GLOWWORM ULTRACOM 2 SXI

GLOBALLY REPLACED

Next: &1, *

NO FAULT FOUND

Next: nff

CASE REMOVAL

Next: &1599, !f2

POWER UP SELF TEST

ENSURE NO DEMANDS ARE PRESENT

Next: &715, ?10, ?1865

OBSERVATION BURNER IGNITION & ESTABLISH

Next: &335, ?110, ?112, ?114, ?1635

OBSERVATION FAN RUNS - CH DEMAND

ENSURE BOILER IS COOL

Next: &2803, ?88, ?90

COMBUSTION CHECK

CONNECT FGA TO THE COMBUSTION TEST POINT ON THE BOILER
ENSURE CH SYSTEM IS COOL

Next: &nff, f483

CH OPERATION

Next: &2363, ?338, ?2317, ?2335, ?2368

TEST MODES

NOT USED

Next: &nff, f555

INSTALLATION SETTINGS

NOT USED

Next: &nff, f596

INITIAL SETUP

Next: &3, !f716

FAULT CODE F00/F10

NOT USED

Next: &nff, f735

FAULT CODE F23 - F24

NOT USED

Next: &nff, f1060

FAULT CODE F20

NOT USED

Next: &nff, f1199

FAULT CODE F01/F11

NOT USED

Next: &nff, f747

FAULT CODE F84

NOT USED

Next: &nff, f839

FAULT CODE F83

NOT USED

Next: &nff, f782

FAULT CODE F76

NOT USED

Next: &nff, f1378

FAULT CODE F73 - F74

NOT USED

Next: &nff, f931

FAULT CODE F71

NOT USED

Next: &nff, f1192

FAULT CODE F70

NOT USED

Next: &nff, f1422

FAULT CODE F61 TO F67

NOT USED

Next: &nff, f1388

FAULT CODE F49

NOT USED

Next: &nff, f1361

FAULT CODE F32

NOT USED

Next: &nff, f1152

FAULT CODE F26/F77

NOT USED

Next: &nff, f1142

FAULT CODE ERR

NOT USED

Next: &nff, f1582

FAULT CODE F86

NOT USED

Next: &nff, f1172

FAULT CODE F22

NOT USED

Next: &nff, f948

FACTORY RESET

NOT USED

Next: &nff, f1160

FAULT CODE HISTORY

NOT USED

Next: &nff, f1594

OBSERVATION DISPLAY

ON/OFF SWITCH ON (RECESSED POSITION, PUSHED IN)

Next: &7, ?1600, ?1631, ?1674, ?2110

STATUS CODES

NOT USED

Next: &nff, f1671

OPERATION DHW

Next: &334, ?2364, ?2366

HEADER FOR QADAI FLOW THERMISTOR

NOT USED

Next: &nff, f2752

QUICK ACCESS DATA AND INFORMATION

THE TABLE BELOW SHOW

Next: &nff, !f2756

LITE DIAGNOSTIC

DIAGNOSIS RELIES ON

Next: &nff, !f2758

HEADER FOR QADAI RETURN THERMISTOR

NOT USED

Next: &nff, f2760

HEADER FOR QADAI RESISTANCE GAS VALVE

NOT USED

Next: &nff, f2764

HEADER FOR QADAI VOLTAGE GAS VALVE

NOT USED

Next: &nff, f2768

HEADER FOR QADAI PRESSURE SENSOR

NOT USED

Next: &nff, f2772

HEADER FOR QADAI FAN VOLTAGE

NOT USED

Next: &nff, f2776

HEADER FOR QADAI PUMP VOLTAGE

NOT USED

Next: &nff, f2780

HEADER FOR QADAI PUMP AND HARNESS ERP

NOT USED

Next: &nff, f2788

HEADER FOR QADAI PUMP VOLTAGE ERP

NOT USED

Next: &nff, f2792

FUSE FURTHER INVESTIGATION

NOT USED

Next: &nff, f2796

OBSERVATION PUMP RUNS

Next: &31, f2804

FAN DOES NOT RUN

SENSOR - TEMPERATURE

Next: End

FAN DOES NOT RUN 2

SENSOR - TEMPERATURE

Next: End

FAN DOES NOT RUN

PCB - MAIN

Next: End

FAULT CODE F23 - F24

SENSOR - TEMPERATURE INSTALLATION

Next: End

FAULT CODE F23 - F24

MOTOR/PUMP

Next: End

FAN DOES NOT RUN

HARNESS DIN - MAIN

Next: End

FAULT CODE F23 - F24

SENSOR - TEMPERATURE

Next: End

FAULT CODE F23 - F24 2

SENSOR - TEMPERATURE

Next: End

FAULT CODE F23 - F24 4

SENSOR - TEMPERATURE

Next: End

FAULT CODE F23 - F24 3

SENSOR - TEMPERATURE

Next: End

FAULT CODE F26

GAS VALVE

Next: End

FAULT CODE F26

PCB - MAIN

Next: End

FACTORY RESET

Z REDIRECTION

Next: End

FAULT CODE F86

WIRE LINK UNDER FLOOR HEATING

Next: End

FAULT CODE F86

UNDER FLOOR SENSOR

Next: End

FAULT CODE F86

PCB - MAIN

Next: End

FAULT CODE F86 2

PCB - MAIN

Next: End

FAULT CODE F71

SENSOR - TEMPERATURE INSTALLATION

Next: End

FAULT CODE F71

SENSOR - TEMPERATURE

Next: End

FAULT CODE F71

PCB - MAIN

Next: End

FAULT CODE F20

SENSOR - TEMPERATURE

Next: End

FAULT CODE F20 2

SENSOR - TEMPERATURE

Next: End

FAULT CODE F20

SENSOR - TEMPERATURE INSTALLATION

Next: End

FAULT CODE F20

VALVE ISOLATION

Next: End

SELF TEST

FROST PROTECTION NORMAL OPERATION

Next: End

FAULT CODE F20 4

MOTOR/PUMP

Next: End

FAULT CODE F32 3

PCB - MAIN

Next: End

FAULT CODE F32

PCB - MAIN

Next: End

FAULT CODE F32

HARNESS DIN - MAIN

Next: End

FAULT CODE F32 2

PCB - MAIN

Next: End

FAULT CODE F49

PCB - MAIN

Next: End

FAULT CODE F49 2

PCB - MAIN

Next: End

FAULT CODE F83

MOTOR/PUMP

Next: End

FAULT CODE F76

CABLE - SENSOR TO HARNESS - HEAT EXCHANGER

Next: End

FAULT CODE F76

PCB - MAIN

Next: End

FAULT CODE F70

PCB - MAIN

Next: End

FAULT CODE F70

MAIN DSN NUMBER

Next: End

SELF TEST

SENSOR - TEMPERATURE

Next: End

FAULT CODE ERR

CABLE - A1

Next: End

BURNER DOES NOT IGNITE

PCB - MAIN & GAS VALVE

Next: End

FAULT CODE HISTORY

Z REDIRECTION

Next: End

NO DISPLAY

FUSE (FUSED SPUR)

