP

GAIN ACCESS TO PUMPS ELECTRICAL CONNECTIONS

Next: !p1118, !f1230

VOLTAGE RECTIFICATION AT PCB

{GAINPCBACS}
CH TEMPERATURE CONTROL SET TO OFF POSITION

Next: p1162, f1163

DISCONNECT SPARK ELECTRODE AT SPARK GENERATOR

DISCONNECT SPARK ELECTRODE LEAD FROM SPARK GENERATOR

Next: !p1166, !f1167

INSPECTION AIR INTAKE MANIFOLD

REMOVE THE AIR INTAKE MANIFOLD

Next: p1210, !f1229

INSPECTION PARAMETER UNIT

Next: p1236, !f1237

FUSE FURTHER INVESTIGATION

THE INFORMATION PROV

Next: !p23, !f24

VOLTAGE GAS VALVE

Next: !p286, !f287

RESISTANCE THERMISTOR FLOW AND HARNESS

REMOVE CONNECTOR X5 FROM THE PCB

Next: p393, f388

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: !p391, !f392

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p398, !f399

OBSERVATION FAN RUNS - FAULT CODE

Next: p492, ?465, ?477

RESET APPLIANCE - FAULT/STATUS CODE DISPLAYED

CH TEMPERATURE CONTROL SET TO OFF

Next: !p507, f508

INSPECTION PARAMETER UNIT

Next: p509, !f510

RESISTANCE STAT OVERHEAT

GAIN ACCESS TO OVERHEAT STAT & DISCONNECT LEADS TO STAT

Next: p520, !f521

PRESSURE GAS INLET

ATTACH PRESSURE GAUGE TO GAS PRESSURE INLET TEST POINT LOCATED UNDERNEATH THE BOILER

Next: p1089, !f567

RESET APPLIANCE - STATUS CODE DISPLAYED

CH TEMPERATURE CONTROL SET TO OFF

Next: !p660, f659

INSPECTION BL TERMINALS - USER INTERFACE

GAIN ACCESS TO THE USER CONTROL INTERFACE PCB, (USE INSULATION MAT AS REQUIRED)

