WORCESTER GREENSTAR COMPACT COMBI
GLOBALLY REPLACED
OBSERVATION BOILER SELF CHECK
ENSURE CENTRAL HEATING TURNED OFF
ENSURE APPLIANCE IS SET TO ECO MODE
OBSERVATION PUMP RUNS
ENSURE APPLIANCE IS SET TO ECO MODE
DHW TEMPERATURE CONTROL TO MAX
OBSERVATION FAN RUNS
ENSURE APPLIANCE IS SET TO ECO MODE
DHW TEMPERATURE CONTROL TO MAX
OBSERVATION BURNER IGNITION
ENSURE APPLIANCE IS SET TO ECO MODE
DHW TEMPERATURE CONTROL TO MAX
OPERATION DHW
DHW TEMPERATURE CONTROL TO MAX
OPERATION CH
CH TEMPERATURE CONTROL TO MAX
OBSERVATION PUMP OVERRUN
ENSURE BOILER IS SET TO ECO MODE
OPERATION PREHEAT
EXTERNAL AND INTERNA
FAULT CODE 210 E9
OUTSIDE MODEL
FAULT CODE 221 E9
OUTSIDE MODEL
FAULT CODE 231 FD
OUTSIDE MODEL
FAULT CODE 233 9U
OUTSIDE MODEL
FAULT CODE 240 241 286 D1 285 E9
OUTSIDE MODEL
FAULT CODE 228 F7
OUTSIDE MODEL
FAULT CODE 323 A8
OUTSIDE MODEL
FAULT CODE 260 345 EF
OUTSIDE MODEL
INFORMATION BOILER SETUP PARAMETERS
1. ENTER
FAULT CODE 219 220 277 E9
OUTSIDE MODEL
FAULT CODE 218 332 E5 222 E2 276 E9
OUTSIDE MODEL
FAULT CODE 212
OUTSIDE MODEL
FAULT CODE 373 8C
OUTSIDE MODEL
INFORMATION BOILER TEST MODES
1. ENTER
INFORMATION SETUP PARAMETER LIST
OUTSIDE MODEL, NOT CURRENTLY USED.
FAULT CODE 800 CC
OUTSIDE MODEL
FAULT CODE 234 EA
OUTSIDE MODEL
FAULT CODE 238 F0
OUTSIDE MODEL
OBSERVATION SPARKING HEARD
REMOVE AIR INTAKE FR
LITE DIAGNOSTIC
DIAGNOSIS RELIES ON
QUICK ACCESS DATA AND INFORMATION
THE TABLE BELOW SHOW
HEADER FOR QADAI SENSOR DHW
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI SENSOR FLOW
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI SENSOR RETURN
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI SENSOR SAFETY
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI SPARK GEN RESISTANCE
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI SPARK GEN VOLTAGE
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI PUMP RESISTANCE
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI PUMP VOLTAGE
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI FAN RESISTANCE
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI FAN VOLTAGE
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI DIVERTER VALVE VOLTAGE
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI GAS VALVE RESISTANCE
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI GAS VALVE VOLTAGE
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI FLOW TURBINE VOLTAGE
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI SENSOR DHW INLET
INTENTIONALLY BLANK FOR QADAI
HEADER FOR QADAI DIVERTER VALVE RESISTANCE
INTENTIONALLY BLANK - HEADER FOR QADAI
FAULT CODE 223 E2
SENSOR 18MM (FLOW)
FAULT CODE 240 241 286 D1 285 D9
HARNESS - LOW VOLTAGE
FAULT CODE 264 C1
HARNESS ASSEMBLY - HV & IGNITION
FAULT CODE 239 242-256 258 259 262 263 267 272 328 F0 257 B7
CONTROL BOX - SKIN MID
FAULT CODE H13
CONTROL BOX - SKIN MID
FAULT CODE 306 FA
FLUE
FAULT 306 FA
SYPHON - LCS
FAULT CODE 306 FA PASSING
GAS VALVE
FAULT CODE 306 FA NOT SHUTTING QUICKLY
GAS VALVE
FAULT CODE 327
RESET SWITCH
FAULT CODE 228 F7
HARNESS - LOW VOLTAGE
FAULT 228 F7
SYPHON - LCS
FAULT CODE 228 F7
CONTROL BOX - SKIN MID
FAULT CODE 323 A8 FW100 NOT FITTED
CONTROL BOX - SKIN MID
FAULT CODE 323 A8 FW100 FITTED
CONTROL BOX - SKIN MID
FAULT CODE 278 F0 RETURN SENSOR
HARNESS - LOW VOLTAGE
FAULT CODE 278 F0
SENSOR - NTC MAX (OVERHEAT)
FAULT CODE 278 F0
SENSOR 18MM (FLOW)
FAULT CODE 278 F0
SENSOR - TEMPERATURE (DHW)