Next: End

NO DISPLAY

SYSTEM PRESSURE SENSOR

Next: End

NO DISPLAY

FAN

Next: End

FAULT CODES

Z REDIRECTION

Next: End

STATUS CODES

Z REDIRECTION

Next: End

BOILER FIRES SELF TEST

PCB - MAIN

Next: End

BOILER FIRES SELF TEST 2

PCB - MAIN

Next: End

SELF TEST 3

PCB - MAIN

Next: End

SELF TEST 2

PCB - MAIN

Next: End

LOW PRESSURE

SYSTEM PRESSURE

Next: End

CASE OFF

DIRECTION CHOICE OR CONTINUE

Next: End

DHW COOL RADS COOL

MOTOR/PUMP

Next: End

DHW COOL RADS COOL

AIR BOX

Next: End

NO DISPLAY

FUSE PCB

Next: End

NO DISPLAY

PCB - MAIN

Next: End

BURNER DOES NOT IGNITE 2

HARNESS DIN - MAIN

Next: End

RESET OPTION

Z REDIRECTION

Next: End

BURNER DOES NOT IGNITE 3

HARNESS DIN - MAIN

Next: End

BURNER DOES NOT IGNITE 4

HARNESS DIN - MAIN

Next: End

BURNER DOES NOT ESTABLISH

PCB - MAIN

Next: End

BURNER DOES NOT ESTABLISH

ELECTRODE - IGNITION

Next: End

BURNER DOES NOT ESTABLISH

HARNESS DIN - MAIN

Next: End

DOES NOT EST

SYPHON

Next: End

DHW COOL RADS COOL

GAS INLET PRESSURE

Next: End

FAULT CODE F83 2

SENSOR - TEMPERATURE

Next: End

FAULT CODE F83

SENSOR - TEMPERATURE

Next: End

FAULT CODE F83 4

SENSOR - TEMPERATURE

Next: End

FAULT CODE F83 3

SENSOR - TEMPERATURE

Next: End

FAULT CODE F61-67

GAS VALVE

Next: End

FAULT CODE F61 - 67

PCB - MAIN & GAS VALVE

Next: End

FAULT CODE F61 - 67

MAIN CONNECTIONS

Next: End

FAULT CODE F61 - 67

MAIN DSN NUMBER

Next: End

FAULT CODE F61 - 67

PCB - MAIN

Next: End

FAN DOES NOT RUN

SENSOR - TEMPERATURE INSTALLATION

Next: End

FAN DOES NOT RUN 4

SENSOR - TEMPERATURE

Next: End

FAN DOES NOT RUN 3

SENSOR - TEMPERATURE

Next: End

FAN DOES NOT RUN 1

SENSOR - TEMPERATURE INSTALLATION

Next: End

FAN DOES NOT RUN 4 1

SENSOR - TEMPERATURE

Next: End

FAN DOES NOT RUN 3 1

SENSOR - TEMPERATURE

Next: End

FAN DOES NOT RUN 2

SENSOR - TEMPERATURE INSTALLATION

Next: End

FAN DOES NOT RUN 4 2

SENSOR - TEMPERATURE

Next: End

FAN DOES NOT RUN 3 2

SENSOR - TEMPERATURE

Next: End

FAN DOES NOT RUN 3

SENSOR - TEMPERATURE INSTALLATION

Next: End

FAN DOES NOT RUN 4 3

SENSOR - TEMPERATURE

Next: End

FAN DOES NOT RUN 3 3

SENSOR - TEMPERATURE

Next: End

FAN DOES NOT RUN 4

SENSOR - TEMPERATURE INSTALLATION

Next: End

FAN DOES NOT RUN 4 4

SENSOR - TEMPERATURE

Next: End

FAN DOES NOT RUN 3 4

SENSOR - TEMPERATURE

Next: End

RADS DO NOT HEAT

VALVE ISOLATION

Next: End

RADS DO NOT HEAT

MOTOR/PUMP

Next: End

SYSTEM PRESSURE RISES

EXPANSION VESSEL

Next: End

RADS DO NOT HEAT

BYPASS

Next: End

RADS DO NOT HEAT

Next: End

RAD TEMP LOW

SENSOR - TEMPERATURE

Next: End

RAD TEMP LOW 2

SENSOR - TEMPERATURE

Next: End

BURNER DOES NOT IGNITE

GAS INLET PRESSURE

Next: End

FAULT CODE F23 - F24 2

VALVE ISOLATION

Next: End

FAULT CODE F20

PCB - MAIN - PUMP OVER-RUN

Next: End

BURNER DOES NOT IGNITE 2

GAS VALVE

Next: End

BURNER DOES NOT IGNITE 2

ELECTRODE - IGNITION

Next: End

BURNER DOES NOT IGNITE

FLUE

Next: End

BURNER DOES NOT IGNITE

BURNER

Next: End

BURNER DOES NOT IGNITE

HEAT EXCHANGER

Next: End

SELF TEST 2

SENSOR - TEMPERATURE

Next: End

FAULT CODE F20 4

SENSOR - TEMPERATURE

Next: End

FAULT CODE F20 3

SENSOR - TEMPERATURE

Next: End

DHW COOL RADS COOL

SENSOR - TEMPERATURE INSTALLATION

Next: End

DHW COOL RADS COOL

SENSOR - TEMPERATURE

Next: End

DHW COOL RADS COOL 2

SENSOR - TEMPERATURE

Next: End

DHW COOL RADS COOL UNABLE TO GAS RATE

MAIN DSN NUMBER

Next: End

CH RAD TEMP LOW UNABLE TO GAS RATE

ADJUSTMENT PARAMETER SETTING

Next: End

DHW COOL RADS COOL

MAIN DSN NUMBER

Next: End

CH RAD TEMP LOW

ADJUSTMENT PARAMETER SETTING

Next: End

F23 - F24

Next: End

F23 - F24

BYPASS

Next: End

BURNER DOES NOT IGNITE

SYPHON

Next: End

F20

Next: End

F20

BYPASS

Next: End

F83

Next: End

F83

BYPASS

Next: End

F84 - RUNNING SLOW

MOTOR/PUMP

Next: End

F70 HAD TO SAVE INCORRECT DS NUMBER FIRST

MAIN DSN NUMBER

Next: End

FAULT CODE F32 2

HARNESS DIN - MAIN

Next: End

FAULT CODE F32 2

FAN

Next: End

FAULT CODE F32 3

HARNESS DIN - MAIN

Next: End

FAULT CODE F32 3

FAN

Next: End

QADAI FLOW

SENSOR - TEMPERATURE

Next: End

BLANK FOR QADAI

Z REDIRECTION

Next: End

BLANK FOR LITE DIAGNOSTIC

Z REDIRECTION

Next: End

QADAI RETURN

SENSOR - TEMPERATURE

Next: End

QADAI

GAS VALVE

Next: End

QADAI VOLTAGE TO GAS VALVE

PCB - MAIN

Next: End

FAN QADAI

PCB - MAIN

Next: End

QADAI

PCB - MAIN

Next: End

QADAI

MOTOR/PUMP

Next: End

QADAI RESISTANCE

MOTOR/PUMP ERP

Next: End

NO VOLTAGE TO ERP PUMP

PCB - MAIN

Next: End

FUSE FURTHER INVESTIGATION

MOTOR/PUMP

Next: End

ERP FUSE FURTHER INVESTIGATION

MOTOR/PUMP ERP

Next: End

PUMP DOES NOT RUN

MOTOR/PUMP

Next: End

BURNER NOISY/ BAFFLES OUT

SYPHON

Next: End

PUMP DOES NOT RUN

PCB - MAIN

Next: End

ERP PUMP NOT RUNNING

PUMP CABLE (ERP)

Next: End

PUMP NOT RUNNING ERP

PCB - MAIN

Next: End

PUMP DOES NOT RUN 5

MOTOR/PUMP

Next: End

PUMP DOES NOT RUN 1

PCB - MAIN

Next: End

ERP FAULT CODE F20

PUMP CABLE (ERP)

Next: End

PUMP NOT RUNNING ERP F20

PCB - MAIN

Next: End

BURNER NOISY/ BAFFLES OUT

GAS INLET PRESSURE

Next: End

PUMP DOES NOT RUN 8

MOTOR/PUMP

Next: End

PUMP DOES NOT RUN 2

PCB - MAIN

Next: End

ERP FAULT CODE F23 F24

PUMP CABLE (ERP)

Next: End

PUMP NOT RUNNING ERP F23 F24

PCB - MAIN

Next: End

PUMP DOES NOT RUN 4

MOTOR/PUMP

Next: End

PUMP DOES NOT RUN 3

PCB - MAIN

Next: End

ERP FAULT CODE F83

PUMP CABLE (ERP)

