XSol Diagnostic System

Interactive Test Sequence Navigator

Welcome to the XSol Diagnostic System

This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.

Start Diagnostic Sequence

or choose a specific test below:

S-PLAN FAULT FINDING GUIDE

GLOBALLY REPLACED

Next: &1, *

NO FAULT FOUND

Next: nff

S-PLAN FAULT FINDING GUIDE

Next: &nff, !f183

NO HEAT OR HOT WATER

Next: &nff, f770

HOT WATER TOO HOT

Next: &nff, f497

SPLAN FF

Z DUMMY TO CLOSE

Next: End

SPLAN NO POWER TO PUMP - HOT WATER

FAULT IN WIRING TO PUMP

Next: End

NO SUPPLY TO HOT WATER VALVE

240V NO SUPPLY TO GREY

Next: End

NO SUPPLY TO GRAY - HEATING

240V NO SUPPLY TO GREY

Next: End

SPLAN NO POWER TO PUMP - HEATING

FAULT IN WIRING TO PUMP

Next: End

ON WITH NO DEMAND

FROST THERMOSTAT

Next: End

MAINS TO HW BROWN WIRE

S PLAN WIRING FAULT

Next: End

HW TO HOT

CYLINDER THERMOSTAT POSITION

Next: End

MAINS FUSE

3 AMP MAIN FUSE

Next: End

WIRING CENTRE TO TIMER FAULT

240V MAINS SUPPLY - TO TIMER

Next: End

TIMER FAULTY 2

Z DUMMY TO CLOSE

Next: End

TIMER FAULTY 1

Z DUMMY TO CLOSE

Next: End

NO CH AND HW

240V NO SUPPLY TO GREY

Next: End

NO HOT WATER HEAT OK

SYNCHRON MOTOR

Next: End

NO HEAT HW OK

SYNCHRON MOTOR

Next: End

JAMMED - NO HW

SYNCHRON MOTOR

Next: End

JAMMED - NO HEATING

SYNCHRON MOTOR

Next: End

SPLAN NO HEATING - HOT WATER

SYNCHRON MOTOR

Next: End

SPLAN NO HEATING

SYNCHRON MOTOR

Next: End

SPLAN NO HEATING 2

TIMER

Next: End

NO HOT WATER

TIMER

Next: End

HEATING OK NO HOT WATER

MICROSWITCH

Next: End

HOT WATER OK NO HEATING

MICROSWITCH

Next: End

STUCK ON NO DEMAND - HEATING

MICROSWITCH

Next: End

S-PLAN NOT HOT WATER

CYLINDER THERMOSTAT

Next: End

SPLAN NO HEATING

ROOM THERMOSTAT

Next: End

BODY PASSING ON HOT WATER

ZONE VALVE BODY

Next: End

BODY PASSING ON HEATING

ZONE VALVE BODY

Next: End

HEATING WITH NO DEMAND

TIMER

Next: End

SPLAN NO HEATING

ZONE VALVE BODY

Next: End

HEAD JAMMED - HEATING

HEATING ZONE VALVE ACTUATOR

Next: End

WATER OK NO HEATING - ROOM STAT LINKED

S-PLAN WIRING FAULT

Next: End

HEATING OK NO WATER - CYL STAT LINKED OUT

S-PLAN WIRING FAULT

Next: End

SPLAN NO HEATING

TIMER

Next: End

SHORT ON WIRE FROM SROST STAT

S-PLAN WIRING FAULT

Next: End

SYNCHRON MOTOR AND ROOM STAT

SYNCHRON MOTOR AND ROOM THERMOSTAT

Next: End

HOT WATER OK NO HEATING - POWER ON BROWN

ZONE VALVE BODY

Next: End

HOT WATER OK NO HEAT - BODY STUCK 2

ZONE VALVE BODY

Next: End

HOT WATER OK NO HEAT - NON RMV HEAD 2

ZONE VALVE JAMMED

Next: End

HEATING NON REMOVE HEAD - ON WITH NO DEMAND

ZONE VALVE JAMMED

Next: End

HEATING OK NO HOT WATER - NON RMV VALV1

ZONE VALVE BODY

Next: End

HEATING OK NO HOT WATER - NON RMV VALV1

ZONE VALVE JAMMED

Next: End

SYNCHRON MOTOR AND CYL STAT

SYNCHRON MOTOR AND CYLINDER THERMOSTAT

Next: End

HEATING OK NO HOT WATER - NON RMV VALV2

ZONE VALVE BODY

Next: End

HEAD JAMMED HOT WATER

HOT WATER ZONE VALVE ACTUATOR