Next: !p663, ?664, ?666

RESET APPLIANCE - FAULT/STATUS CODE DISPLAYED

CH TEMPERATURE CONTROL SET TO OFF

Next: !p671, f672

INSPECTION WIRING HARNESS CONNECTIONS

{GAINPCBACS}

Next: !p673, !f674

RESET APPLIANCE - STATUS CODE DISPLAYED

CH TEMPERATURE CONTROL SET TO OFF

Next: !p676, !f678

OBSERVATION SYSTEM WATER

GAIN ACCESS TO SYSTEM AS REQUIRED

Next: p686, !f687

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p717, !f718

RESISTANCE FAN ASSEMBLY

{GAINPCBACS}
REMOVE FAN DRIVER PCB FROM THE FAN ASSEMBLY

Next: !p1275, !f1274

RESISTANCE SAFETY CIRCUIT AND HARNESS

REMOVE CONNECTOR X5 FROM THE PCB

Next: !p817, f818

RESISTANCE STAT OVERHEAT

GAIN ACCESS TO OVERHEAT STAT & DISCONNECT LEADS TO STAT

Next: p819, !f820

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p844, !f845

VOLTAGE PUMP AT PUMP

GAIN ACCESS TO PUMPS ELECTRICAL CONNECTIONS

Next: !p866, !f1231

OBSERVATION SYSTEM WATER

GAIN ACCESS TO SYSTEM AS REQUIRED

Next: p898, !f871

RESISTANCE SAFETY CIRCUIT AND HARNESS

REMOVE CONNECTOR X5 FROM THE PCB

Next: !p904, f905

RESISTANCE STAT OVERHEAT

GAIN ACCESS TO OVERHEAT STAT & DISCONNECT LEADS TO STAT

Next: p906, !f907

VOLTAGE PUMP AT PUMP

GAIN ACCESS TO PUMPS ELECTRICAL CONNECTIONS

Next: !p927, !f1232

STATUS CODES

Next: !p42, !f43

INSPECTION FLUE

Next: p1001, !f1002

COMBUSTION PERFORMANCE CHECK

CONNECT FGA TO THE COMBUSTION TEST POINT ON THE BOILER

Next: !p1003, f1004

INSPECTION HEAT EXCHANGER FLUEWAYS

REMOVE THE COMBUSTION CONTROL UNIT AND GAIN
ACCESS TO THE HEAT EXCHANGER FLUEWAYS

Next: p1007, ?1009, ?1011

INSPECTION BURNER

Next: p1013, !f1014

ADJUSTMENT GAS VALVE

CONNECT FGA TO THE COMBUSTION TEST POINT ON THE BOILER

Next: p1015, !f1016

GAS VALVE ADJUSTED CORRECTLY

THE COMBUSTION READI

Next: !p1017, !f1018

OBSERVATION SPARK GENERATOR

{GAINPCBACS}
REMOVE SPARK IGNITION LEAD FROM THE SPARK GENERATOR AND MAKE SAFE

Next: p1045, !f1044

INSPECTION FLUE

Next: p1047, !f1046

INSPECTION INTERFACE AND SUMP

Next: p1054, ?1049, ?1051

INSPECTION ELECTRODE IGNITION

REMOVE SPARK ELECTRODE ASSEMBLY FROM THE BOILER

Next: p1055, !f1056

INSPECTION HEAT EXCHANGER FLUEWAYS

REMOVE THE COMBUSTION CONTROL UNIT AND GAIN
ACCESS TO THE HEAT EXCHANGER FLUEWAYS

Next: p1057, ?1059, ?1061

INSPECTION BURNER

Next: !p1063, !f1064

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p1066, !f1067

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: p1068, !f1069

RESISTANCE POTENTIOMETER - CH TEMPERATURE

DISCONNECT USER INTE

Next: !p1070, !f1071

INSPECTION INTERFACE AND SUMP

Next: p1083, ?1078, ?1080

INSPECTION HEAT EXCHANGER FLUEWAYS

REMOVE THE COMBUSTION CONTROL UNIT AND GAIN
ACCESS TO THE HEAT EXCHANGER FLUEWAYS

Next: !p1084, ?1085, ?1087

INSPECTION FLUE

Next: p1076, !f1101

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: p1112, !f1113

RESISTANCE POTENTIOMETER - CH TEMPERATURE

DISCONNECT USER INTE

Next: !p1114, !f1115

VOLTAGE RECTIFICATION AT PCB - IGNITION

{GAINPCBACS}

Next: !p1164, f1209

INSPECTION FLUE

Next: p1211, !f1212

INSPECTION INTERFACE AND SUMP

Next: p1213, ?1215, ?1217

INSPECTION ELECTRODE IGNITION

REMOVE SPARK ELECTRODE ASSEMBLY FROM THE BOILER

Next: p1219, !f1220

INSPECTION HEAT EXCHANGER FLUEWAYS