Next: End

PUMP NOT RUNNING ERP F83

PCB - MAIN

Next: End

PUMP DOES NOT RUN 7

MOTOR/PUMP

Next: End

PUMP DOES NOT RUN 4

PCB - MAIN

Next: End

ERP FAULT CODE F84

PUMP CABLE (ERP)

Next: End

PUMP NOT RUNNING ERP F84

PCB - MAIN

Next: End

QADAI

SYSTEM PRESSURE SENSOR

Next: End

BURNER NOISY/ BAFFLES OUT

AIR BOX

Next: End

BURNER NOISY/ BAFFLES OUT

FLUE

Next: End

BURNER NOISY/ BAFFLES OUT

BURNER

Next: End

BURNER NOISY/ BAFFLES OUT

HEAT EXCHANGER

Next: End

BURNER DOES NOT IGNITE

AIR BOX

Next: End

TYPE DIAG PROCEDURE

DIRECTION CHOICE OR CONTINUE

Next: End

COMBUSTION CHECK

GAS INLET PRESSURE

Next: End

AIR/GAS RATIO INCORRECT

FLUE

Next: End

AIR/GAS RATIO INCORRECT

COMBUSTION SEALS

Next: End

AIR/GAS RATIO INCORRECT

AIR BOX

Next: End

AIR/GAS RATIO INCORRECT

SYPHON

Next: End

AIR/GAS RATIO INCORRECT

BURNER

Next: End

AIR/GAS RATIO INCORRECT

HEAT EXCHANGER

Next: End

TEST MODE

DIRECTION CHOICE OR CONTINUE

Next: End

INSTALLATION SETTINGS

DIRECTION CHOICE OR CONTINUE

Next: End

INITIAL SET UP

DIRECTION CHOICE OR CONTINUE

Next: End

FAULT CODE F00/F10

PCB - MAIN

Next: End

FAULT CODE F00/F10

SENSOR - TEMPERATURE

Next: End

FAULT CODE F01/F11

SENSOR - TEMPERATURE

Next: End

FAULT CODE F01/F11

PCB - MAIN

Next: End

FAULT CODE F83

SENSOR - TEMPERATURE INSTALLATION

Next: End

FAULT CODE F84

SENSOR - TEMPERATURE INSTALLATION

Next: End

FAULT CODE F84

SENSOR - TEMPERATURE

Next: End

FAULT CODE F84 2

SENSOR - TEMPERATURE

Next: End

FAULT CODE F84

PCB - MAIN

Next: End

FAULT CODE F84 2

PCB - MAIN

Next: End

FAULT CODE F73 - F74

PCB - MAIN

Next: End

FAULT CODE F73 - F74

HARNESS DIN - MAIN

Next: End

FAULT CODE F73 - F74 2

PCB - MAIN

Next: End

FAULT CODE F22

PCB - MAIN

Next: End

FAULT CODE F22 2

PCB - MAIN

Next: End

FAN DOES NOT RUN 2

PCB - MAIN

Next: End

BOILER RESET

FAULT CODE F22

Next: End

FAN DOES NOT RUN

FAN

Next: End

FAULT CODE F23 - F24 2

PCB - MAIN

Next: End

FAULT CODE F26

HARNESS DIN - MAIN

Next: End

FAULT CODE F26

FAULT CODE RESET

Next: End

FACTORY RESET

DIRECTION CHOICE OR CONTINUE

Next: End

FAULT CODE F86

FAULT CODE RESET

Next: End

FAULT CODE F86 2

FAULT CODE RESET

Next: End

FAULT CODE F71

FAULT CODE RESET

Next: End

FAULT CODE F20

PCB - MAIN

Next: End

FAULT CODE F32

FAN

Next: End

FAULT CODE F32

FAULT CODE RESET

Next: End

FAULT CODE RESET - F49

FAULT CODE RESET - F49

Next: End

FAULT CODE F49

EBUS CONTROLS

Next: End

FAULT CODE F76

FAULT CODE RESET

Next: End

HEAT EXCHANGER - THERMAL FUSE

HEAT EXCHANGER - THERMAL FUSE

Next: End

FAULT CODE F70

FAULT CODE RESET

Next: End

FAULT CODE F70

FACTORY RESET

Next: End

FAULT CODE F70

DIRECTION CHOICE OR CONTINUE

Next: End

FAULT CODE ERR

FAULT CODE RESET

Next: End

FAULT CODE ERR

FACTORY RESET

Next: End

FAULT CODE ERR

PCB - INTERFACE

Next: End

FAULT CODE HISTORY

DIRECTION CHOICE OR CONTINUE

Next: End

NO DISPLAY

Next: End

FUSE FURTHER INVESTIGATION

Z REDIRECTION

Next: End

FAULT CODES

DIRECTION CHOICE OR CONTINUE

Next: End

BURNER DOES NOT IGNITE

PCB - MAIN - HARNESS DIN - MAIN

Next: End

STATUS CODES

DIRECTION CHOICE OR CONTINUE

Next: End

BOILER FIRES SELF TEST 2

INTERNAL PROGRAMMER

Next: End

SELF TEST

EBUS CONTROLS

Next: End

SELF TEST 2

EBUS CONTROLS

Next: End

LOW SYSTEM PRESSURE

Z REDIRECTION

Next: End

NO DISPLAY

DIRECTION CHOICE OR CONTINUE

Next: End

NO DISPLAY 2

PCB - INTERFACE

Next: End

BURNER DOES NOT IGNITE 2

FAN

Next: End

RESET OPTIONS

DIRECTION CHOICE OR CONTINUE

Next: End

BURNER DOES NOT IGNITE

SPARK GENERATOR

Next: End

BURNER DOES NOT IGNITE 2

PCB - MAIN

Next: End

BURNER DOES NOT ESTABLISH 2

PCB - MAIN

Next: End

BURNER DOES NOT ESTABLISH

SPARK GENERATOR

Next: End

FAULT CODE F83

PCB - MAIN

Next: End

FAULT CODE F61 - 67

FAULT CODE RESET

Next: End

FAULT CODE F61 - 67

PCB - MAIN - HARNESS DIN - MAIN

Next: End

FAULT CODE F61 TO F67

DIRECTION CHOICE OR CONTINUE

Next: End

FAULT CODE F61 - 67

FACTORY RESET

Next: End

CH DOES NOT RESPOND

EBUS CONTROLS

Next: End

CH DOES NOT RESPOND 6

INTERNAL PROGRAMMER

Next: End

CH DOES NOT RESPOND 8

INTERNAL PROGRAMMER

Next: End

DHW NOT RECOGNISED 2

PCB - MAIN

Next: End

DHW NOT RECOGNISED 2 1

PCB - MAIN

Next: End

DHW NOT RECOGNISED 2 2

PCB - MAIN

Next: End

DHW NOT RECOGNISED 2 3

PCB - MAIN

Next: End

DHW NOT RECOGNISED 2 4

PCB - MAIN

Next: End

SYSTEM PRESSURE RISES

PIPE EXPANSION VESSEL

Next: End

RADS DO NOT HEAT

Next: End

NO SUPPLY

Next: End

OPERATION DHW

Next: End

RAD TEMP LOW

PCB - MAIN

Next: End

BURNER DOES NOT IGNITE

ELECTRODE - IGNITION

Next: End

BURNER DOES NOT IGNITE

PCB - MAIN

Next: End

FAULT CODE F23 - F24

FAULT CODE RESET

Next: End

FAULT CODE F20

FAULT CODE RESET

Next: End

FAULT CODE F20 2

PCB - MAIN

Next: End

FAULT CODE F20 3

PCB - MAIN

Next: End

LOW SYSTEM PRESSURE 2