Next: End

BODY STUCK HOT WATER

ZONE VALVE BODY

Next: End

HW NON REMOVE HEAD - ON WITH NO DEMAND

ZONE VALVE JAMMED

Next: End

HOT WATER WITH NO DEMAND

TIMER

Next: End

HOT WATER TO HOT

CYLINDER THERMOSTAT

Next: End

NEITHER DEMAND WORKING

POWER SUPPLY (EXTERNAL)

Next: End

NO HEAT OR HOT WATER

TIMER

Next: End

NO HEAT OR HOT WATER

S-PLAN WIRING FAULT - TIMER TO WIRING CENTRE

Next: End

ALL OFF

ROOM THERMOSTAT

Next: End

ALL OFF - ROOM STAT LINKED

S-PLAN WIRING FAULT

Next: End

SYNCRON AND ROOM STAT FOR ALL OFF

SYNCHRON MOTOR AND ROOM THERMOSTAT

Next: End

ALL OFF - BODY STUCK 2

ZONE VALVE BODY

Next: End

ALL OFF - BODY STUCK2

ZONE VALVE JAMMED

Next: End

ALL OFF

CYLINDER THERMOSTAT

Next: End

ALL OFF - CYL STAT LINKED OUT

S-PLAN WIRING FAULT

Next: End

SYNCHRON MOTOR AND CYL STAT FOR ALL OFF

SYNCHRON MOTOR AND CYLINDER THERMOSTAT

Next: End

ALL OFF - BODY STUCK 1

ZONE VALVE BODY

Next: End

ALL OFF - BODY STUCK1

ZONE VALVE JAMMED

Next: End

HW AND CH NOT RUNNING

PUMP

Next: End

CH AND HW

FAULT IN WIRING TO PUMP

Next: End

NO HOT WATER MOTOR OK

S PLAN WIRING FAULT

Next: End

NO HEAT HW OK

S PLAN WIRING FAULT

Next: End

HEATING OK NO HOT WATER - NON RMV VALV2

ZONE VALVE JAMMED

Next: End

HOT WATER OK NO HEATING - NON REMV HEAD

ZONE VALVE JAMMED

Next: End

HEAD JAMMED HOT WATER 2

HOT WATER ZONE VALVE ACTUATOR

Next: End

HEAD JAMMED - HEATING 2

HEATING ZONE VALVE ACTUATOR

Next: End

NO VOLTAGE TO CYL STAT WITH TIMER LINKED

S-PLAN WIRING FAULT

Next: End

HEAT OK - NO HW

TIMER AND SYNCHRON MOTOR

Next: End

NO VOLTAGE TO ROOM STAT WITH TIMER LINKED

S-PLAN WIRING FAULT

Next: End

HW OK - NO HEATING

TIMER AND SYNCHRON MOTOR

Next: End

HEAT OK - NO HW

TIMER & ZONE VALVE BODY

Next: End

HEAT OK - NO HW

TIMER & ZONE VALVE JAMMED

Next: End

HOT WATER OK NO HEAT

TIMER & ZONE VALVE JAMMED

Next: End

HOT WATER OK NO HEAT

TIMER & ZONE VALVE BODY

Next: End

HOT WATER ON WITH NO DEMAND

TIMER

Next: End

STUCK ON WITH NO DEMAND

BOILER

Next: End

MICROSWITCH FAULTY - HOT WATER

HOT WATER ZONE VALVE ACTUATOR

Next: End

MICROSWITCH FAULTY - HEATING

HEATING ZONE VALVE ACTUATOR

Next: End

MICROSWITCH STUCK ON WITH NO DEMAND

HEATING ZONE VALVE ACTUATOR

Next: End

MICROSWITCH STUCK - HOT WATER ON WITH NO DEMAND

HOT WATER ZONE VALVE ACTUATOR

Next: End

MICROSWITCH STUCK - HOT WATER ON WITH NO DEMAND 2

HOT WATER ZONE VALVE ACTUATOR

Next: End

VOLTAGE STILL NOT PRESENT AT BROWN WIRE

CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT

Next: !p646

VOLTAGE OK BUT VALVE NOT MOVING

CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT

Next: p737

VOLTAGE OK BUT VALVE NOT MOVING

CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT

Next: p714

VOLTAGE STILL NOT PRESENT AT BROWN WIRE

CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT

Next: !p645

HEAD SPRINGS BACK WHEN REMOVED

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS)

