Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
GLOW-WORM MICRON 60FF (FROM SNO 0035001)
WARNING - IMPORTA
OPERATIONAL SEQUENCE
OUTSIDE MODEL
DHW OPERATION
{BLRSTATMAX}
TYPE OF DIAGNOSTIC PROCEDURE
PLEASE SELECT FROM O
ENHANCED FAULT CODES
SELECT APPROPRIATE F
EPROM / PCB / SOFTWARE ERROR
OUTSIDE MODEL
BLOCKING ERROR
OUTSIDE MODEL
FURTHER INVESTIGATION PCB
OUTSIDE MODEL
FURTHER INVESTIGATION FUSE
NOT INSIDE MODEL
FAN RUNS WITH DEMAND
{BLRSTATMAX}
EXTERNAL CONTROLS CALLING FOR HEAT
ENSURE BOILER IS COOL
FURTHER INVESTIGATION MAINS FUSE
OUTSIDE MODEL
OBSERVATION DOES BOILER FIRE WITH NO DEMAND
ENSURE NO DEMANDS
OVERHEAT OR EARTH FAULT
OUTSIDE MODEL
BURNER IGNITION
{BLRSTATMAX}
RADIATORS PROVIDE INSUFFICIENT HEAT
GAS INLET PRESSURE
RADIATORS PROVIDE INSUFFICIENT HEAT
THERMISTOR
BOILER COOL RADIATORS COOL
BURNER INJECTOR
BOILER NOISY PUMP RUNS HIGH
PUMP EXTERNAL
DHW TOO HOT
THERMISTOR
OPERATIONAL SEQUENCE
SYSTEM CHECKS
BOILER TO TEMPERATURE RADIATORS COOL PUMP RUNS HIGH
PUMP EXTERNAL
ENHANCED FAULT CODES
SYSTEM CHECKS
PCB ERROR CODE
PCB
LED1&2 SLOW FLASH
SOCKET AND SEE
TYPE OF DIAG PROC
SYSTEM CHECKS
ELECTRICAL CHECKS
SYSTEM CHECKS
PUMP OVERRUN
PCB
FURTHER INV PCB
PUMP + PCB
FURTHER INV PCB
GAS VALVE + PCB
POLARITY FAULT
EARTH LEAD
FAN RUNS NO DEMAND
FUSE 2A
FAN RUNS WITH DEMAND
THERMISTOR
SPARKING PRESENT
AIR PRESSURE SWITCH TUBES
SPARKING PRESENT
VENTURI
NO FAN
EARTH LEAD
FAN RUNS NO DEMAND
HARNESS FAN
FAN RUNS NO DEMAND
MAINS FUSE
PUMP WIRING
SYSTEM CHECKS
FURTHER INV FUSE
GAS VALVE + MAINS FUSE
FURTHER INV FUSE
PUMP + MAINS FUSE
FURTHER INV RESISTANCES
THERMISTOR + MAINS FUSE
FURTHER INV FUSE
GAS VALVE + FUSE
FURTHER INV FUSE
PUMP + FUSE 2A
FURTHER INV RESISTANCES
THERMISTOR + FUSE
SHORTING
IGNITION ELECTRODE
BLOCKING ERROR
IGNITION LEAD ASSEMBLY
PASSING
GAS VALVE
AUTO FROST
THERMISTOR
FURTHER INV OVERHEAT LIMPET FAILED
PUMP EXTERNAL
NOT SHUTTING OFF FURTHER INV OVERHEAT
THERMISTOR
OVERHEAT FAULT
THERMISTOR
OVERHEAT INV
THERMOSTAT OVERHEAT
BURNER IGNITES BUT FLAME BAFFLES OUT OR DIES AWAY
GAS INLET PRESSURE
BURNER IGNITES BUT FLAME BAFFLES OUT OR DIES AWAY
HEAT EXCHANGER FLUE WAYS
BURNER IGNITES BUT DOES NOT ESTABLISH
IGNITION ELECTRODE AND GAP
BURNER IGNITES BUT DOES NOT ESTABLISH
HEAT EXCHANGER FLUE WAYS
BURNER IGNITES BUT DOES NOT ESTABLISH
IGNITION LEAD ASSEMBLY
NO SPARKING
AIR PRESSURE SWITCH
NO SPARKING
IGNITION ELECTRODE AND GAP
NO SPARKING
IGNITION LEAD ASSEMBLY
BURNER DOES NOT IGNITE
AIR PRESSURE SWITCH TUBES
BURNER DOES NOT IGNITE
VENTURI
UNABLE TO ADJUST SOFT LIGHT PRESSURE
GAS INLET PRESSURE
UNABLE TO ADJUST SOFT LIGHT
THERMOSTAT OVERHEAT
UNABLE TO ADJUST SOFT LIGHT
GAS VALVE + PCB
UNABLE TO ADJUST SOFT LIGHT
GAS VALVE SOLENOIDS
UNABLE TO ADJUST SOFT LIGHT
GAS VALVE
SOFT LIGHT ADJUSTMENT
GAS VALVE ADJUSTMENT
BURNER IGNITION
GAS INLET PRESSURE
BOILER DOES NOT IGNITE
THERMOSTAT OVERHEAT
BURNER DOES NOT IGNITE
GAS VALVE + PCB
BURNER DOES NOT IGNITE