SYSTEM PRESSURE SENSOR

Next: End

LOW SYSTEM PRESSURE

SYSTEM PRESSURE SENSOR

Next: End

LOW SYSTEM PRESSURE

BLOCK - OUTLET ASSEMBLY

Next: End

FAULT CODE F20

SYSTEM PRESSURE SENSOR

Next: End

FAULT CODE F20 2

SYSTEM PRESSURE SENSOR

Next: End

FAULT CODE F20

BLOCK - OUTLET ASSEMBLY

Next: End

DHW COOL RADS COOL 2

SYSTEM PRESSURE SENSOR

Next: End

DHW COOL RADS COOL

SYSTEM PRESSURE SENSOR

Next: End

DHW COOL RADS COOL

BLOCK - OUTLET ASSEMBLY

Next: End

BURNER DOES NOT IGNITE

HARNESS DIN - MAIN

Next: End

DHW RADS DO NOT HEAT

SYSTEM PRESSURE SENSOR

Next: End

DHW RADS DO NOT HEAT 2

SYSTEM PRESSURE SENSOR

Next: End

DHW RADS DO NOT HEAT

BLOCK - OUTLET ASSEMBLY

Next: End

FAULT CODE F22

SYSTEM PRESSURE SENSOR

Next: End

FAULT CODE F22 2

SYSTEM PRESSURE SENSOR

Next: End

FAULT CODE F22

BLOCK - OUTLET ASSEMBLY

Next: End

FAULT CODE F23 - F24

SYSTEM PRESSURE SENSOR

Next: End

FAULT CODE F23 - F24 2

SYSTEM PRESSURE SENSOR

Next: End

FAULT CODE F23 - F24

BLOCK - OUTLET ASSEMBLY

Next: End

FAULT CODE F73 - F74 2

SYSTEM PRESSURE SENSOR

Next: End

FAULT CODE F73 - F74 3

SYSTEM PRESSURE SENSOR

Next: End

FAULT CODE F73 - F74

BLOCK - OUTLET ASSEMBLY

Next: End

FAULT CODE F83

SYSTEM PRESSURE SENSOR

Next: End

FAULT CODE F83 2

SYSTEM PRESSURE SENSOR

Next: End

FAULT CODE F83

BLOCK - OUTLET ASSEMBLY

Next: End

BURNER DOES NOT IGNITE

GAS VALVE

Next: End

DHW COOL RADS COOL - GAS RATE LOW

PCB - MAIN

Next: End

DHW COOL RADS COOL UNABLE TO GAS RATE

DIRECTION CHOICE OR CONTINUE

Next: End

RAD TEMP LOW UNABLE TO GAS RATE

Z REDIRECTION

Next: End

DHW COOL RADS COOL

PCB - MAIN

Next: End

DHW COOL RADS COOL 3

PCB - MAIN

Next: End

DHW COOL RADS COOL

DIRECTION CHOICE OR CONTINUE

Next: End

RAD TEMP LOW

Z REDIRECTION

Next: End

FAULT CODE F23 - F24

SYSTEM RESTRICTION OR BLOCKAGE

Next: End

F20

SYSTEM RESTRICTION OR BLOCKAGE

Next: End

CONTINUES TO FIRE BUT RADS COOL

SYSTEM RESTRICTION OR BLOCKAGE

Next: End

F83

SYSTEM RESTRICTION OR BLOCKAGE

Next: End

FAULT CODE F32 4

PCB - MAIN

Next: End

FAULT CODE F32 5

PCB - MAIN

Next: End

FLOW THERMISTOR

RESULT AS EXPECTED

Next: End

RETURN THERMISTOR

RESULT AS EXPECTED

Next: End

GAS VALVE

RESULT AS EXPECTED

Next: End

GAS VALVE VOLTAGE

RESULT AS EXPECTED

Next: End

SENSOR FLOW

RESULT AS EXPECTED

Next: End

FAN

RESULT AS EXPECTED

Next: End

PUMP VOLTAGE

RESULT AS EXPECTED

Next: End

MOTOR/PUMP

RESULT AS EXPECTED

Next: End

ERP PUMP

RESULT AS EXPECTED

Next: End

PUMP VOLTAGE ERP

RESULT AS EXPECTED

Next: End

NO DISPLAY

FUSE FURTHER INVESTIGATION

Next: End

NO DISPLAY ERP

FUSE FURTHER INVESTIGATION

Next: End

PUMP DOES NOT RUN 2

MOTOR/PUMP

Next: End

ERP 1

MOTOR/PUMP ERP

Next: End

PUMP DOES NOT RUN 1

MOTOR/PUMP

Next: End

ERP FAULT CODE F20

MOTOR/PUMP ERP

Next: End

PUMP DOES NOT RUN 3

MOTOR/PUMP

Next: End

ERP FAULT CODE F23 F24

MOTOR/PUMP ERP

Next: End

PUMP DOES NOT RUN 9

MOTOR/PUMP

Next: End

ERP FAULT CODE F83

MOTOR/PUMP ERP

Next: End

PUMP DOES NOT RUN 6

MOTOR/PUMP

Next: End

ERP FAULT CODE F84

MOTOR/PUMP ERP

Next: End

BURNER NOISY/ BAFFLES OUT

GAS VALVE

Next: End

SELF TEST

PCB - MAIN

Next: End

GAS RATIO ADJUSTMENT

GAS VALVE ADJUSTMENT

Next: End

AIR/GAS RATIO INCORRECT

GAS VALVE

Next: End

TEST MODE

Z REDIRECTION

Next: End

INSTALLATION SETTINGS

Z REDIRECTION

Next: End

FAULT CODE F00/F10

FAULT CODE RESET

Next: End

FAULT CODE F00/F10

HARNESS DIN - MAIN

Next: End

FAULT CODE F01/F11

HARNESS DIN - MAIN

Next: End

FAULT CODE F01/F11

FAULT CODE RESET

Next: End

FAULT CODE F83

FAULT CODE RESET

Next: End

FAULT CODE F84

FAULT CODE RESET

Next: End

FAULT CODE F73 - F74

SYSTEM PRESSURE SENSOR

Next: End

FAULT CODE F73 - F74

FAULT CODE RESET

Next: End

CH SYMBOL FLASHING AND CH FLOW TEMPERATURE BELOW 12 °C (FIG 2)

CHARACTERISTIC TEST FROM POWER UP SELF TEST

Next: p11

BURNER DOES NOT IGNITE

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH

Next: p234

BURNER IGNITES SMOOTHLY BUT DOES NOT ESTABLISH - SPARKING CONTINUES

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH

Next: p2126

BURNER IGNITES BUT IS NOISY AND/OR BAFFLES OUT

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH

Next: p279

FAN DOES NOT RUN

CHARACTERISTIC TEST FROM ? OBSERVATION FAN RUNS - FAULT CODE F32

Next: p1344

FAN RUNS AND/OR STOPS AND RESTARTS - FAULT CODE F32 OCCURS

CHARACTERISTIC TEST FROM ? OBSERVATION FAN RUNS - FAULT CODE F32

Next: p2738

DISPLAY NOT ILLUMINATED (BLANK)

CHARACTERISTIC TEST FROM OBSERVATION DISPLAY

Next: p1601

FAULT CODE DISPLAYED

CHARACTERISTIC TEST FROM OBSERVATION DISPLAY

Next: p1632

FAULT CODE F32 DISPLAYED

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH

Next: p2746

LOW SYSTEM PRESSURE DISPLAYED

CHARACTERISTIC TEST FROM OBSERVATION DISPLAY

Next: p1941

CH SYMBOL FLASHING AND CH FLOW TEMP ABOVE 12°C (FIG 3)