Next: !p628

VALVE HEAD IS NOT REMOVEABLE

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS)

Next: !p720

VALVE SPINDLE IS STUCK

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: !p710

HEAD OF THE VALVE IS NOT REMOVEABLE

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: p855

VALVE SPINDLE IS STUCK

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: !p716

HEAD OF THE VALVE IS NOT REMOVEABLE

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: !p718

VALVE SPINDLE IS STUCK

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: !p739

HEAD OF THE VALVE IS NOT REMOVEABLE

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: !p741

VALVE SPINDLE IS STUCK

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: !p746

HEAD OF THE VALVE IS NOT REMOVEABLE

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: p852

HOT WATER VALVE IS NOT CLOSED WITH NO HW DEMAND

CHARACTERISTIC TEST FROM IS HOT WATER COMMING ON ALL TIME OR ONLY WITH HEATING DEMAND

Next: p758

HOT WATER VALVE CLOSED AND CYLINDER CIRCS REMAIN COOL WITH CH DEMAND

CHARACTERISTIC TEST FROM IS HOT WATER COMMING ON ALL TIME OR ONLY WITH HEATING DEMAND

Next: p757

HEAD SPRINGS BACK WHEN REMOVED

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS)

Next: !p763

VALVE HEAD IS NOT REMOVEABLE

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS)

Next: !p765

NEITHER VALVE OPENS

CHARACTERISTIC TEST FROM LINK OUT TIMER - BOTH

Next: !p783

HEATING VALVE OPENS BUT HOT WATER VALVE REMAINS CLOSED

CHARACTERISTIC TEST FROM LINK OUT TIMER - BOTH

Next: p785

HOT WATER VALVE OPENS BUT HEATING REMAINS CLOSED

CHARACTERISTIC TEST FROM LINK OUT TIMER - BOTH

Next: p787

VOLTAGE OK BUT VALVE NOT MOVING

CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT

Next: p795

VOLTAGE STILL NOT PRESENT AT BROWN WIRE

CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT

Next: !p797

VALVE SPINDLE IS STUCK

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: !p800

HEAD OF THE VALVE IS NOT REMOVEABLE

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: !p802

VOLTAGE OK BUT VALVE NOT MOVING

CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT

Next: p810

VOLTAGE STILL NOT PRESENT AT BROWN WIRE

CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT

Next: !p812

VALVE SPINDLE IS STUCK

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: !p815

HEAD OF THE VALVE IS NOT REMOVEABLE

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: !p817

VOLTAGE STILL NOT PRESENT AT BROWN WIRE

CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT

Next: !p874

VOLTAGE OK BUT VALVE NOT MOVING

CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT

Next: p876

VALVE SPINDLE IS STUCK

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: !p892

HEAD OF THE VALVE IS NOT REMOVEABLE

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: !p893

VOLTAGE OK BUT VALVE NOT MOVING

CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT

Next: p884

VOLTAGE STILL NOT PRESENT AT BROWN WIRE

CHARACTERISTIC TEST FROM LINK OUT CYLINDER THERMOSTAT

Next: !p886

VALVE SPINDLE IS STUCK

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: !p896

HEAD OF THE VALVE IS NOT REMOVEABLE

CHARACTERISTIC TEST FROM REMOVE HEAD FROM VALVE (IF POSS) CHECK SPINDLE

Next: !p895

HOT WATER ZONE VALVE OPERATION

LOCATE AND IDENTIFY

Next: p214, f215

VOLTAGE ON BROWN WIRE

IDENTIFY THE HOT WATER ZONE VALVE ELECTRICAL LEAD AND TERMINAL CONNECTIONS USED

Next: p832, f217

VOLTAGE CYLINDER THERMOSTAT COMMON

SET THE CYLINDER THERMOSTAT TO ITS MAXIMUM POSITION
REMOVE COVER FROM CYLINDER THERMOSTAT

Next: p218, f655

VOLTAGE ON GREY WIRE

LOCATE THE GREY WIRES IN THE WIRING CENTRE

Next: p869, !f336

VOLTAGE TO PUMP

REMOVE COVER FROM THE PUMP WIRING BOX.