REMOVE THE COMBUSTION CONTROL UNIT AND GAIN
ACCESS TO THE HEAT EXCHANGER FLUEWAYS

Next: p1221, ?1223, ?1225

INSPECTION BURNER

Next: !p1227, !f1228

RESISTANCE HARNESS PARAMETER UNIT

REMOVE CONNECTOR X5 FROM THE PCB
DISCONNECT ELECTRICAL CONNECTOR TO PARAMETER UNIT

Next: p1238, !f1239

RESET APPLIANCE - FAULT/STATUS CODE DISPLAYED

CH TEMPERATURE CONTROL SET TO OFF

Next: !p1240, !f1241

INSPECTION BUTTON STUCK IN

Next: !p1258, !f1259

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p1264, !f1265

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: p1266, !f1267

RESISTANCE POTENTIOMETER - CH TEMPERATURE

DISCONNECT USER INTE

Next: !p1268, !f1269

FAULT CODES

Next: !p16, !f15

VOLTAGE MAINS AT PCB

{GAINPCBACS}

Next: p19, !f20

RESISTANCE FUSE PCB

REMOVE FUSE FROM THE PCB

Next: p21, f22

OBSERVATION BOILER RESPONDS

Next: !p25, !f795

INSPECTION CONDENSATE

Next: p280, !f281

PRESSURE GAS INLET

ATTACH PRESSURE GAUGE TO GAS PRESSURE INLET TEST POINT LOCATED UNDERNEATH THE BOILER

Next: p340, !f341

PRESSURE GAS INLET

ATTACH PRESSURE GAUGE TO GAS PRESSURE INLET TEST POINT LOCATED UNDERNEATH THE BOILER

Next: p1120, !f283

RESISTANCE GAS VALVE

REMOVE ELECTRICAL CONNECTOR FROM THE GAS VALVE

Next: p284, f285

VOLTAGE GAS VALVE

Next: p288, !f308

INSPECTION AIR INTAKE MANIFOLD

REMOVE THE AIR INTAKE MANIFOLD

Next: p1043, !f291

INSPECTION CONDENSATE

Next: p342, !f343

INSPECTION AIR INTAKE MANIFOLD

REMOVE THE AIR INTAKE MANIFOLD

Next: p929, !f345

RESET APPLIANCE - FAULT CODE

CH TEMPERATURE CONTROL SET TO OFF

Next: !p389, !f390

RESISTANCE THERMISTOR RETURN AND HARNESS

REMOVE CONNECTOR X5 FROM THE PCB

Next: p387, f397

OBSERVATION FAN ROTATION & RESISTANCE

{GAINPCBACS}
REMOVE FAN DRIVER PCB FROM THE FAN ASSEMBLY

Next: p1263, ?449, ?451, ?1244

OBSERVATION FAN ROTATION & RESISTANCE

{GAINPCBACS}
REMOVE FAN DRIVER PCB FROM THE FAN ASSEMBLY

Next: !p1273, ?469, ?471, ?1246

OBSERVATION FAN ROTATION & RESISTANCE - FAN PULSES

{GAINPCBACS}
REMOVE FAN DRIVER PCB FROM THE FAN ASSEMBLY

Next: !p485, !f491

OBSERVATION FAN ROTATION & RESISTANCE - FAN PULSES

{GAINPCBACS}
REMOVE FAN DRIVER PCB FROM THE FAN ASSEMBLY

Next: !p498, !f496

INSPECTION WIRING HARNESS CONNECTIONS

{GAINPCBACS}

Next: !p511, !f650

RESISTANCE SAFETY CIRCUIT AND HARNESS

REMOVE CONNECTOR X5 FROM THE PCB

Next: p518, f519

RESISTANCE SWITCH AIR PRESSURE

GAIN ACCESS TO AIR PRESSURE SWITCH AND DISCONNECT LEADS

Next: !p522, !f523

OBSERVATION SYSTEM WATER

GAIN ACCESS TO SYSTEM AS REQUIRED

Next: p812, !f614

OBSERVATION SYSTEM WATER

GAIN ACCESS TO SYSTEM AS REQUIRED

Next: p807, !f552

OBSERVATION BOILER KW OUTPUT

Next: p562, !f563

GAS RATE

Next: p1065, f565

DISCONNECT EXTERNAL BL CONNECTIONS

REMOVE EXTERNAL CONN

Next: !p668, !f669

OPERATION AIR PRESSURE SWITCH

REMOVE AIR PRESSURE SWITCH AND DISCONNECT LEADS

Next: !p682, !f683

OBSERVATION SYSTEM PUMP RUNNING

CH TEMPERATURE CONTROL SET TO OFF POSITION
LOCATE & GAIN ACCESS TO SYSTEM PUMP

Next: p688, f865

PUMP LIMPET TEST

Next: p690, !f691

RESET APPLIANCE - STATUS CODE - TEMPERATURE PROTECTION

ENSURE BOILER IS COOL

Next: p692, f716

TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

