XSol Diagnostic System

Interactive Test Sequence Navigator

Welcome to the XSol Diagnostic System

This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.

Start Diagnostic Sequence

or choose a specific test below:

GLEDHILL BOILERMATE 2000 BM 185

WARNING - IMPORTA

Next: &7, *

SYSTEM CHECKS

Next: &321, !f130

GLEDHILL BOILERMATE 2000 BM 185

{ISOLATEMAINSPOWER}<

Next: &6, !f129

DHW FLOW RATE

Next: &50, f47

THERMAL STORE

{ISOLATEMAINSPOWER}
USE INSULATION MAT AS REQUIRED

Next: &110, f60

DHW OPERATION

Next: &183, ?147, ?149

CH OPERATION

Next: &nff, ?184, ?186, ?190

PCB SAFETY NOTICE

{ISOLATEMAINSPOWER}

Next: &46, !f322

THERMAL STORE

FUSE 5 AMP 20MM

Next: End

ELECTRICAL SAFETY CHECKS

ELECTRICAL CHECKS

Next: End

SYSTEM CHECKS

SYSTEM CHECKS

Next: End

RADIATORS ONLY WARM

CH PUMP

Next: End

THERMAL STORE

BOILER FAULT

Next: End

DHW FLOW RATE

DHW FLOW REGULATOR

Next: End

CH ON CONTINUOUSLY

CLOCK

Next: End

DHW TOO COOL

SECONDARY HEAT EXCHANGER

Next: End

DHW TOO COOL PUMP RUNS

DHW SENSOR

Next: End

MAINS ABS DISP PRESENT

STORE SENSOR

Next: End

DHW TOO COOL PUMP NOT RUNNING

DHW SENSOR

Next: End

DHW TOO HOT

DHW SENSOR

Next: End

DHW TOO HOT

PHE SENSOR

Next: End

BOILERPUMP

PCB & BOILER PUMP

Next: End

PCB + DHW PUMP

PCB & DHW PUMP

Next: End

PCB + CH PUMP

PCB & CH PUMP

Next: End

PUMP+PCB

PCB & BOILER PUMP

Next: End

Z DIRECTION

Z DIRECTION

Next: End

THERMAL STORE NOT UP TO TEMP

AIR IN SYSTEM

Next: End

DHW TOO COOL

AIR IN SYSTEM

Next: End

CH RADS DO NOT HEAT

AIR IN SYSTEM

Next: End

DHW FLOW RATE

DHW FILTER

Next: End

THERMAL STORE

Next: End

BOILER DEMAND

BOILER PUMP

Next: End

RADIATORS DO NOT HEAT

CH PUMP

Next: End

CH DEMAND

PCB

Next: End

RADIATORS DO NOT HEAT

EXTERNAL PROGRAMMER/ROOM THERMOSTAT

Next: End

RADIATORS DO NOT HEAT

CLOCK

Next: End

THERMAL STORE

Next: End

THERMAL STORE

BOILER PUMP

Next: End

DHW FLOW RATE

SECONDARY HEAT EXCHANGER

Next: End

CH ON CONTINUOUSLY

PCB

Next: End

DHW TOO COOL PUMP RUNS 2

PCB

Next: End

MAINS ABS DISP PRESENT

PCB

Next: End

PUMP (DHW)