FAULT CODE 375 376 E4 SENSOR NOT FITTED
HARNESS - LOW VOLTAGE
FAULT CODE 375 376 E4
SENSOR NTC - RIGHT ANGLED (DHW INLET SENSOR)
FAULT CODE 380 SENSOR NOT FITTED
CONTROL BOX - SKIN MID
FAULT CODE 380
SENSOR NTC - RIGHT ANGLED (DHW INLET SENSOR)
INFORMATION BOILER SETUP PARAMETERS
Z REDIRECT
FAULT CODE 219 220 277 E9 WILL NOT RESET
SENSOR - NTC MAX (OVERHEAT)
FAULT CODE 219 220 227 E9 WILL NOT RESET
CONTROL BOX - SKIN MID
FAULT CODE 219 220 277 E9
SYSTEM PRESSURE
FAULT CODE 219 220 277 E9
SENSOR 18MM (FLOW)
FAULT CODE 218 332 E5 222 E2 267 E9 WILL NOT RESET
CONTROL BOX - SKIN MID
FAULT CODE 218 332 E5 222 E2 267 E9
SYSTEM PRESSURE
FAULT CODE 218 332 E5 222 E2 267 E9
SENSOR 18MM (FLOW)
FAULT CODE 218 332 E5 222 E2 267 E9 WILL NOT RESET
SENSOR - NTC MAX (OVERHEAT)
FAULT CODE 260
SYSTEM PRESSURE
FAULT CODE 260
SENSOR 18MM (FLOW)
FAULT CODE 237 273 C4 274
CONTROL BOX - SKIN MID
FAULT CODE 212
SENSOR 18MM (FLOW)
FAULT CODE 212
SENSOR - NTC MAX (OVERHEAT)
FAULT CODE 212
PUMP
FAULT CODE 212
SYSTEM PRESSURE
FAULT CODE 271
SYSTEM PRESSURE
FAULT CODE 271
PUMP
FAULT CODE 271
SENSOR - NTC MAX (OVERHEAT)
FAULT CODE 271
SENSOR 18MM (FLOW)
FAULT CODE 373 8C
Z REDIRECT
FAULT CODE 373 8C
SYSTEM PRESSURE
FAULT CODE 373 8C
PUMP
FAULT CODE 373 8C WILL NOT RESET
SENSOR - NTC MAX (OVERHEAT)
FAULT CODE 373 8C
SENSOR 18MM (FLOW)
OBSERVATION BURNER IGNITION IGNITES BUT CUTS OUT
SENSOR 18MM (FLOW)
OBSERVATION BURNER IGNITION IGNITES BUT CUTS OUT
SENSOR - NTC MAX (OVERHEAT)
INFORMATION BOILER TEST MODES
Z REDIRECT
INFORMATION SETUP PARAMETER LIST
Z REDIRECT
ALTERNATIVE TESTS VOLTAGE RECTIFICATION CIRCUIT (NO DISPLAY)
HARNESS - LOW VOLTAGE
DUMMY OPERATION PREHEAT (NO DISPLAY) 2
Z REDIRECT
OPERATION DHW FLOW RATE NOT OBTAINABLE
ISOLATION VALVES
OPERATION DHW DHW COOL RADS COOL
SENSOR - TEMPERATURE (DHW)
FAULT CODE 800 CC SENSOR NOT FITTED
CONTROL BOX - SKIN MID
FAULT CODE 800 CC SENSOR FITTED
CONTROL BOX - SKIN MID
COMBUSTION TEST
ELECTRODE
FAULT CODE 278 F0
SENSOR NTC - RIGHT ANGLED (DHW INLET SENSOR)
OBSERVATION PUMP RUNS INSUFFICIENT FLOW
WATER SUPPLY (BELOW MINIMUM)
OPERATION DHW
WATER SUPPLY (INSUFFICIENT)
OBSERVATION FAN RUNS NO RESPONSE TO DHW NO INLET SENSOR
CONTROL BOX - SKIN MID
OPERATION DHW TOO COOL BOILER CUTS OUT
PLATE HEAT EXCHANGER
OPERATION CH UP TO TEMP RADS DO NOT HEAT STUCK OPEN
VALVE - BY-PASS
OBSERVATION FAN RUNS
SENSOR 18MM (FLOW)
OBSERVATION BURNER IGNITION DOES NOT IGNITE
SYPHON - LCS
OBSERVATION BURNER IGNITION DOES NOT IGNITE
VALVE - GAS - AIR (BEARING PLATE)
OBSERVATION BURNER IGNITION
CONTROL BOX - SKIN MID AND GAS VALVE
OBSERVATION BURNER IGNITION TO GAS VALVE SPARK NO IGNITION
HARNESS ASSEMBLY - HV & IGNITION
OBSERVATION BURNER IGNITION NO IGNITION
PIPE - SUCTION (AIR INTAKE)
OBSERVATION BURNER IGNITION IGNITION LEAD
HARNESS ASSEMBLY - HV & IGNITION
OBSERVATION BURNER IGNITION NO SPARKING
GAS VALVE
FAULT CODE 278 F0 NO INLET SENSOR
CONTROL BOX - SKIN MID
OBSERVATION BURNER IGNITION NO POWER TO SPARK GEN
CONTROL BOX - SKIN MID
OBSERVATION BURNER IGNITION HARNESS TO SPARK GENERATOR NO SPARKING
HARNESS ASSEMBLY - HV & IGNITION
OBSERVATION BURNER IGNITION DOES NOT ESTABLISH
VALVE - GAS - AIR (BEARING PLATE)
OBSERVATION BURNER IGNITION DOES NOT ESTABLISH
PIPE - SUCTION (AIR INTAKE)
OBSERVATION BURNER IGNITION RECTIFICATION GROUND
HARNESS - LOW VOLTAGE
OBSERVATION BURNER IGNITION RECTIFICATION LEAD
HARNESS - LOW VOLTAGE