CHARACTERISTIC TEST FROM POWER UP SELF TEST

Next: p1867

RESET DISPLAYED

CHARACTERISTIC TEST FROM OBSERVATION DISPLAY

Next: p2111

24 VOLT EXTERNAL CONTROLS FITTED

CHARACTERISTIC TEST FROM OBSERVATION EXTERNAL CONTROLS FITTED

Next: p2258

EBUS CONTROLS FITTED

CHARACTERISTIC TEST FROM OBSERVATION EXTERNAL CONTROLS FITTED

Next: p2260

BOILER REACHES TEMPERATURE RADIATORS DO NOT HEAT

CHARACTERISTIC TEST FROM CH OPERATION

Next: p2318

EXCESSIVE SYSTEM PRESSURE AS CH TEMPERATURE RISES

CHARACTERISTIC TEST FROM CH OPERATION

Next: p2336

BOILER DOES NOT RESPOND TO DHW DEMAND

CHARACTERISTIC TEST FROM OPERATION DHW

Next: !p2365

BOILER RESPONDS TO DHW DEMAND BUT OPERATION UNSATISFACTORY

CHARACTERISTIC TEST FROM OPERATION DHW

Next: !p2367

BOILER SHUTS DOWN BEFORE REACHING TEMPERATURE

CHARACTERISTIC TEST FROM CH OPERATION

Next: p2370

BOILER GOES TO FAULT CODE F20 - TEMPERATURE BELOW 97°C

CHARACTERISTIC TEST FROM RUN BOILER TO MAX TEMP - FAULT CODE F20

Next: !p2491

BOILER FLOW TEMPERATURE EXCEEDS 85°C AND BOILER STILL FIRED

CHARACTERISTIC TEST FROM RUN BOILER TO MAX TEMP - FAULT CODE F20

Next: !p2493

SENSOR RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2505

MANIFOLD RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2507

SENSOR RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2511

MANIFOLD RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2513

SENSOR RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2517

MANIFOLD RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2519

SENSOR RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2523

MANIFOLD RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2525

SENSOR RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2529

MANIFOLD RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2531

SENSOR RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2535

MANIFOLD RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2537

SENSOR RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2541

MANIFOLD RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2543

SENSOR RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2547

MANIFOLD RESTRICTED AND/OR BLOCKED

CHARACTERISTIC TEST FROM INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

Next: !p2549

UNABLE TO GAS RATE (EG LPG INSTALLATION)

CHARACTERISTIC TEST FROM GAS RATE

Next: p2660

GAS RATE INCORRECT

CHARACTERISTIC TEST FROM GAS RATE

Next: p2662

BOILER CONTINUES TO FIRE BUT RADIATORS ONLY GET WARM

CHARACTERISTIC TEST FROM CH OPERATION

Next: p1999

FAN DOES NOT RUN - CH DEMAND RECOGNISED (RADIATOR SYMBOL FLASHING)

CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS - CH DEMAND

Next: p99

FAN DOES NOT RUN - CH DEMAND NOT RECOGNISED (RADIATOR SYMBOL NOT FLASHING)

CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS - CH DEMAND

Next: p2255

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p102, !f103

RESET APPLIANCE - FAULT CODE F20 TO F24

ENSURE NO DEMANDS ARE PRESENT
ENSURE BOILER IS COOL

Next: p1061, f1089

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p1090, !f1091

RESISTANCE GAS VALVE AND HARNESS

{GAINPCBACS}
REMOVE CONNECTOR X20 FROM THE PCB

Next: p1147, f1144

RESISTANCE GAS VALVE

REMOVE LEFT - HAND SIDE BOILER CASE
REMOVE ELECTRICAL CONNECTOR TO THE GAS VALVE

Next: !p1148, !f1149

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: p1153, !f1339

FACTORY RESET PROCEDURE

FACTORY RESET PRO

Next: !p1161, !f1162

OBSERVATION UNDERFLOOR HEATING

Next: p1175, f1180

RESISTANCE SENSOR UNDER FLOOR

{GAINPCBACS}
REMOVE UNDER FLOOR HEATING SENSOR CONNECTOR FROM X18 ON THE PCB

Next: p1185, !f1186

RESET APPLIANCE - FAULT CODE F20 TO F24

ENSURE NO DEMANDS ARE PRESENT
ENSURE BOILER IS COOL

Next: p1206, f1201

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p1202, !f1203

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1362, f1363

OBSERVATION ARE ANY EBUS CONTROLS FITTED

{GAINPCBACS}

Next: p1364, !f1365

RESISTANCE THERMAL FUSE AND HARNESS

REMOVE CONNECTOR X20 FROM THE PCB

Next: p1384, f1380

RESISTANCE HARNESS THERMAL FUSE

REMOVE CONNECTOR X20 FROM THE PCB
REMOVE CONNECTOR TO THERMAL FUSE

Next: !p1387, !f1382

RESET APPLIANCE - FAULT CODE F61 - F67

ENSURE NO DEMANDS ARE PRESENT

Next: p2231, f2235

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1423, f1424

OBSERVATION DSN NUMBER

PARAMETER DSN NUM

Next: p2729, f1426

DSN NUMBER ALTERED CORRECTLY

THE DSN PARAMETER IS

Next: !p1429, !f1430

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1583, f1584

FACTORY RESET - PCB MAIN

FACTORY RESET PRO

Next: !p1585, f1586

RESISTANCE HARNESS INTERFACE

REMOVE CONNECTOR X51 FROM THE PCB
REMOVE PCB TO INTERFACE PCB CONNECTOR

Next: !p1587, !f1588
Next: !p1595, !f1596

RESISTANCE FUSE (FUSED SPUR)

REMOVE FUSE FROM FUSED SPUR

Next: !p1604, f1605

FUSE FURTHER INVESTIGATION (FUSED SPUR)

THE INFORMATION PROV

Next: !p1606, !f1607

ACTIVATE STATUS CODES

STATUS CODES OF T

Next: !p1672, !f1673

OBSERVATION EXTERNAL CONTROLS FITTED - SELF TEST

{GAINPCBACS}

Next: p1881, f1885

DISCONNECT INTERNAL PROGRAMMER (SELF TEST)

GAIN ACCESS TO UPPER

Next: !p1879, !f1880

DISCONNECT EBUS CONTROLS - SELF TEST

REMOVE EBUS WIRING C

Next: !p1886, !f1887

DISCONNECT EBUS CONTROLS - SELF TEST

REMOVE EBUS WIRING C

Next: !p1888, !f1889

FUSE FURTHER INVESTIGATION (PCB FUSE)

THE INFORMATION PROV

Next: !p2092, !f2093

VOLTAGE FAN HALL SENSOR AT PCB

{GAINPCBACS}

Next: p2122, f2100

RESISTANCE HARNESS FAN

REMOVE ELECTRICAL CONNECTORS X20 FROM THE PCB AND TO THE FAN ASSEMBLY

Next: !p2101, !f2102

RESISTANCE HARNESS SPARK GENERATOR

REMOVE ELECTRICAL CONNECTOR TO SPARK GENERATOR AND CONNECTOR X21 FROM THE PCB

Next: !p2115, !f2116

INSPECTION ELECTRODE IGNITION

REMOVE IGNITION ELECTRODE

Next: p2132, !f2133

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p2198, !f2199

RESISTANCE GAS VALVE AND HARNESS

{GAINPCBACS}
REMOVE CONNECTOR X20 FROM THE PCB

Next: p2236, f2237

RESISTANCE GAS VALVE

REMOVE LEFT - HAND SIDE BOILER CASE
REMOVE ELECTRICAL CONNECTOR TO THE GAS VALVE

Next: !p2238, !f2239

DSN NUMBER ALTERED CORRECTLY

THE DSN PARAMETER IS

Next: !p2244, !f2245

VOLTAGE SPARK GENERATOR AT PCB

{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR TO SPARK GENERATOR AND MAKE SAFE