Next: !p234, !f235

HEATING ZONE VALVE OPERATION

LOCATE AND IDENTIFY

Next: p341, f354

VOLTAGE ON GREY WIRE

LOCATE THE GREY WIRES IN THE WIRING CENTRE

Next: p866, !f345

VOLTAGE TO PUMP

REMOVE COVER FROM THE PUMP WIRING BOX.

Next: !p348, !f349

VOLTAGE ON BROWN WIRE

IDENTIFY THE HEATING ZONE VALVE ELECTRICAL LEAD AND TERMINAL CONNECTIONS USED

Next: p842, f356

VOLTAGE ROOM THERMOSTAT COMMON

REMOVE COVER FROM THE ROOM THERMOSTAT

Next: p357, f658

HOT WATER GETTING TOO HOT

Next: !p498, ?754, ?756

REMOVE HEAD FROM VALVE

Next: !p631, ?627, ?629

FROST THERMOSTAT CHECK

{ALLDEMANDOFF}
AS

Next: !p662, !f614

DISCONNECT HEATING VALVE ORANGE

DISCONNECT AND MAKE SAFE THE ORANGE WIRE FROM THE HEATING ZONE VALVE IN THE WIRING CENTRE

Next: p902, f913

LINK OUT TIMER - HOT WATER

REMOVE THE PROGRAMME

Next: !p656, ?873, ?875

LINK OUT TIMER - HEATING

REMOVE THE PROGRAMME

Next: !p659, ?883, ?885

REMOVE HEAD FROM VALVE

Next: !p761, ?762, ?764

OBSERVATION ZONE VALVES-NO CH AND HW OPERATION

LOCATE AND IDENTIFY

Next: p771, f773

MAINS POWER INTO SYSTEM

GAIN ACCESS TO THE MAINS INPUT CONNECTIONS IN THE WIRING CENTER
IDENTIFY THE MAIN LIVE TERMINAL

Next: p774, f775

RESISTANCE 3AMP FUSE

REMOVE FUSE FROM FUSED SPUR

Next: !p776, !f777

VOLTAGE TO PUMP - CH AND HW

REMOVE COVER FROM THE PUMP WIRING BOX.