OBSERVATION BURNER IGNITION IGNITION LEAD NO SPARKING
HARNESS ASSEMBLY - HV & IGNITION
OBSERVATION BOILER SELF CHECK BOILER SELF CHECK
FROST PROTECTION
OBSERVATION BOILER SELF CHECK FROST PROTECTION
SENSOR 18MM (FLOW)
OBSERVATION BOILER SELF CHECK FROST PROTECTION
OPEN TAP OR LEAK
OBSERVATION BOILER SELF CHECK FROST PROTECTION INTERNAL CONTROLS
CONTROL BOX - SKIN MID
OBSERVATION BOILER SELF CHECK PUMP RUNS AFTER SELF CHECK
FROST PROTECTION
OBSERVATION BOILER SELF CHECK FROST PROTECTION PUMP ONLY
SENSOR 18MM (FLOW)
OBSERVATION BURNER IGNITION BAFFLES
SYPHON - LCS
OBSERVATION BURNER IGNITION BAFFLES
VALVE - GAS - AIR (BEARING PLATE)
OBSERVATION BURNER IGNITION BAFFLES
PIPE - SUCTION (AIR INTAKE)
OPERATION CH SHUTS DOWN BEFORE TEMP
HEAT EXCHANGER ASSEMBLY
OPERATION CH INSUFFICIENT HEAT TEMP SETTINGS
BOILER SETUP PARAMETERS
FURTHER INVESTIGATION FUSE PCB
GAS VALVE
FURTHER INVESTIGATION FUSE PCB
TRANSFORMER - IGNITION
FURTHER INVESTIGATION FUSE
CONTROL BOX - SKIN MID
FURTHER INVESTIGATION MAINS FUSE
GAS VALVE
FURTHER INVESTIGATION MAINS FUSE
TRANSFORMER - IGNITION
FURTHER INVESTIGATION MAINS FUSE
CONTROL BOX - SKIN MID
OBSERVATION DISPLAY ILLUMINATES FAULTY DISPLAY
CONTROL BOX - SKIN MID
OPERATION CH INSUFFICIENT HEAT
VALVE - GAS - AIR (BEARING PLATE)
FAULT CODE 229 EA BAFFLES
SYPHON - LCS
FAULT CODE 229 EA BAFFLES
VALVE - GAS - AIR (BEARING PLATE)
FAULT CODE 229 EA BAFFLES
PIPE - SUCTION (AIR INTAKE)
FAULT CODE 229 EA BAFFLES OR NOISY
HOUSING - BURNER
FAULT CODE 229 EA DOES NOT ESTABLISH
VALVE - GAS - AIR (BEARING PLATE)
FAULT CODE 229 EA DOES NOT ESTABLISH
PIPE - SUCTION (AIR INTAKE)
FAULT CODE 229 EA RECTIFICATION GROUND
HARNESS - LOW VOLTAGE
FAULT CODE 229 EAN RECTIFICATION LEAD
HARNESS - LOW VOLTAGE
FAULT CODE 229 EADOES NOT IGNITE
SYPHON - LCS
FAULT CODE 229 EA DOES NOT IGNITE
VALVE - GAS - AIR (BEARING PLATE)
FAULT CODE 229 EA
CONTROL BOX - SKIN MID AND GAS VALVE
FAULT CODE 229 EA TO GAS VALVE SPARK NO IGNITION
HARNESS ASSEMBLY - HV & IGNITION
FAULT CODE 229 EA NO IGNITION
PIPE - SUCTION (AIR INTAKE)
FAULT CODE 229 EA IGNITION LEAD
HARNESS ASSEMBLY - HV & IGNITION
FAULT CODE 229 EA SPARK BUT NO IGNITION
ELECTRODE
FAULT CODE 229 EA IGNITES OK
VALVE - GAS - AIR (BEARING PLATE)
FAULT CODE 229 EA IGNITES OK
INLET PRESSURE
FAULT CODE 229 EA IGNITION OK
ELECTRODE
FAULT CODE 234 EA
GAS VALVE
FAULT CODE 238 F0 RESETS BUT FAULT REOCCURS
HARNESS ASSEMBLY - HV & IGNITION
FAULT CODE 234 EA
Z REDIRECT
OBSERVATION SPARKING HEARD
Z REDIRECT
OBSERVATION FAN RUNS NO RESPONSE TO DHW
SENSOR NTC - RIGHT ANGLED (DHW INLET SENSOR)
FAULT CODE 238 F0
WATER INGRESS
FAULT CODE 238 F0 WILL NOT RESET
GAS VALVE
FAULT CODE 260 345 EF
HARNESS ASSEMBLY - HV & IGNITION
FAULT CODE 260 345 EF NO POWER TO PUMP
CONTROL BOX - SKIN MID
OBSERVATION CH DEMAND NOT RESPONDING TO DEMAND
CONTROL BOX - SKIN MID
FAULT CODE 271 NO POWER TO PUMP
CONTROL BOX - SKIN MID
FAULT CODE 271
HARNESS ASSEMBLY - HV & IGNITION
OBSERVATION CH DEMAND NO POWER TO EXT CONTROLS
CONTROL BOX - SKIN MID
FAULT CODE 373 8C NO POWER TO PUMP
CONTROL BOX - SKIN MID
FAULT CODE 373 8C
HARNESS ASSEMBLY - HV & IGNITION
OBSERVATION BURNER IGNITION BAFFLES OR NOISY
HOUSING - BURNER
FAULT CODE 218 332 E5 222 E2 267 E9
HEAT EXCHANGER ASSEMBLY
FAULT CODE 219 220 277 E9
HEAT EXCHANGER ASSEMBLY
FAULT CODE 373 8C
HEAT EXCHANGER ASSEMBLY
FAULT CODE 271
HEAT EXCHANGER ASSEMBLY
INFORMATION USER DISPLAY
Z REDIRECT