GAS VALVE SOLENOIDS
BURNER IGNITION
BURNER INJECTOR
OVERHEAT THERMOSTAT
THERMOSTAT OVERHEAT WATER INGRESS
LED 1 ILLU
THERMOSTAT OVERHEAT
EARTH FAULT
SOCKET AND SEE
NO APPARENT FAULT
FUSE FURTHER INVESTIGATION (MAINS)
RADIATORS PROVIDE INSUFFICIENT HEAT
GAS VALVE
LED 1&2 SLOW FLASH
SYSTEM CHECKS
PCB ERROR CODE
SYSTEM CHECKS
BLOCKING ERROR
SYSTEM CHECKS
FURTHER INV PCB
PCB
BOILER NOISY
HEAT EXCHANGER ASSEMBLY
FURTHER INV PCB
PUMP WIRING + PCB
FURTHER INV PCB
WATER INGRESS + PCB
FURTHER INV PCB
THERMISTOR + PCB
FURTHER INV PCB
HARNESS GAS VALVE + PCB
FAN RUNS DEMAND
FAN
FURTHER INVESTIGATION FUSE
SYSTEM CHECKS
SPARKING PRESENT
AIR PRESSURE SWITCH
PCB FURTHER INVESTIGATION
SYSTEM CHECKS
FURTHER INVESTIGATION MAINS FUSE
SYSTEM CHECKS
FURTHER INV FUSE
THERMISTOR + MAINS FUSE
FURTHER INV FUSE
WATER INGRESS + MAINS FUSE
FURTHER INV FUSE
HARNESS GAS VALVE + MAINS FUSE
FURTHER INV FUSE
PUMP WIRING + MAINS FUSE
FURTHER INV FUSE
THERMISTOR + FUSE
FURTHER INV FUSE
WATER INGRESS + FUSE
FURTHER INV FUSE
HARNESS GAS VALVE + FUSE
FURTHER INV FUSE
PUMP WIRING + FUSE 2A
BLOCKING ERROR
PCB
BOILER FIRES WITH NO DEMAND
FROST PROTECTION - NORMAL OPERATION
FURTHER INV OVERHEAT NOT RUNNING
PUMP EXTERNAL
OVERHEAT LOCKOUT
OVERHEAT
OVERHEAT INV
PCB
NO SPARKING
PCB
RUNNING SLOW
FAN
UNABLE TO ADJUST SOFT LIGHT
HARNESS OVERHEAT
UNABLE TO ADJUST SOFT LIGHT
HARNESS GAS VALVE + PCB
UNABLE TO ADJUST SOFT LIGHT
HARNESS GAS VALVE
SOFT LIGHT PRESSURE INCORRECT/ABSENT
Z DIRECTION
BURNER DOES NOT IGNITE
HARNESS OVERHEAT
BURNER DOES NOT IGNITE
HARNESS GAS VALVE + PCB
BURNER DOES NOT IGNITE
GAS VALVE
BURNER DOES NOT IGNITE
HARNESS GAS VALVE
BURNER IGNITION
BURNER
LED 1 ILLU
PCB
OVERHEAT
HARNESS OVERHEAT
NO FAULT
FUSE FURTHER INVESTIGATION
Boiler to temperature, radiators cool
CHARACTERISTIC TEST FROM CH OPERATION
RADIATORS HEAT BUT BOILER NOISY
CHARACTERISTIC TEST FROM CH OPERATION
Boiler cool, radiators cool
CHARACTERISTIC TEST FROM CH OPERATION
DHW too cool
CHARACTERISTIC TEST FROM DHW OPERATION
DHW too hot
CHARACTERISTIC TEST FROM DHW OPERATION
Boiler does not react to DHW demand
CHARACTERISTIC TEST FROM DHW OPERATION
RESISTANCE TO EARTH LOW OR SHORT CIRCUIT
CHARACTERISTIC TEST FROM RESISTANCE THERMISTOR TO EARTH
WATER INGRESS IN THERMISTOR POCKET
CHARACTERISTIC TEST FROM RESISTANCE THERMISTOR TO EARTH
RESISTANCE TO EARTH LOW OR SHORT CIRCUIT
CHARACTERISTIC TEST FROM RESISTANCE THERMISTOR TO EARTH
WATER INGRESS IN THERMISTOR POCKET
CHARACTERISTIC TEST FROM RESISTANCE THERMISTOR TO EARTH
RESISTANCE TO EARTH LOW OR SHORT CIRCUIT
CHARACTERISTIC TEST FROM RESISTANCE THERMISTOR TO EARTH
WATER INGRESS IN THERMISTOR POCKET
CHARACTERISTIC TEST FROM RESISTANCE THERMISTOR TO EARTH
BOILER GOES TO LOCKOUT BEFORE REACHING TEMPERATURE
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER TO TEMP
BOILER CONTINUES FIRING PAST 85 DEGREES C
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER TO TEMP
