47 415 09 IDEAL RESPONSE FF80
WARNING - IMPORTA
CH MODULATION
BOILER CH THERMOSTAT TO MAXIMUM
CONNECT U-GAUGE TO THE GAS VALVE OUTLET PRESSURE TEST POINT
SYSTEM PRESSURE RISE
BOILER CH THERMOSTAT TO MAXIMUM
CH OPERATION
BOILER CH THERMOSTAT TO MAXIMUM
DHW MODULATION
CONNECT A U-GAUGE TO
DHW FULL GAS PRESSURE
ATTACH U-GAUGE TO BURNER PRESSURE TEST POINT
DHW BURNER ESTABLISHED
ATTACH U-GAUGE TO BURNER PRESSURE TEST POINT
DHW BURNER IGNITES
REFIT INNER SEALING PANEL
ATTACH U-GAUGE TO BURNER PRESSURE TEST POINT
DHW FAN RUNS
REMOVE INNER COVER
DHW FULL GAS PRESSURE
SENSOR (DHW)
FAN VOLTAGE (FAN DISCONNECTED)
FAN HARNESS
FAN VOLTAGE (FULL)
FAN HARNESS
FAN VOLTAGE (FULL)
SENSING PIPE ASSEMBLY
DHW FULL GAS PRESSURE
INLET PRESSURE
GAS INLET PRESSURE
SENSING PIPE ASSEMBLY
HOT WATER OPERATION
SENSOR (DHW)
HOT WATER OPERATION
BURNER INJECTOR
BURNER PRESSURE DOES NOT REDUCE
SENSING PIPE ASSEMBLY
BURNER PRESSURE REDUCES, BURNER GOES OUT BUT FAN STILL RUNS
SENSING PIPE ASSEMBLY
DHW RUNS HOT THEN COLD WITH BOILER CYCLING
SENSOR (DHW)
ELECTRICAL CHECKS
SAFETY CHECKS
CH OPERATION
SENSOR (CH)
CH OPERATION
CH POTENTIOMETER
RADIATORS COOL BUT BOILER UP TO TEMPERATURE
DHW FLOW SWITCH ASSEMBLY
FAN PRESSURE (IGNITION)
PCB 38
BURNER PRESSURE DOES NOT REDUCE
SENSOR (DHW)
RADIATORS DO NOT HEAT, BOILER NOISY
DHW FLOW SWITCH ASSEMBLY
SYSTEM PRESSURE RISE
EXPANSION VESSEL
CH MODULATION
SENSOR (CH)
CH MODULATION
CH POTENTIOMETER
PUMP OVERRUN
PCB 38
RE-IGNITE DELAY
PCB 38
BURNER PRESSURE CORRECT, NO IGNITION
PCB 37 (SUPERSEDED BY 41)
DHW BURNER IGNITES
SPARK GENERATOR ASSEMBLY
DHW BURNER IGNITES
IGNITION SPARK ELECTRODES
DHW BURNER IGNITES
BURNER INJECTOR
FLAME SENSE CHARGE
PCB 37 (SUPERSEDED BY 41)
DHW NURNER ESTABLISHES
FLAME SENSE ELECTRODE LEAD
DHW FLOW RATE
FLOW ADJUSTER
DHW FLOW RATE
DHW INLET FILTER
DHW FLOW RATE
MAINS WATER SUPPLY
DHW FAN RUNS
ROCKER SWITCH (MAINS)
CH SWITCH VOLTAGE (INPUT)
PCB 38
CH BURNER IGNITION
PROGRAMME CONTROL BLOCK LINK
CH BURNER IGNITES
SENSOR (CH)
CH BURNER IGNITES
CH POTENTIOMETER
DHW FAN RUNS
BOILER OVERHEAT THERMOSTAT
DHW FAN RUNS
NON-RESETTABLE OVERHEAT
DHW FAN RUNS
SYSTEM PRESSURE
DHW FAN RUNS
FUSE F2
DHW FAN RUNS
FUSE F1 (PCB 38)
DHW FAN RUNS
DHW FLOW SWITCH ASSEMBLY
DHW FAN RUNS
SENSOR (DHW)
FAN VOLTAGE (FULL) (FAIL)
FAN HARNESS
FAN VOLTAGE (FULL) (PASS)
FAN HARNESS
DHW BURNER IGNITES
FUSE F1 (PCB 37)
FAN VOLTAGE IGNITION (FAN DISCONNECTED)
FAN HARNESS
FAN HARNESS AND CONNECTIONS
FAN HARNESS
DHW BURNER IGNITES
SENSING PIPE ASSEMBLY
DHW BURNER IGNITES
GAS VALVE
DHW BURNER IGNITES
GAS VALVE
DHW BURNER IGNITES
INLET PRESSURE
FAN VOLTAGE (FAN DISCONNECTED)
FAN ASSEMBLY
FAN SENSING PIPE ASSEMBLY
FAN ASSEMBLY
DHW FULL GAS PRESSURE
GAS VALVE
DHW HEAT EXCHANGER NOISY
HEAT EXCHANGER ASSEMBLY
HEAT EXCHANGER QUIET, DHW LOW TEMPERATURE
HEAT EXCHANGER ASSEMBLY