OBSERVATION DISPLAY ILLUMINATES PUMP RUNS AFTER SELF CHECK
FROST PROTECTION
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK FROST PROTECTION PUMP ONLY
SENSOR 18MM (FLOW)
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK
FROST PROTECTION
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK FROST PROTECTION
SENSOR 18MM (FLOW)
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK FROST PROTECTION
OPEN TAP OR LEAK
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK FROST PROTECTION INTERNAL CONTROLS
CONTROL BOX - SKIN MID
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK SENSOR OVERHEAT
SENSOR - NTC MAX (OVERHEAT)
OBSERVATION BOILER SELF CHECK NO DISPLAY
WATER INGRESS
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK INCORRECT POWER FAN PULSING
CONTROL BOX - SKIN MID
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK FAN PULSES
HARNESS ASSEMBLY - HV & IGNITION
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK CODE PLUG
HARNESS - LOW VOLTAGE
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK NO POWER TO FAN
CONTROL BOX - SKIN MID
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK FAN DOES NOT RUN
HARNESS ASSEMBLY - HV & IGNITION
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK NO VOLTAGE TO PUMP
CONTROL BOX - SKIN MID
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK
HARNESS ASSEMBLY - HV & IGNITION
OBSERVATION DISPLAY ILLUMINATES DISPLAY 1
Z REDIRECT
OBSERVATION PUMP RUNS DHW ISOLATIONNO DISPLAY
ISOLATION VALVES
OBSERVATION PUMP RUNS INSUFFICIENT FLOWNO DISPLAY
WATER SUPPLY (BELOW MINIMUM)
OBSERVATION PUMP RUNS NO POWER TO DHW TURBINENO DISPLAY
CONTROL BOX - SKIN MID
OBSERVATION PUMP RUNS DHW TURBINENO DISPLAY
HARNESS - LOW VOLTAGE
OBSERVATION FAN RUNS RETURN SENSORNO DISPLAY
HARNESS - LOW VOLTAGE
OBSERVATION FAN RUNSNO DISPLAY
SENSOR 18MM (FLOW)
OBSERVATION FAN RUNS DHW SENSORNO DISPLAY
SENSOR - TEMPERATURE (DHW)
OPERATION CH REACHES TEMP RADS DO NOT HEAT
SYSTEM PRESSURE
OBSERVATION FAN RUNS NOT FIRING FOR DHWNO DISPLAY
SENSOR - NTC MAX (OVERHEAT)
OBSERVATION FAN RUNSNO DISPLAY
LIMITER - TEMPERATURE (FLUE STAT)
OBSERVATION FAN RUNS NO RESPONSE TO DHW NO INLET SENSORNO DISPLAY
CONTROL BOX - SKIN MID
OPERATION CH BOILER REACHES TEMP RADS DO NOT HEAT
ISOLATION VALVES
OBSERVATION FAN RUNS NO RESPONSE TO DHWNO DISPLAY
SENSOR NTC - RIGHT ANGLED (DHW INLET SENSOR)
OPERATION DHW TOO COOL BOILER STAYS LIT
VALVE - GAS - AIR (BEARING PLATE)
OPERATION DHW TOO COOL STAYS LIT
SENSOR - TEMPERATURE (DHW)
OPERATION DHW TOO COOL BOILER STAYS LIT
SENSOR NTC - RIGHT ANGLED (RETURN SENSOR)
OPERATION DHW TOO COOL RADS COOL
PLATE HEAT EXCHANGER
FAULT CODE 258 356 EH
CONTROL BOX - SKIN MID
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK
SENSOR 18MM (FLOW)
OPERATION PREHEAT NOT RESPONDING TO DEMAND NO PROGRAMMER
CONTROL BOX - SKIN MID
OPERATION PREHEAT NO RESPONDING TO DEMAND
CONTROL BOX - SKIN MID
COMBUSTION TEST
PIPE - SUCTION (AIR INTAKE)
COMBUSTION TEST
SYPHON - LCS
COMBUSTION TEST MAX AND MINIMUM
HEAT EXCHANGER ASSEMBLY
FAULT CODE 229 EA IGNITES OK
PIPE - SUCTION (AIR INTAKE)
FAULT CODE 229 EA IGNITES OK
SYPHON - LCS
FAULT CODE 1001 - 1008 - BATTERIES ETC
COMFORT CONTROLS
FAULT CODE 1001 - 1008
CONTROL BOX - SKIN MID
EXTERNAL MIXING DILUTING DHW TEMPERATURE
EXTERNAL MIXING
BLANK FOR LITE DIAGNOSTIC
Z REDIRECT
BLANK FOR QADAI
Z REDIRECT
QADAI
SENSOR - TEMPERATURE (DHW)
OPERATION CH UP TO TEMP RADS DO NOT HEAT