Burner does not ignite
CHARACTERISTIC TEST FROM BURNER IGNITION
BURNER IGNITES BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM BURNER IGNITION
BURNER IGNITES BUT BAFFLES OUT
CHARACTERISTIC TEST FROM BURNER IGNITION
SOFT LIGHT PRESSURE CORRECT BUT BURNER PRESSURE INCORRECT
CHARACTERISTIC TEST FROM PRESSURE BURNER AND SOFT LIGHT
SOFT LIGHT PRESSURE INCORRECT/ABSENT
CHARACTERISTIC TEST FROM PRESSURE BURNER AND SOFT LIGHT
07/10/2019 13:57:28 1908_1_50_1 22/10/2019 13:04:15
07/10/2019 14:47:36
GAS INLET PRESSURE
ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT
EXTERNAL CONTROLS CALLING
SOCKET AND SEE TEST
GAIN ACCESS TO APPLIANCE TERMINAL STRIP
RESISTANCE THERMISTOR TO EARTH
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
RESISTANCE PUMP
DISCONNECT WIRES FROM PUMP
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR PLUG FROM THE GAS VALVE
MAINS POWER SUPPLY FUSE
REMOVE THE FUSE FROM THE APPLIANCE MAINS POWER SUPPLY I.E. FUSED SPUR
FUSE FURTHER INVESTIGATION
THE INFORMATION PROV
MAINS FUSE FURTHER INVESTIGATION
THE INFORMATION PROV
THERMISTOR
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR PLUG FROM THE GAS VALVE
RESISTANCE PUMP
DISCONNECT WIRES FROM PUMP
THERMISTOR
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR PLUG FROM THE GAS VALVE
RESISTANCE PUMP
DISCONNECT WIRES FROM PUMP
RESISTANCE ELECTRODE TO EARTH
DISCONNECT THE SPARK ELECTRODE FROM THE IGNITION LEAD ASSEMBLY CONNECTOR
THERMISTOR
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
OBSERVATION BOILER RESET OVERHEAT
ENSURE BOILER IS COOL
PRESSURE APS SWITCHING
DISCONNECT LEADS FROM THE AIR PRESSURE SWITCH NOTING THE CONNECTIONS
IGNITION ELECTRODE AND GAP
DISCONNECT THE IGNITION LEAD TO THE ELECTRODE
RESISTANCE OVERHEAT THERMOSTAT AND HARNESS
REMOVE THE OVERHEAT CONNECTOR FROM THE PCB
THIS IS THE CONNECTOR WHICH HAS THE 2 BROWN WIRES
OVERHEAT THERMOSTAT
REMOVE ONE OF THE BROWN LEADS FROM THE OVERHEAT THERMOSTAT
ENSURE APPLIANCE IS COOL
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR PLUG FROM THE GAS VALVE
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR PLUG FROM THE GAS VALVE
RESISTANCE OVERHEAT THERMOSTAT AND HARNESS
REMOVE THE OVERHEAT CONNECTOR FROM THE PCB
THIS IS THE CONNECTOR WHICH HAS THE 2 BROWN WIRES
OVERHEAT THERMOSTAT
REMOVE ONE OF THE BROWN LEADS FROM THE OVERHEAT THERMOSTAT
ENSURE APPLIANCE IS COOL
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR PLUG FROM THE GAS VALVE
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR PLUG FROM THE GAS VALVE
SOCKET AND SEE TEST
GAIN ACCESS TO APPLIANCE TERMINAL STRIP
OVERHEAT THERMOSTAT
REMOVE ONE OF THE BROWN LEADS FROM THE OVERHEAT THERMOSTAT
ENSURE APPLIANCE IS COOL
BURNER PRESSURE
{BLRSTATMAX}
ATTACH PRESSURE GAUGE TO BURNER PRESSURE TEST POINT
THERMISTOR
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
THERMISTOR
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
RESISTANCE GAS VALVE AND HARNESS TO EARTH