Next: !p820, f822

VOLTAGE ON ORANGE WIRE - NO CH AND HW

LOCATE THE ORANGE WIRES IN THE WIRING CENTRE

Next: !p825, !f830

RESISTANCE SYNCHRON MOTOR

REMOVE THE COVER FROM THE VALVE
REMOVE THE SYNCHRON MOTOR FROM THE VALVE

Next: !p840, !f841

RESISTANCE SYNCHRON MOTOR

REMOVE THE COVER FROM THE VALVE
REMOVE THE SYNCHRON MOTOR FROM THE VALVE

Next: !p850, !f851

REMOVE TIMER

{ALLDEMANDOFF}
RE

Next: !p901, f640

RESISTANCE END FEED MICROSWITCH - HEATING

NOTE: THIS TE

Next: !p914, !f915

RESISTANCE END FEED MICROSWITCH - HOT WATER

NOTE: THIS TE

Next: !p917, !f918

RESISTANCE END FEED MICROSWITCH - HOT WATER

NOTE: THIS TE

Next: !p920, !f921

VOLTAGE ON ORANGE WIRE

LOCATE THE ORANGE WIRES IN THE WIRING CENTRE

Next: p228, f229

LINK OUT CYLINDER THERMOSTAT

PLACE A LINK BETWEEN

Next: !p313, ?524, ?526

PUMP RUNNING - HOT WATER

IF POSSIBLE REMOVE T

Next: p232, f233

BOILER RUNNING

Next: !p397, !f237

VOLTAGE ON ORANGE WIRE

LOCATE THE ORANGE WIRES IN THE WIRING CENTRE

Next: p342, f343

PUMP RUNNING - NO HEATING

IF POSSIBLE REMOVE T

Next: p346, f347

BOILER RUNNING

Next: !p394, !f351

LINK OUT ROOM THERMOSTAT

PLACE A WIRE LINK BE

Next: !p363, ?529, ?531

REMOVE TIMER

{ALLDEMANDOFF}
RE

Next: !p611, f612

REMOVE HEAD FROM VALVE

Next: p861, ?709, ?711

REMOVE HEAD FROM VALVE

Next: !p7, ?715, ?717

REMOVE HEAD FROM VALVE

Next: !p742, ?738, ?740

REMOVE HEAD FROM VALVE

Next: p858, ?745, ?747

INSPECTION CYLINDER THERMOSTAT

LOCATE CYLINDER THERMOSTAT

Next: !p768, !f769

ISOLATE POWER AND LOOK FOR VALVE SPRING BACK

{ALLDEMANDOFF}

Next: p759, f760

HOT WATER RESPONDS TO TIMER

{ALLDEMANDOFF}
RE

Next: !p766, !f767

PUMP RUNNING - NO CH AND HW

IF POSSIBLE REMOVE T

Next: p818, f819

MAINS SUPPLY TO TIMER

REMOVE THE PROGRAMMER FROM ITS BACKPLATE.

Next: p778, !f779

LINK OUT TIMER

REMOVE THE PROGRAMME

Next: !p780, ?782, ?784, ?786

TIMER FAULTY

Next: p803, !f804

TIMER FAULTY

Next: p788, !f789

VOLTAGE ROOM THERMOSTAT COMMON

REMOVE COVER FROM THE ROOM THERMOSTAT

Next: p790, !f791

LINK OUT ROOM THERMOSTAT

PLACE A WIRE LINK BE

Next: !p792, ?794, ?796

REMOVE HEAD FROM VALVE

Next: !p798, ?799, ?801

VOLTAGE CYLINDER THERMOSTAT COMMON

SET THE CYLINDER THERMOSTAT TO ITS MAXIMUM POSITION
REMOVE COVER FROM CYLINDER THERMOSTAT

Next: p805, !f806

LINK OUT CYLINDER THERMOSTAT

PLACE A LINK BETWEEN

Next: !p807, ?809, ?811

REMOVE HEAD FROM VALVE

Next: !p813, ?814, ?816

BOILER RUNNING - NO CH AND HW

Next: !p831, !f824

RESISTANCE BROWN WIRE TO BLUE - HW

IDENTIFY THE HOT WATER ZONE VALVE ELECTRICAL LEAD AND TERMINAL CONNECTIONS USED

Next: p744, f839

RESISTANCE BROWN WIRE TO BLUE - HEATING

IDENTIFY THE HEATING ZONE VALVE ELECTRICAL LEAD AND TERMINAL CONNECTIONS USED

Next: p707, f849

MECHANICAL CHECK SYNCHRON MOTOR

REMOVE THE COVER FROM THE VALVE
REMOVE THE SYNCHRON MOTOR FROM THE VALVE

Next: !p853, !f854

MECHANICAL CHECK SYNCHRON MOTOR

REMOVE THE COVER FROM THE VALVE
REMOVE THE SYNCHRON MOTOR FROM THE VALVE

Next: !p856, !f857

MECHANICAL CHECK SYNCHRON MOTOR

REMOVE THE COVER FROM THE VALVE
REMOVE THE SYNCHRON MOTOR FROM THE VALVE

Next: !p864, !f860

MECHANICAL CHECK SYNCHRON MOTOR

REMOVE THE COVER FROM THE VALVE
REMOVE THE SYNCHRON MOTOR FROM THE VALVE

Next: !p865, !f863

VOLTAGE ON BROWN WIRE

IDENTIFY THE HEATING ZONE VALVE ELECTRICAL LEAD AND TERMINAL CONNECTIONS USED

Next: p910, !f868

VOLTAGE ON BROWN WIRE

IDENTIFY THE HOT WATER ZONE VALVE ELECTRICAL LEAD AND TERMINAL CONNECTIONS USED

Next: p907, !f871

REMOVE HEAD FROM VALVE

Next: !p877, ?878, ?880

REMOVE HEAD FROM VALVE

Next: !p887, ?888, ?890

DISCONNECT HOT WATER VALVE ORANGE - DOES DEMAND STOP

DISCONNECT AND MAKE SAFE THE ORANGE WIRE FROM THE HOT WATER ZONE VALVE IN THE WIRING CENTRE

Next: !p905, f919

RESISTANCE END FEED MICROSWITCH - HOT WATER

NOTE: THIS TE

Next: !p908, !f909

RESISTANCE END FEED MICROSWITCH - HEATING

NOTE: THIS TE

Next: !p911, !f912

System Information

  • Total Tests: 217
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control