HARNESS - LOW VOLTAGE
QADAI
SENSOR 18MM (FLOW)
QADAI
SENSOR NTC - RIGHT ANGLED (RETURN SENSOR)
QADAI
SENSOR - NTC MAX (OVERHEAT)
QADAI
TRANSFORMER - IGNITION
SPARK GEN VOLTAGE QADAI
CONTROL BOX - SKIN MID
OPERATION CH SHUTS DOWN BEFORE TEMP
SYSTEM PRESSURE
PUMP VOLTAGE QADAI
CONTROL BOX - SKIN MID
FAN VOLTAGE QADAI
CONTROL BOX - SKIN MID
QADAI
FAN
DIVERTER VALVE VOLTAGE QADAI
CONTROL BOX - SKIN MID
RESISTANCE INCORRECT QADAI
GAS VALVE
GAS VALVE VOLTAGE QADAI
CONTROL BOX - SKIN MID
BURNER IGNITES BUT BAFFLES OUT OR NOISY
MIXING UNIT ASSEMBLY
OBSERVATION BURNER IGNITION BAFFLES
FLUEWAYS
SPARKING HEARD NO IGNITION
MIXING UNIT ASSEMBLY
OBSERVATION BURNER IGNITION
BURNER
IGNITES BUT DOES NOT ESTABLISH
MIXING UNIT ASSEMBLY
SPARKING HEARD NO IGNITION FAULT CODE
MIXING UNIT ASSEMBLY
FAULT CODE 229 EA
BURNER
FAULT CODE 229 EA DOES NOT IGNITE
FLUEWAYS
IGNITES BUT DOES NOT ESTABLISH FAULT CODE
MIXING UNIT ASSEMBLY
IGNITES BUT BAFFLES OUT OR NOISY FAULT CODE
MIXING UNIT ASSEMBLY
FAULT CODE 229 EA BAFFLES
FLUEWAYS
QADAI
SENSOR NTC - RIGHT ANGLED (DHW INLET SENSOR)
QADAI
SENSOR - FLOW (TURBINE)
BOILER REMAINS LIT RADS ONLY WARM
MIXING UNIT ASSEMBLY
FAULT CODE 229 EA 374 8C
MIXING UNIT ASSEMBLY
DHW COOL RADS STAY COOL
MIXING UNIT ASSEMBLY
QADAI
MOTOR - DIVERTER VALVE
OPERATION DHW DHW COOL RADS HOT
CONTROL BOX - SKIN MID
OPERATION DHW DHW COOL RADS HOT
HARNESS - LOW VOLTAGE
OPERATION CH SHUTS DOWN BEFORE TEMP
BOILER SETUP PARAMETERS
OPERATION DHW TOO HOT
SENSOR - TEMPERATURE (DHW)
OPERATION CH UP TO TEMP RADS DO NOT HEAT NO VOLTAGE TO DIVERTER
CONTROL BOX - SKIN MID
OPERATION DHW TOO COOL BOILER STAYS LIT
INLET PRESSURE
INFORMATION CASE REMOVAL
Z REDIRECT
FAULT CODES
Z REDIRECT
OBSERVATION FAN RUNS DHW SENSOR
SENSOR - TEMPERATURE (DHW)
OBSERVATION FAN RUNS NOT FIRING FOR DHW
SENSOR - NTC MAX (OVERHEAT)
OBSERVATION FAN RUNS
LIMITER - TEMPERATURE (FLUE STAT)
TYPE OF DIAGNOSTIC PROCEDURE
Z REDIRECT
OBSERVATION DISPLAY ILLUMINATES
FUSE (FUSED SPUR)
OBSERVATION DISPLAY ILLUMINATES
FUSE INTERNAL 5A
OBSERVATION DISPLAY ILLUMINATES ALL OFF
CONTROL BOX - SKIN MID
OBSERVATION DISPLAY ILLUMINATES BLANK DISPLAY
HARNESS - LOW VOLTAGE
OBSERVATION PUMP RUNS NO POWER TO DHW TURBINE
CONTROL BOX - SKIN MID
OBSERVATION PUMP RUNS DHW TURBINE
HARNESS - LOW VOLTAGE
OBSERVATION FAN RUNS RETURN SENSOR
HARNESS - LOW VOLTAGE
OBSERVATION CH DEMAND NOT RESPONDING TO DEMAND NO PROGRAMMER
CONTROL BOX - SKIN MID
OBSERVATION PUMP RUNS DHW ISOLATION
ISOLATION VALVES
OPERATION CH SHUTS DOWN BEFORE TEMP
SENSOR 18MM (FLOW)
OPERATION CH SHUTS DOWN BEFORE TEMP
SENSOR - NTC MAX (OVERHEAT)
OPERATION CH SHUTS DOWN BEFORE TEMP
SENSOR NTC - RIGHT ANGLED (RETURN SENSOR)
OPERATION CH INSUFFICIENT HEAT OUTPUT SETTINGS
BOILER SETUP PARAMETERS
OPERATION CH INSUFFICIENT HEAT
INLET PRESSURE
OPERATION DHW DHW COOL RADS COLD
SYSTEM PRESSURE
OBSERVATION PUMP OVERRUN
BOILER SETUP PARAMETERS
OPERATION DHW INSUFFICENT HEAT NO VOLTAGE TO DIVERTER
CONTROL BOX - SKIN MID
OPERATION DHW INSUFFICIENT HEAT
HARNESS - LOW VOLTAGE
FAULT CODE H11
SENSOR - TEMPERATURE (DHW)
FAULT CODE 210 E9
LIMITER - TEMPERATURE (FLUE STAT)
FAULT CODE 221 E9
SENSOR - NTC MAX (OVERHEAT)
FAULT CODE 221 E9
HARNESS - LOW VOLTAGE
FAULT CODE 233 9U
CODE PLUG
OBSERVATION BOILER SELF CHECK NO VOLTAGE TO PUMP
CONTROL BOX - SKIN MID
OBSERVATION BOILER SELF CHECK
HARNESS ASSEMBLY - HV & IGNITION
FAULT CODE 233 9U
HARNESS - LOW VOLTAGE