Next: p238, f2098

RESISTANCE GAS VALVE AND HARNESS

{GAINPCBACS}
REMOVE CONNECTOR X20 FROM THE PCB

Next: !p246, f247

RESISTANCE GAS VALVE

REMOVE LEFT - HAND SIDE BOILER CASE
REMOVE ELECTRICAL CONNECTOR TO THE GAS VALVE

Next: !p1669, !f1589

INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

DRAIN PRIMARY SYSTEM WATER FROM BOILER
REMOVE SYSTEM PRESSURE SENSOR FROM THE LEFT HAND MANIFOLD

Next: !p2503, ?2504, ?2506

INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

DRAIN PRIMARY SYSTEM WATER FROM BOILER
REMOVE SYSTEM PRESSURE SENSOR FROM THE LEFT HAND MANIFOLD

Next: !p2509, ?2510, ?2512

RESISTANCE GAS VALVE

REMOVE LEFT - HAND SIDE BOILER CASE
REMOVE ELECTRICAL CONNECTOR TO THE GAS VALVE

Next: !p252, !f253

INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

DRAIN PRIMARY SYSTEM WATER FROM BOILER
REMOVE SYSTEM PRESSURE SENSOR FROM THE LEFT HAND MANIFOLD

Next: !p2515, ?2516, ?2518

INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

DRAIN PRIMARY SYSTEM WATER FROM BOILER
REMOVE SYSTEM PRESSURE SENSOR FROM THE LEFT HAND MANIFOLD

Next: !p2521, ?2522, ?2524

INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

DRAIN PRIMARY SYSTEM WATER FROM BOILER
REMOVE SYSTEM PRESSURE SENSOR FROM THE LEFT HAND MANIFOLD

Next: !p2533, ?2534, ?2536

INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

DRAIN PRIMARY SYSTEM WATER FROM BOILER
REMOVE SYSTEM PRESSURE SENSOR FROM THE LEFT HAND MANIFOLD

Next: !p2539, ?2540, ?2542

INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

DRAIN PRIMARY SYSTEM WATER FROM BOILER
REMOVE SYSTEM PRESSURE SENSOR FROM THE LEFT HAND MANIFOLD

Next: !p2545, ?2546, ?2548
Next: p2671, f2672

OBSERVATION DSN NUMBER - OUTPUT

PARAMETER DSN NUM

Next: !p2673, f2674

DSN NUMBER ALTERED CORRECTLY

THE DSN PARAMETER IS

Next: !p2675, !f2676
Next: p2687, f2688

OBSERVATION DSN NUMBER - OUTPUT

PARAMETER DSN NUM

Next: !p2689, f2690

DSN NUMBER ALTERED CORRECTLY

THE DSN PARAMETER IS

Next: !p2691, !f2692

INSPECTION EXTERNAL BYPASS

Next: p2696, !f2697

INSPECTION EXTERNAL BYPASS

Next: p2701, !f2702

INSPECTION EXTERNAL BYPASS

Next: p2706, !f2707

INSPECTION EXTERNAL BYPASS

Next: p2711, !f2712

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: !p2753, !f2754

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: !p2761, !f2762

RESISTANCE GAS VALVE

REMOVE LEFT - HAND SIDE BOILER CASE
REMOVE ELECTRICAL CONNECTOR TO THE GAS VALVE

Next: !p2765, !f2766

VOLTAGE GAS VALVE AT PCB

{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR FROM GAS VALVE AND MAKE SAFE

Next: !p2769, !f2770

VOLTAGE SENSOR SYSTEM PRESSURE - RETURN

{GAINPCBACS}

Next: !p2773, !f2859

VOLTAGE FAN 22 VDC AT PCB

REMOVE ELECTRICAL CONNECTOR FROM FAN ASSEMBLY, LEAVE IN A SAFE LOCATION

Next: !p2777, !f2778

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: !p2781, !f2782

RESISTANCE PUMP AND HARNESS

{GAINPCBACS}
REMOVE X14 PUMP CONNECTOR FROM THE PCB

Next: !p2785, !f2786

RESISTANCE PUMP AND HARNESS ERP

{GAINPCBACS}
REMOVE X14 PUMP CONNECTOR FROM THE PCB

Next: !p2789, !f2790

VOLTAGE PUMP AT PCB ERP

{GAINPCBACS}

Next: !p2793, !f2794

OBSERVATION TYPE OF PUMP

Next: p2797, f2798

RESISTANCE PUMP AND HARNESS (FUSE FURTHER INVESTIGATION)