BURNER PRESSURE DOES NOT REDUCE
GAS VALVE
CH OPERATION
HEAT EXCHANGER ASSEMBLY
DHW FULL GAS PRESSURE
PCB 38
CH MODULATION
PCB 38
DHW BURNER IGNITES
BURNER
FLAME RECTIFICATION VOLTAGE
PCB 37 (SUPERSEDED BY 41)
DHW BURNER ESTABLISHES
BURNER
DHW BURNER ESTABLISHES
FLAME SENSE ELECTRODE
HEAT EXCHANGER - WATER PRESENT
HEAT EXCHANGER - WATER PRESENT
DHW FLOW RATE
HEAT EXCHANGER ASSEMBLY
CH BURNER IGNITION
ROCKER SWITCH (CH)
CH BURNER IGNITES
ROCKER SWITCH (CH)
DHW FAN RUNS
EMC FILTER
CH BURNER IGNITION
KIT - TIMER - INTERNAL
CH BURNER IGNITES
WIRING MAINS BLOCK TO PROGRAMMER
CH SENSOR RESISTANCE
PCB 38
DHW FAN RUNS
DHW OVERHEAT THERMOSTAT
DHW FAN RUNS
WATER PRESSURE SWITCH
DHW FAN RUNS
E02-144 TRANSFORMER
FAN VOLTAGE (FULL) (FAIL)
FAN ASSEMBLY
FAN VOLTAGE (FULL) (PASS)
FAN ASSEMBLY
DHW BURNER IGNITES
AIR PRESSURE SWITCH
BURNER PRESSURE INCORRECT
PCB 37 (SUPERSEDED BY 41)
FAN VOLTAGE IGNITION (FAN DISCONNECTED)
FAN ASSEMBLY
FAN HARNESS AND CONNECTIONS
FAN ASSEMBLY
DHW BURNER IGNITES
GAS VALVE
DHW HEAT EXCHANGER NOISY
CHARACTERISTIC TEST FROM HOT WATER OPERATION
HEAT EXCHANGER QUIET, DHW LOW TEMPERATURE
CHARACTERISTIC TEST FROM HOT WATER OPERATION
BURNER PRESSURE DOES NOT REDUCE
CHARACTERISTIC TEST FROM DHW MODULATION
BURNER PRESSURE REDUCES, BURNER GOES OUT BUT FAN STILL RUNS
CHARACTERISTIC TEST FROM DHW MODULATION
DHW RUNS HOT THEN COLD WITH BOILER CYCLING
CHARACTERISTIC TEST FROM DHW MODULATION
BOILER AND SYSTEM TEMPERATURE LOW
CHARACTERISTIC TEST FROM CH OPERATION
RADIATORS COOL BUT BOILER UP TO TEMPERATURE
CHARACTERISTIC TEST FROM CH OPERATION
RADIATORS DO NOT HEAT, BOILER NOISY
CHARACTERISTIC TEST FROM CH OPERATION
RADIATORS HEAT OK BUT HEAT EXCHANGER NOISY
CHARACTERISTIC TEST FROM CH OPERATION
ELECTRODE OR LEAD CONDITION POOR OR GAP INCORRECT
CHARACTERISTIC TEST FROM FLAME SENSE ELECTRODE
WATER PRESENT IN HEAT EXCHANGER WHEN BURNER REMOVED
CHARACTERISTIC TEST FROM FLAME SENSE ELECTRODE
VOLTAGE ABSENT ON ONE TEST BUT PRESENT ON OTHER
CHARACTERISTIC TEST FROM VOLTAGE PROGRAMMER OUTPUT
VOLTAGE ABSENT ON BOTH TESTS
CHARACTERISTIC TEST FROM VOLTAGE PROGRAMMER OUTPUT
BURNER PRESSURE INCORRECT
CHARACTERISTIC TEST FROM DHW BURNER IGNITES
BURNER PRESSURE CORRECT, NO IGNITION
CHARACTERISTIC TEST FROM DHW BURNER IGNITES
18/11/2016 13:09:01 1607_1_50_1 16/12/2016 10:50:54
18/11/2016 13:23:45
FUSE F1 (PCB 37)
REMOVE THE FUSE F1 LOCATED AT THE TOP L/H SIDE OF PCB 37 (MARKED F1)
GAS VALVE SOLENOID 1 RESISTANCE
DISCONNECT BLACK PLUG FROM THE LOWER SOLENOID
FAN HARNESS & CONNECTIONS
DISCONNECT THE FAN HARNESS WHICH RUNS FROM CON 9 ON PCB38 TO THE FAN
FAN HARNESS & CONNECTIONS
DISCONNECT THE FAN HARNESS WHICH RUNS FROM CON 9 ON PCB38 TO THE FAN
GAS VALVE 2 SOLENOID RESISTANCE
DISCONNECT BLACK PLUG FROM THE UPPER SOLENOID
GAS INLET PRESSURE
ATTACH A U-GAUGE TO THE GAS VALVE INLET PRESSURE TEST POINT