FAULT CODE 231 FD
CONTROL BOX - SKIN MID
FAULT CODE 223 E2
HARNESS - LOW VOLTAGE
FAULT CODE 240 241 286 D1 285 D9
CONTROL BOX - SKIN MID
FAULT CODE 240 241 286 D1 285 D9
SENSOR NTC - RIGHT ANGLED (RETURN SENSOR)
FAULT CODE 228 F7
Z REDIRECT
FAULT CODE H13
Z REDIRECT
FAULT CODE 327
CONTROL BOX - SKIN MID
FAULT CODE 306 FA
CONTROL BOX - SKIN MID
FAULT 228 F7
ELECTRODE
FAULT CODE 278 F0
Z REDIRECT
FAULT CODE 278 F0
SENSOR NTC - RIGHT ANGLED (RETURN SENSOR)
FAULT CODE 278 F0 SAFETY SENSOR
HARNESS - LOW VOLTAGE
FAULT CODE 278 F0 FLOW SENSOR
HARNESS - LOW VOLTAGE
FAULT CODE 278 F0 DHW SENSOR
HARNESS - LOW VOLTAGE
FAULT CODE 375 376 E4 SENSOR NOT FITTED
CONTROL BOX - SKIN MID
FAULT CODE 375 376 F4
Z REDIRECT
FAULT CODE 375 376 E4 SENSOR FITTED
CONTROL BOX - SKIN MID
FAULT CODE 375 376 E4 SENSOR FITTED
HARNESS - LOW VOLTAGE
FAULT CODE 380
EXTERNAL HEAT SOURCE
FAULT CODE 380 SENSOR FITTED
CONTROL BOX - SKIN MID
FAULT CODE 219 220 277 E9
HARNESS - LOW VOLTAGE
FAULT CODE 218 332 E5 222 E2 267 E9
HARNESS - LOW VOLTAGE
FAULT CODE 260 STUCK IN FAULT CODE
CONTROL BOX - SKIN MID
FAULT CODE 237 273 C4 274
Z REDIRECT
FAULT CODE 212
CONTROL BOX - SKIN MID
OBSERVATION BURNER IGNITION IGNITES BUT CUTS OUT
CONTROL BOX - SKIN MID
DUMMY OPERATION PREHEAT (NO DISPLAY) 1
Z REDIRECT
OPERATION DHW FLOW RATE NOT OBTAINABLE
PLATE HEAT EXCHANGER
OPERATION DHW FLOW RATE NOT OBTAINABLE
SENSOR - FLOW (TURBINE)
OPERATION DHW FLOW RATE NOT OBTAINABLE
FILTER - DCW
OPERATION DHW FLOW RATE NOT OBTAINABLE
REGULATOR
OPERATION DHW FLOW RATE NOT OBTAINABLE
BODY BRASS - SILENCER (NOZZLES)
OPERATION DHW FLOW RATE NOT OBTAINABLE
ADAPTOR - FLOW - LIMITER
FAULT CODE 800 CC
Z REDIRECT
COMBUSTION TEST DROPS ON MINIMUM
GAS VALVE
FAULT CODE 278 F0
CONTROL BOX - SKIN MID
FAULT CODE 278 F0 DHW INLET SENSOR
HARNESS - LOW VOLTAGE
OPERATION DHW DHW COOL RADS COLD LOW FAN SPEED
CONTROL BOX - SKIN MID
OBSERVATION BURNER IGNITION NO IGNITION
INLET PRESSURE
OBSERVATION BURNER IGNITION NO IGNITION NO DROP
NOZZLE (INJECTOR)
OBSERVATION BURNER IGNITION NO POWER TO GAS VALVE
CONTROL BOX - SKIN MID
OBSERVATION BURNER IGNITION
CONTROL BOX - SKIN MID AND HARNESS ASSEMBLY
OBSERVATION BURNER IGNITION SPARKING NO IGNITION
NOZZLE (INJECTOR)
OBSERVATION BURNER IGNITION NO IGNITION
TRANSFORMER - IGNITION
OBSERVATION BURNER IGNITION TO GAS VALVE NO SPARKING
HARNESS ASSEMBLY - HV & IGNITION
OPERATION CH INSUFFICIENT HEAT
CONTROL BOX - SKIN MID
OPERATION DHW TOO HOT
CONTROL BOX - SKIN MID
OBSERVATION BURNER IGNITION NO SPARKING
TRANSFORMER - IGNITION
OBSERVATION BURNER IGNITION NO SPARKING
ELECTRODE
OBSERVATION BURNER IGNITION NO VOLTAGE TO RECTIFICATION CIRCUIT
CONTROL BOX - SKIN MID
OBSERVATION BURNER IGNITION RECTIFICATION SHORTING
HARNESS - LOW VOLTAGE
OBSERVATION BURNER IGNITION NOT RECOGNISING RECIFICATION VOLTAGE
CONTROL BOX - SKIN MID
OBSERVATION BURNER IGNITION NOT ESTABLISHING LOW VOLTAGE
CONTROL BOX - SKIN MID
OBSERVATION BOILER SELF CHECK FROST PROTECTION
INTERNAL TIMER
OBSERVATION BOILER SELF CHECK FROST PROTECTION
CONTROL BOX - SKIN MID
OBSERVATION BOILER SELF CHECK FROST PROTECTION PUMP RUNS
CONTROL BOX - SKIN MID
OBSERVATION BURNER IGNITION BURNER BAFFLES
NOZZLE (INJECTOR)
OBSERVATION BURNER IGNITION BURNER BAFFLES
HOSE - GAS
OPERATION CH SHUTS DOWN BEFORE TEMP STUCK LOW TEMP
CONTROL BOX - SKIN MID
FURTHER INVESTIGATION FUSE PCB PUMP
HARNESS ASSEMBLY - HV & IGNITION