DHW PUMP

Next: End

BLANK DISPLAY

PCB

Next: End

DHW TOO HOT

PCB

Next: End

CH PUMP

PCB

Next: End

BOILERPUMP

PCB

Next: End

DHW PUMP

PCB

Next: End

RADIATORS DO NOT HEAT

PCB

Next: End

BOILER DEMAND

Next: End

DHW TOO COOL

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p148

DHW TOO HOT

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p300

RADIATORS DO NOT HEAT

CHARACTERISTIC TEST FROM CH OPERATION

Next: p185

RADIATORS ONLY WARM

CHARACTERISTIC TEST FROM CH OPERATION

Next: p187

CH ON CONTINUOUSLY

CHARACTERISTIC TEST FROM CH OPERATION

Next: p267

MAINS VOLTAGE ABSENT / DISPLAY BLANK

CHARACTERISTIC TEST FROM BOILER DEMAND

Next: p97

MAINS VOLTAGE ABSENT / DISPLAY ILLUMINATED

CHARACTERISTIC TEST FROM BOILER DEMAND

Next: p107

DHW PUMP VOLTAGE PRESENT

Next: !p295, f296

CH PUMP VOLTAGE

Next: !p194, f195

EXTERNAL CONTROLS/ROOM THERMOSTAT CALLING

EXTERNAL CONTROLS CALLING FOR CH

Next: !p196, f197

CLOCK INPUT

Next: !p201, f305

BOILER PUMP VOLTAGE

Next: !p216, f309

MEASURE DHW TEMPERATURE FROM PCB

{ISOLATEMAINSPOWER}
ATTACH TEMPERATURE CLAMP AS INDICATED
USE INSULATION MAT AS REQUIRED

Next: p312, !f298

RESISTANCE PUMP

{ISOLATEMAINSPOWER}
GAIN ACCESS TO THE PUMP WIRING AT THE PUMP

Next: !p306, !f316

RESISTANCE PUMP

{ISOLATEMAINSPOWER}
GAIN ACCESS TO THE PUMP WIRING AT THE PUMP

Next: !p310, !f311

RESISTANCE PUMP

{ISOLATEMAINSPOWER}
GAIN ACCESS TO THE PUMP WIRING AT THE PUMP

Next: !p319, !f320

DHW FILTER

{ISOLATEMAINSPOWER}
MAINS WATER SUPPLY OFF
DRAIN DHW PIPEWORK

Next: p218, !f49

BOILER DEMAND

Next: p323, ?93, ?95

BOILER TEMPERATURE

Next: p213, !f212

BOILER PUMP VOLTAGE

Next: !p131, f318

MEASURE STORE TEMPERATURE FROM PCB

{ISOLATEMAINSPOWER}
REMOVE THE SENSOR FROM ITS HOUSING

Next: !p291, !f292

DHW PUMP RUNS

Next: p342, f160

MEASURE DHW TEMPERATURE FROM PCB

{ISOLATEMAINSPOWER}
ATTACH TEMPERATURE CLAMP AS INDICATED
USE INSULATION MAT AS REQUIRED

Next: p276, !f279

CH PUMP RUNS

Next: p349, f193

CH PUMP LIMPET TEST

Next: p207, !f208

SYSTEM BYPASS

Next: !p205, !f204

SYSTEM BYPASS

Next: !p209, !f210

BOILER PUMP RUNS

Next: !p214, f215

DHW FLOW REGULATOR

{ISOLATEMAINSPOWER}
MAINS WATER SUPPLY OFF
DRAIN DHW PIPEWORK

Next: !p219, !f220

RESISTANCE CLOCK

{ISOLATEMAINSPOWER}
DISCONNECT PLUG FOR CLOCK (UPPER MIDDLE RIGHT CONNECTIONS AS SHOWN)

Next: !p270, !f273

DIFFERENTIAL SECONDARY HEAT EXCHANGER

{ISOLATEMAINSPOWER}
ATTACH TEMPERATURE CLAMPS AS SHOWN

Next: !p277, !f278

MEASURE DHW TEMPERATURE FROM PCB

{ISOLATEMAINSPOWER}
ATTACH TEMPERATURE CLAMP AS INDICATED
USE INSULATION MAT AS REQUIRED

Next: p301, !f302

MEASURE PHE TEMPERATURE FROM PCB

{ISOLATEMAINSPOWER}
ATTACH TEMPERATURE CLAMP AS INDICATED
USE INSULATION MAT AS REQUIRED

Next: !p303, !f304

RESISTANCE PUMP

{ISOLATEMAINSPOWER}
GAIN ACCESS TO THE PUMP WIRING AT THE PUMP

Next: !p313, !f315

BOILER OPERATION

Next: p81, f78

BOILER PUMP RUNS

Next: !p82, f83

MAINS POWER SUPPLY

Next: p98, !f99

FUSE RESISTANCE

{ISOLATEMAINSPOWER}
REMOVE THE FUSE FROM THE FUSE HOLDER ON THE PCB

Next: !p299, !f106

System Information

  • Total Tests: 98
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control