{GAINPCBACS}
REMOVE X14 PUMP CONNECTOR FROM THE PCB

Next: !p2799, !f2800

OBSERVATION TYPE OF PUMP

Next: p2805, f2806

RESISTANCE PUMP AND HARNESS

{GAINPCBACS}
REMOVE X14 PUMP CONNECTOR FROM THE PCB

Next: p2807, !f2808

OBSERVATION TYPE OF PUMP

Next: p2816, f2817

RESISTANCE PUMP AND HARNESS

{GAINPCBACS}
REMOVE X14 PUMP CONNECTOR FROM THE PCB

Next: p2818, !f2819

OBSERVATION TYPE OF PUMP

Next: p2827, f2828

RESISTANCE PUMP AND HARNESS

{GAINPCBACS}
REMOVE X14 PUMP CONNECTOR FROM THE PCB

Next: p2829, !f2830

OBSERVATION TYPE OF PUMP

Next: p2838, f2839

RESISTANCE PUMP AND HARNESS

{GAINPCBACS}
REMOVE X14 PUMP CONNECTOR FROM THE PCB

Next: p2840, !f2841

OBSERVATION TYPE OF PUMP

Next: p2849, f2850

RESISTANCE PUMP AND HARNESS

{GAINPCBACS}
REMOVE X14 PUMP CONNECTOR FROM THE PCB

Next: p2851, !f2852

PRESSURE GAS VALVE INLET

ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE INLET TEST POINT

Next: p504, !f485

INSPECTION BURNER ASSEMBLY

REMOVE COMBUSTION BLOCK FROM BOILER
REMOVE LEFT-HAND SIDE CASE IF REQUIRED

Next: p549, !f550

TEST MODE ACTIVATION

Next: !p556, !f557

RESISTANCE THERMISTOR FLOW AND HARNESS

{GAINPCBACS}
REMOVE CONNECTOR X20 FROM THE PCB

Next: p736, f737

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: !p740, !f741

RESISTANCE THERMISTOR RETURN AND HARNESS

{GAINPCBACS}
REMOVE CONNECTOR X20 FROM THE PCB

Next: p748, f749

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: !p750, !f751

RESET APPLIANCE - FAULT CODE 83

ENSURE NO DEMANDS ARE PRESENT

Next: p785, f2197

VOLTAGE SENSOR SYSTEM PRESSURE - RETURN

{GAINPCBACS}

Next: p932, f933

ADJUST PRIMARY SYSTEM PRESSURE - FAULT CODE F22

{GAINPCBACS}
LOCATE PRIMARY SYSTEM FILLING LOOP

Next: p949, f950

VOLTAGE FAN 22 VDC AT PCB

REMOVE ELECTRICAL CONNECTOR FROM FAN ASSEMBLY, LEAVE IN A SAFE LOCATION

Next: p106, !f107

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: !p104, !f105

RESISTANCE HARNESS FAN

REMOVE ELECTRICAL CONNECTORS X20 FROM THE PCB AND TO THE FAN ASSEMBLY

Next: !p108, !f109

OBSERVATION SYSTEM PRESSURE

Next: p2450, f2532

OBSERVATION PUMP RUNS

Next: p1097, f2826

PUMP LIMPET TEST

Next: p1077, !f1078

TEMPERATURE DIFFERENTIAL FLOW AND RETURN - CH

ATTACH TEMPERATURE C

Next: !p2483, f2695

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: !p1092, !f1093

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p1111, !f1125

TEMPERATURE FLOW - FROST PROTECTION

REMOVE LEFT HAND SID

Next: p12, !f13

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: p1071, !f1126

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1150, !f1151

OBSERVATION FAN RUNS - FAULT CODE F32

Next: !p1358, ?1340, ?1342

RESISTANCE LINK UNDER FLOOR HEATING CONNECTOR

{GAINPCBACS}
REMOVE UNDER FLOOR HEATING SENSOR CONNECTOR FROM X18 ON THE PCB

Next: p1183, !f1184

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1189, !f1190

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1191, !f1188

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p1195, !f1196

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1197, !f1198

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p24, !f15

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: !p1204, !f1205

OBSERVATION SYSTEM PRESSURE

Next: p1240, f2508

OBSERVATION PUMP RUNS

Next: p1286, f2815

PUMP LIMPET TEST

Next: p2583, !f1322

TEMPERATURE DIFFERENTIAL FLOW AND RETURN - CH

ATTACH TEMPERATURE C

Next: p2485, f2700

VOLTAGE FAN CONTROL PCB

{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR FROM FAN ASSEMBLY, LEAVE IN A SAFE LOCATION

Next: p1345, !f1355

VOLTAGE FAN 22 VDC AT PCB

REMOVE ELECTRICAL CONNECTOR FROM FAN ASSEMBLY, LEAVE IN A SAFE LOCATION

Next: p1351, !f1352

RESISTANCE HARNESS FAN

REMOVE ELECTRICAL CONNECTORS X20 FROM THE PCB AND TO THE FAN ASSEMBLY

Next: !p1353, !f1354

DISCONNECT EBUS CONTROLS

REMOVE CONNECTOR X17 FROM THE PCB

Next: !p1366, !f1367

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1385, !f1386

FACTORY RESET - PCB MAIN

FACTORY RESET PRO

Next: !p1427, !f1428

VOLTAGE MAINS POWER INPUT AT PCB

{GAINPCBACS}

Next: p2065, f1603

DISCONNECT WATER PRESSURE SENSOR CONNECTOR

REMOVE WATER PRESSURE SENSOR CONNECTOR AND MAKE SAFE

Next: p1608, !f1609

DISCONNECT FAN CONNECTOR

REMOVE ELECTRICAL CONNECTOR TO FAN ASSEMBLY AND MAKE SAFE

Next: p1610, !f1611

VOLTAGE DISPLAY AT INTERFACE PCB

GAIN ACCESS TO INTERFACE PCB (USE INSULATION MAT AS REQUIRED)

Next: !p2096, !f2097

FAULT CODES

Next: !p1633, !f1634

OBSERVATION EXTERNAL CONTROLS FITTED - SELF TEST

{GAINPCBACS}

Next: p1876, f1884

DISCONNECT EXTERNAL CONTROLS

REMOVE ALL EXTERNAL

Next: !p1877, f1878

DISCONNECT EXTERNAL CONTROLS

REMOVE ALL EXTERNAL

Next: !p1882, !f1883

SYSTEM PRESSURE SET CORRECTLY

THE SYSTEM PRESSURE

Next: !p1949, !f1950

OBSERVATION SYSTEM PRESSURE

Next: p2138, f2514

PUMP LIMPET TEST

Next: p2010, !f2011

INSPECTION AIR BOX

REMOVE AIR BOX FROM GAS VALVE

Next: p2648, !f2013

RESISTANCE FUSE PCB

REMOVE FUSE FROM PCB

Next: p1602, f2091

RESET OPTIONS

Next: !p2112, !f2113

RESISTANCE HARNESS FAN

REMOVE ELECTRICAL CONNECTORS X20 FROM THE PCB AND TO THE FAN ASSEMBLY

Next: !p2123, !f2124

INSPECTION CONDENSATE PIPE

Next: p2127, !f2137

VOLTAGE RECTIFICATION AT PCB

{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR TO SPARK GENERATOR AND MAKE SAFE
ENSURE NO DEMANDS

Next: p2128, !f2129

RESISTANCE HARNESS SPARK GENERATOR

REMOVE ELECTRICAL CONNECTOR TO SPARK GENERATOR AND CONNECTOR X21 FROM THE PCB

Next: !p2134, !f2135

PRESSURE GAS VALVE INLET

ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE INLET TEST POINT

Next: p2009, !f2162

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p2179, !f2195

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: p788, !f2196

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: !p2200, !f2201

OBSERVATION GAS VALVE CLOSURE

Next: !p2232, !f2233

OBSERVATION PCB CONNECTIONS

Next: p2240, !f2241

OBSERVATION DSN NUMBER

PARAMETER DSN NUM

Next: p2242, f2243

FACTORY RESET - PCB MAIN

FACTORY RESET PRO

Next: !p2246, !f2247

OBSERVATION EXTERNAL CONTROLS FITTED

{GAINPCBACS}

Next: p2256, ?2257, ?2259

BYPASS EXTERNAL CONTROLS - 240V

DISCONNECT 240V EXTE

Next: !p2269, f2270

BYPASS EXTERNAL CONTROLS - 24V

DISCONNECT 24V EXTER

Next: !p2263, f2264

DISCONNECT EBUS CONTROLS - CH DEMAND

DISCONNECT EBUS WIRING CONNECTIONS TO CONNECTOR X17 AND MAKE SAFE

Next: !p2261, f2275

DISCONNECT INTERNAL PROGRAMMER

GAIN ACCESS TO UPPER

Next: !p2267, f2296

DISCONNECT INTERNAL PROGRAMMER

GAIN ACCESS TO UPPER

Next: !p2273, f2310

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p2278, !f2279

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: !p2280, !f2281

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p2292, !f2293

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: !p2294, !f2295

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p2299, !f2300

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: !p2301, !f2302

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p2306, !f2307

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: !p2308, !f2309

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p2313, !f2314

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: !p2315, !f2316

PUMP LIMPET TEST

Next: p2354, !f2322

INSPECTION EXPANSION VESSEL PRESSURE

DISCHARGE PRIMARY SYSTEM WATER

Next: !p2337, !f2338

INSPECTION CONDENSATE PIPE

Next: p235, !f270

TEMPERATURE DIFFERENTIAL - INTERNAL BYPASS

ENSURE RADIATORS ARE

Next: !p2352, !f2353

INSPECTION EXTERNAL BYPASS

Next: p2351, !f2358

PRESSURE GAS VALVE INLET

ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE INLET TEST POINT

Next: p295, !f243

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p2371, !f2372

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: !p2373, !f2374

OBSERVATION SYSTEM PRESSURE

Next: p2319, f2520

OBSERVATION SPARKING HEARD

REMOVE IGNITION LEAD FROM SPARK GENERATOR AND MAKE SAFE

Next: !p240, f2114

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: !p30, !f26

VOLTAGE GAS VALVE AT PCB

{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR FROM GAS VALVE AND MAKE SAFE