FURTHER INVESTIGATION FUSE PCB GAS VALVE
HARNESS ASSEMBLY - HV & IGNITION
FURTHER INVESTIGATION FUSE PCB FAN
HARNESS ASSEMBLY - HV & IGNITION
FURTHER INVESTIGATION
FUSE INTERNAL 5A FURTHER INVESTIGATION
FURTHER INVESTIGATION FUSE PCB SPARK GENERATOR
HARNESS ASSEMBLY - HV & IGNITION
FURTHER INVESTIGATION MAINS FUSE PUMP
HARNESS ASSEMBLY - HV & IGNITION
FURTHER INVESTIGATION MAINS FUSE GAS VALVE
HARNESS ASSEMBLY - HV & IGNITION
FURTHER INVESTIGATION MAINS FUSE FAN
HARNESS ASSEMBLY - HV & IGNITION
FURTHER INVESTIGATION
FUSE (FUSED SPUR) FURTHER INVESTIGATION
FURTHER INVESTIGATION MAINS FUSE SPARK GENERATOR
HARNESS ASSEMBLY - HV & IGNITION
OPERATION CH INSUFFICIENT HEAT
FLUEWAYS
FAULT CODE 229 EA BURNER BAFFLES
NOZZLE (INJECTOR)
FAULT CODE 229 EA IGNITION BURNER BAFFLES
HOSE - GAS
FAULT CODE 229 EA BAFFLES
GAS VALVE
FAULT CODE 229 EA NO VOLTAGE TO RECTIFICATION CIRCUIT
CONTROL BOX - SKIN MID
FAULT CODE 229 EA RECTIFICATION SHORTING
HARNESS - LOW VOLTAGE
FAULT CODE 229 EA NOT RECOGNISING RECIFICATION VOLTAGE
CONTROL BOX - SKIN MID
FAULT CODE 229 EA NOT ESTABLISHING LOW VOLTAGE
CONTROL BOX - SKIN MID
FAULT CODE 229 EA NO IGNITION
INLET PRESSURE
FAULT CODE 229 EA NO IGNITION NO DROP
NOZZLE (INJECTOR)
FAULT CODE 229 EA NO IGNITION NO DROP
HOSE - GAS
FAULT CODE 229 EA NO POWER TO GAS VALVE
CONTROL BOX - SKIN MID
FAULT CODE 229 EA
CONTROL BOX - SKIN MID AND HARNESS ASSEMBLY
FAULT CODE 229 EA NO PRESSURE DROP
GAS VALVE
FAULT CODE 229 EA SPARKING NO IGNITION
NOZZLE (INJECTOR)
FAULT CODE 229 EA NO IGNITION PRESSURE DROP
HOSE - GAS
FAULT CODE 229 EA NO IGNITION
TRANSFORMER - IGNITION
FAULT CODE 229 EA PRESSURE DROP SEEN
GAS VALVE
FAULT CODE 299 EA IGNITES OK
FLUEWAYS
FAULT CODE 229 EA
NO FAULT FOUND
FAULT CODE 234 EA
HARNESS ASSEMBLY - HV & IGNITION
FAULT CODE 234 EA
CONTROL BOX - SKIN MID
OBSERVATION FAN RUNS NO RESPONSE TO DHW WITH INLET SENSOR
CONTROL BOX - SKIN MID
OBSERVATION FAN RUNS DHW INLET SENSOR
HARNESS - LOW VOLTAGE
OBSERVATION FAN RUNS
EXTERNAL HEAT SOURCE
FAULT CODE 238 F0
CONTROL BOX - SKIN MID
FAULT CODE 238 F0 WILL NOT RESET
HARNESS ASSEMBLY - HV & IGNITION
OBSERVATION CH DEMAND
INTERNAL TIMER
FAULT CODE 271 STUCK
PUMP
OBSERVATION BURNER IGNITION BAFFLES
GAS VALVE
FAULT CODE 218 332 E5 222 E2 267 E9
PLATE HEAT EXCHANGER
FAULT CODE 218 332 E5 222 E2 267 E9 NOT SHUTTING DOWN
CONTROL BOX - SKIN MID
FAULT CODE 219 220 277 E9
PLATE HEAT EXCHANGER
FAULT CODE 219 220 277 E9 NOT SHUTTING DOWN
CONTROL BOX - SKIN MID
FAULT CODE 373 8C
CONTROL BOX - SKIN MID
FAULT CODE 373 8C
PLATE HEAT EXCHANGER
FAULT CODE 271
PLATE HEAT EXCHANGER
FAULT CODE 271
CONTROL BOX - SKIN MID
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK FROST PROTECTION PUMP RUNS
CONTROL BOX - SKIN MID
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK FROST PROTECTION
CONTROL BOX - SKIN MID
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK SAFETY SENSOR
HARNESS - LOW VOLTAGE
OPERATION CH
EXPANSION VESSEL
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK STUCK IN FAULT
CONTROL BOX - SKIN MID
OBSERVATION DISPLAY ILLUMINATES SELF CHECK FAN RUNS CONSTANT SPEED
HARNESS ASSEMBLY - HV & IGNITION
OBSERVATION PUMP RUNS INSUFFICIENT FLOW RATENO DISPLAY
PLATE HEAT EXCHANGER
OBSERVATION PUMP RUNS INSUFFICIENT FLOW RATENO DISPLAY
SENSOR - FLOW (TURBINE)
OBSERVATION PUMP RUNSNO DISPLAY
FILTER - DCW
OBSERVATION PUMP RUNSNO DISPLAY
REGULATOR
OBSERVATION PUMP RUNSNO DISPLAY