DISCONNECT THE GAS V
FUSE 2A
REMOVE THE FUSE FROM THE PCB
THERMISTOR
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
AIR PRESSURE SWITCH N/O
REMOVE THE LEADS FROM THE AIR PRESSURE SWITCH (MAKE A NOTE OF THE CONNECTIONS)
FAN HARNESS
DISCONNECT THE BLUE AND PURPLE LEADS FROM THE FAN
DISCONNECT THE 5 PIN PLUG AT THE PCB
PCB FURTHER INVESTIGATION
THE INFORMATION PROV
RESISTANCE THERMISTOR TO EARTH
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
RESISTANCE GAS VALVE AND HARNESS TO EARTH
DISCONNECT THE GAS V
RESISTANCE THERMISTOR TO EARTH
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
RESISTANCE GAS VALVE AND HARNESS TO EARTH
DISCONNECT THE GAS V
RESISTANCE IGNITION LEAD
DISCONNECT THE IGNITION LEAD ASSEMBLY CONNECTOR FROM THE SPARK ELECTRODE AND FROM THE PCB
OBSERVATION GAS VALVE PASSING
REMOVE BURNER
CONNECT U-GAUGE TO BURNER INJECTOR
VOLTAGE AT SWITCH LIVE (LS)
GAIN ACCESS TO THE MAIN CONNECTOR BLOCK AT THE FRONT OF THE CONTROL BOX
OBSERVATION RUN BOILER TO TEMP
{BLRSTATMAX}
ALLOW BOILER TO RUN AND BURNER TO IGNITE
THERMISTOR
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
THERMISTOR
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
RESISTANCE OVERHEAT STAT AT TEMP
{BLRSTATMAX}
SPARKING PRESENT
EXTERNAL CONTROLS CALLING FOR HEAT
REMOVE THE COMBUSTION CHAMBER COVER
FAN RUNS AT HIGH SPEED
EXTERNAL CONTROLS CALLING FOR HEAT
FAN RUNS AT HIGH SPEED
EXTERNAL CONTROLS CALLING FOR HEAT
GAS INLET PRESSURE
ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT
EXTERNAL CONTROLS CALLING
IGNITION ELECTRODE AND GAP
DISCONNECT THE IGNITION LEAD TO THE ELECTRODE
IGNITION LEAD ASSEMBLY
DISCONNECT THE IGNITION LEAD ASSEMBLY CONNECTOR
FROM THE PCB AND ELECTRODE
PRESSURE BURNER AND SOFT LIGHT
{BLRSTATMAX}
ATTACH PRESSURE GAUGE TO BURNER PRESSURE TEST POINT
RESISTANCE IGNITION LEAD
DISCONNECT THE IGNITION LEAD ASSEMBLY CONNECTOR
FROM THE PCB AND ELECTRODE
GAS INLET PRESSURE
ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT
EXTERNAL CONTROLS CALLING
GAS INLET PRESSURE
ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT
EXTERNAL CONTROLS CALLING
GAS VALVE VOLTAGE
EXTERNAL CONTROLS CA
RESISTANCE GAS VALVE AND HARNESS TO EARTH
DISCONNECT THE GAS V
RESISTANCE GAS VALVE AND HARNESS TO EARTH
DISCONNECT THE GAS V
OBSERVATION CAN SOFT LIGHT PRESSURE BE ADJUSTED
{BLRSTATMAX}
ATTACH PRESSURE GAUGE TO BURNER PRESSURE TEST POINT
SOFT LIGHT PRESSURE CORRECTLY ADJUSTED
THE SOFT LIGHT PRESS
GAS VALVE VOLTAGE
EXTERNAL CONTROLS CA
RESISTANCE GAS VALVE AND HARNESS TO EARTH
DISCONNECT THE GAS V
RESISTANCE GAS VALVE AND HARNESS TO EARTH
DISCONNECT THE GAS V
RESISTANCE OVERHEAT THERMOSTAT AND HARNESS
REMOVE THE OVERHEAT CONNECTOR FROM THE PCB
THIS IS THE CONNECTOR WHICH HAS THE 2 BROWN WIRES
OBSERVATION REMOVE PERMANENT MAINS SUPPLY TO APPLIANCE
REMOVE THE MAINS SUP
System Information
- Total Tests: 279
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control