Next: p244, f245

RESISTANCE GAS VALVE AND HARNESS

{GAINPCBACS}
REMOVE CONNECTOR X20 FROM THE PCB

Next: p2550, f251

OBSERVATION PUMP OVERRUN TIME

Next: p2486, !f2487

RUN BOILER TO MAX TEMP - FAULT CODE F20

REMOVE LEFT HAND SID

Next: !p2488, ?2490, ?2492

INSPECTION SENSOR SYSTEM PRESSURE AND MANIFOLD

DRAIN PRIMARY SYSTEM WATER FROM BOILER
REMOVE SYSTEM PRESSURE SENSOR FROM THE LEFT HAND MANIFOLD

Next: !p2527, ?2528, ?2530

INSPECTION ELECTRODE IGNITION

REMOVE IGNITION ELECTRODE

Next: p2554, !f2552

INSPECTION FLUE ASSEMBLY

Next: p2555, !f2556

INSPECTION BURNER ASSEMBLY

REMOVE COMBUSTION BLOCK FROM BOILER
REMOVE LEFT-HAND SIDE CASE IF REQUIRED

Next: p2557, !f2558

INSPECTION FLUEWAYS HEAT EXCHANGER

Next: !p2560, !f2559

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p2604, !f2603

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: p1287, !f2624

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p2651, !f2652

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: p2653, !f2654

TEMPERATURE DIFFERENTIAL FLOW AND RETURN - CH

ATTACH TEMPERATURE C

Next: p2655, f2705

GAS RATE

Next: p2657, ?2659, ?2661

OBSERVATION MAXIMUM HEATING POWER

Next: !p2685, f2686

INSPECTION FLUE ASSEMBLY

Next: p2663, !f2664

INSPECTION BURNER ASSEMBLY

REMOVE COMBUSTION BLOCK FROM BOILER
REMOVE LEFT-HAND SIDE CASE IF REQUIRED

Next: p2665, !f2666

INSPECTION FLUEWAYS HEAT EXCHANGER

Next: !p2667, !f2668

INSPECTION FLUE ASSEMBLY

Next: p2679, !f2680

PARAMETER SET CORRECTLY - RADIATOR TEMPERATURE LOW

THE MAXIMUM HEATING

Next: !p2677, !f2678

INSPECTION BURNER ASSEMBLY

REMOVE COMBUSTION BLOCK FROM BOILER
REMOVE LEFT-HAND SIDE CASE IF REQUIRED

Next: p2681, !f2682

INSPECTION FLUEWAYS HEAT EXCHANGER

Next: !p2683, !f2684

PARAMETER SET CORRECTLY - RADIATOR TEMPERATURE LOW

THE MAXIMUM HEATING

Next: !p2693, !f2694

INSPECTION INTERNAL BYPASS

APPLIANCE DRAINED AND DISCHARGED

Next: !p2699, !f2698

INSPECTION INTERNAL BYPASS

APPLIANCE DRAINED AND DISCHARGED

Next: !p2703, !f2704

INSPECTION INTERNAL BYPASS

APPLIANCE DRAINED AND DISCHARGED

Next: !p2708, !f2709

INSPECTION INTERNAL BYPASS

APPLIANCE DRAINED AND DISCHARGED

Next: !p2713, !f2714

OBSERVATION PUMP RUNS

Next: p2719, f2848

PUMP LIMPET TEST

Next: p847, !f2723

OBSERVATION DS NUMBER RESET

SOMETIMES THE SOFTWA

Next: p1425, !f2734

RESISTANCE HARNESS FAN

REMOVE ELECTRICAL CONNECTORS X20 FROM THE PCB AND TO THE FAN ASSEMBLY

Next: p2739, !f2740

VOLTAGE FAN HALL SENSOR AT PCB

{GAINPCBACS}

Next: !p2741, !f2742

RESISTANCE HARNESS FAN

REMOVE ELECTRICAL CONNECTORS X20 FROM THE PCB AND TO THE FAN ASSEMBLY

Next: p2747, !f2748

VOLTAGE FAN HALL SENSOR AT PCB

{GAINPCBACS}

Next: !p2749, !f2750

INSPECTION CONDENSATE PIPE

Next: p284, !f281

RESISTANCE PUMP AND HARNESS ERP

{GAINPCBACS}
REMOVE X14 PUMP CONNECTOR FROM THE PCB

Next: !p2801, !f2802

PRESSURE GAS VALVE INLET

ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE INLET TEST POINT

Next: p282, !f283

RESISTANCE PUMP HARNESS ERP

REMOVE X14 PUMP CONNECTOR FROM THE PCB
DISCONNECT PLUG FROM THE PUMP

Next: p2811, !f2812

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: !p2809, !f2810

VOLTAGE PUMP AT PCB ERP

{GAINPCBACS}

Next: !p2813, !f2814

RESISTANCE PUMP HARNESS ERP

REMOVE X14 PUMP CONNECTOR FROM THE PCB
DISCONNECT PLUG FROM THE PUMP

Next: p2822, !f2823

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: !p2820, !f2821

INSPECTION FLUE ASSEMBLY

Next: p289, !f290

VOLTAGE PUMP AT PCB ERP

{GAINPCBACS}

Next: !p2824, !f2825

RESISTANCE PUMP HARNESS ERP

REMOVE X14 PUMP CONNECTOR FROM THE PCB
DISCONNECT PLUG FROM THE PUMP

Next: p2833, !f2834

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: !p2831, !f2832

VOLTAGE PUMP AT PCB ERP

{GAINPCBACS}

Next: !p2835, !f2836

RESISTANCE PUMP HARNESS ERP

REMOVE X14 PUMP CONNECTOR FROM THE PCB
DISCONNECT PLUG FROM THE PUMP

Next: p2844, !f2845

INSPECTION AIR BOX

REMOVE AIR BOX FROM GAS VALVE

Next: p280, !f288

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: !p2842, !f2843

VOLTAGE PUMP AT PCB ERP

{GAINPCBACS}

Next: !p2846, !f2847

RESISTANCE PUMP HARNESS ERP

REMOVE X14 PUMP CONNECTOR FROM THE PCB
DISCONNECT PLUG FROM THE PUMP

Next: p2855, !f2856

VOLTAGE PUMP AT PCB

{GAINPCBACS}

Next: !p2853, !f2854

VOLTAGE PUMP AT PCB ERP

{GAINPCBACS}

Next: !p2857, !f2858

INSPECTION BURNER ASSEMBLY

REMOVE COMBUSTION BLOCK FROM BOILER
REMOVE LEFT-HAND SIDE CASE IF REQUIRED

Next: p291, !f292

INSPECTION AIR BOX

REMOVE AIR BOX FROM GAS VALVE

Next: p242, !f321

INSPECTION FLUE ASSEMBLY

Next: p486, !f487

INSPECTION COMBUSTION SEALS

Next: p488, !f489

ADJUSTMENT AIR/GAS RATIO

CONNECT FGA TO THE COMBUSTION TEST POINT ON THE BOILER
ENSURE CH SYSTEM IS COOL

Next: !p490, f548

INSPECTION AIR BOX

REMOVE AIR BOX FROM GAS VALVE

Next: p526, !f524

INSPECTION CONDENSATE PIPE

Next: p484, !f546

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p738, !f739

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p752, !f753

OBSERVATION SYSTEM PRESSURE

Next: p786, f2544

OBSERVATION PUMP RUNS

Next: p790, f2837

PUMP LIMPET TEST

Next: p797, !f1377

CH OPERATION - FAULT CODE F83

Next: !p799, f2710

RESISTANCE THERMISTOR FLOW

REMOVE LEFT HAND SIDE PANEL
REMOVE RED LEADS TO FLOW THERMISTOR

Next: p842, !f843

RESISTANCE THERMISTOR RETURN

REMOVE LEFT HAND SIDE PANEL
REMOVE BLUE LEADS TO RETURN THERMISTOR

Next: p846, !f845

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: p2715, !f848

CH OPERATION - FAULT CODE

Next: !p849, !f850

ADJUST PRIMARY SYSTEM PRESSURE

LOCATE PRIMARY SYSTEM FILLING LOOP

Next: p938, f2538

RESISTANCE HARNESS SENSOR SYSTEM PRESSURE

REMOVE CONNECTOR X2 FROM THE PCB
REMOVE CONNECTOR TO SYSTEM PRESSURE SENSOR

Next: !p936, !f937

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p945, !f946

RESET APPLIANCE - FAULT CODE

ENSURE NO DEMANDS ARE PRESENT

Next: !p1059, !f952

VOLTAGE FAN CONTROL PCB

{GAINPCBACS}
REMOVE ELECTRICAL CONNECTOR FROM FAN ASSEMBLY, LEAVE IN A SAFE LOCATION

Next: p100, f101

System Information

  • Total Tests: 717
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control