ATTACH TEMPERATURE CLAMP TO FLOW PIPE

Next: !p721, ?702, ?704

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p706, !f707

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p708, !f709

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p719, !f720

TEMPERATURE FLOW & RETURN DIFFERENTIAL

ENSURE BOILER IS COOL
ATTACH TEMPERATURE CLAMPS TO FLOW & RETURN PIPE

Next: p723, !f724

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p725, !f726

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p727, !f728

OBSERVATION SYSTEM WATER

GAIN ACCESS TO SYSTEM AS REQUIRED

Next: p839, !f764

VOLTAGE EXTERNAL CONTROLS

ATTACH A SOCKET & SEE TO THE ELECTRICAL TEST POINT

Next: p17, !f18

PUMP LIMPET TEST

Next: p808, !f809

INSPECTION SYSTEM BYPASS

Next: !p810, !f811

PUMP LIMPET TEST

Next: p813, !f814

RESET APPLIANCE - FAULT CODE - OVERHEAT

ENSURE BOILER IS COOL

Next: p815, f816

TEMPERATURE - RUN BOILER TO MAXIMUM

ATTACH TEMPERATURE CLAMP TO FLOW PIPE JUST ABOVE HEAT EXCHANGER

Next: !p823, ?825, ?827

RESISTANCE SWITCH AIR PRESSURE

GAIN ACCESS TO AIR PRESSURE SWITCH AND DISCONNECT LEADS

Next: !p821, !f822

RESISTANCE STAT OVERHEAT

GAIN ACCESS TO OVERHEAT STAT & DISCONNECT LEADS TO STAT

Next: p833, !f834

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p829, !f830

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p831, !f832

INSPECTION FLUE

Next: p835, !f836

OPERATION AIR PRESSURE SWITCH

REMOVE AIR PRESSURE SWITCH AND DISCONNECT LEADS

Next: !p837, !f838

PUMP LIMPET TEST

Next: p840, !f841

RESET APPLIANCE - STATUS CODE - TEMPERATURE PROTECTION

ENSURE BOILER IS COOL

Next: p842, f843

TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

ATTACH TEMPERATURE CLAMP TO FLOW PIPE

Next: !p848, ?850, ?852

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p846, !f847

TEMPERATURE FLOW & RETURN DIFFERENTIAL

ENSURE BOILER IS COOL
ATTACH TEMPERATURE CLAMPS TO FLOW & RETURN PIPE

Next: p858, !f859

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p854, !f855

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p856, !f857

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p860, !f861

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p862, !f863

OBSERVATION SYSTEM PUMP RUNNING

CH TEMPERATURE CONTROL SET TO OFF POSITION
LOCATE & GAIN ACCESS TO SYSTEM PUMP

Next: p899, f926

PUMP LIMPET TEST

Next: p900, !f901

RESET APPLIANCE - FAULT CODE - OVERHEAT

ENSURE BOILER IS COOL

Next: p902, f903

TEMPERATURE - RUN BOILER TO MAXIMUM

ATTACH TEMPERATURE CLAMP TO FLOW PIPE JUST ABOVE HEAT EXCHANGER

Next: !p910, ?912, ?914

RESISTANCE SWITCH AIR PRESSURE

GAIN ACCESS TO AIR PRESSURE SWITCH AND DISCONNECT LEADS

Next: !p908, !f909

RESISTANCE STAT OVERHEAT

GAIN ACCESS TO OVERHEAT STAT & DISCONNECT LEADS TO STAT

Next: p920, !f921

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p916, !f917

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p918, !f919

INSPECTION FLUE

Next: p922, !f923

OPERATION AIR PRESSURE SWITCH

REMOVE AIR PRESSURE SWITCH AND DISCONNECT LEADS

Next: !p924, !f925

INSPECTION INTERFACE AND SUMP

Next: p1000, ?1019, ?1021

System Information

  • Total Tests: 404
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control