BODY BRASS - SILENCER (NOZZLES)
OBSERVATION PUMP RUNSNO DISPLAY
ADAPTOR - FLOW - LIMITER
OBSERVATION PUMP RUNS IGNORING DEMANDNO DISPLAY
CONTROL BOX - SKIN MID
OBSERVATION PUMP RUNS TURBINE FAULTYNO DISPLAY
SENSOR - FLOW (TURBINE)
NO DISPLAY
CONTROL BOX - SKIN MID (NO DISPLAY)
OBSERVATION FAN RUNSNO DISPLAY
SENSOR NTC - RIGHT ANGLED (RETURN SENSOR)
OBSERVATION FAN RUNS FLUE SENSORNO DISPLAY
HARNESS - LOW VOLTAGE
OBSERVATION FAN RUNSNO DISPLAY
EXTERNAL HEAT SOURCE
OBSERVATION FAN RUNS NO RESPONSE TO DHW WITH INLET SENSORNO DISPLAY
CONTROL BOX - SKIN MID
OBSERVATION FAN RUNS DHW INLET SENSORNO DISPLAY
HARNESS - LOW VOLTAGE
OPERATION DHW TOO COOL BOILER STAYS LIT
NOZZLE (INJECTOR)
OPERATION DHW TOO COOL BOILER STAYS LIT
HOSE - GAS
FAULT CODE 258 356 EH
Z REDIRECT
OBSERVATION PUMP OVERRUN DHW
CONTROL BOX - SKIN MID
OBSERVATION DISPLAY ILLUMINATES BOILER SELF CHECK FLOW SENSOR
HARNESS - LOW VOLTAGE
OPERATION PREHEAT
INTERNAL TIMER
OPERATION PREHEAT STUCK IN ECO
CONTROL BOX - SKIN MID
OPERATION PREHEAT NOT FIRING WITH PREHEAT DISPLAYED
CONTROL BOX - SKIN MID
COMBUSTION TEST FAILED AIR INTEGRITY FAILED
SEAL - CONDENSATE COLLECTOR
COMBUSTION TEST FAILED AIR INTEGRITY FAILED
SEAL - FLUE
OPERATION CH REACHES TEMP RADS DO NOT HEAT
DIVERTER VALVE ASSEMBLY
COMBUSTION TEST FAILED AIR INTEGRITY OK
SEAL - CONDENSATE COLLECTOR
COMBUSTION TEST FAILED AIR INTEGRITY OK
SEAL - FLUE
COMBUSTION TEST
NOZZLE (INJECTOR)
COMBUSTION TEST
HOSE - GAS
COMBUSTION TEST FAILS COMBUSTION
GAS VALVE
FAULT CODE 229 EA COMBUSTION TEST FAILED AIR INTEGRITY FAILED
SEAL - CONDENSATE COLLECTOR
FAULT CODE 229 EA COMBUSTION TEST FAILED AIR INTEGRITY OK
SEAL - CONDENSATE COLLECTOR
FAULT CODE 229 EA IGNITES OK
NOZZLE (INJECTOR)
FAULT CODE 229 EA IGNITES OK
HOSE - GAS
FAULT CODE 1001 - 1008 STUCK FAULTY
COMFORT CONTROLS
OPERATION CH UP TO TEMP RADS DO NOT HEAT
MOTOR - DIVERTER VALVE
OPERATION DHW TOO COOL BOILER STAYS LIT
CONTROL BOX - SKIN MID
SENSOR DHW
RESULT AS EXPECTED
SENSOR FLOW
RESULT AS EXPECTED
SENSOR RETURN
RESULT AS EXPECTED
SENSOR SAFETY
RESULT AS EXPECTED
SPARK GEN RESISTANCE
RESULT AS EXPECTED
SPARK GEN VOLTAGE
RESULT AS EXPECTED
PUMP RESISTANCE
RESULT AS EXPECTED
PUMP VOLTAGE
RESULT AS EXPECTED
FAN VOLTAGE
RESULT AS EXPECTED
FAN RESISTANCE
RESULT AS EXPECTED
DIVERTER VALVE VOLTAGE
RESULT AS EXPECTED
GAS VALVE RESISTANCE
RESULT AS EXPECTED
GAS VALVE VOLTAGE
RESULT AS EXPECTED
FLOW TURBINE VOLTAGE
RESULT AS EXPECTED
FAULT CODE 229 EA DOES NOT ESTABLISH
FLUEWAYS
SENSOR DHW INLET
RESULT AS EXPECTED
DIVERTER VALVE RESISTANCE
RESULT AS EXPECTED
OPERATION DHW DHW COOL RADS HOT
DIVERTER VALVE ASSEMBLY
OPERATION DHW DHW COOL RADS HOT
MOTOR - DIVERTER VALVE
OBSERVATION FAN RUNS FLUE SENSOR
HARNESS - LOW VOLTAGE
OBSERVATION DISPLAY ILLUMINATES MAINS FUSE
Z REDIRECT
OBSERVATION DISPLAY ILLUMINATES BLANK DISPLAY
SENSOR - FLOW (TURBINE)
OBSERVATION PUMP RUNS INSUFFICIENT FLOW RATE
PLATE HEAT EXCHANGER
OBSERVATION PUMP RUNS INSUFFICIENT FLOW RATE
SENSOR - FLOW (TURBINE)
OBSERVATION PUMP RUNS
FILTER - DCW
OBSERVATION PUMP RUNS
REGULATOR
OBSERVATION PUMP RUNS
BODY BRASS - SILENCER (NOZZLES)
OBSERVATION PUMP RUNS
ADAPTOR - FLOW - LIMITER
OBSERVATION PUMP RUNS DOES NOT RECOGNISING DEMAND
CONTROL BOX - SKIN MID
OBSERVATION PUMP RUNS IGNORING DEMAND
CONTROL BOX - SKIN MID
OBSERVATION PUMP RUNS TURBINE FAULTY
SENSOR - FLOW (TURBINE)
OBSERVATION FAN RUNS
SENSOR NTC - RIGHT ANGLED (RETURN SENSOR)
OPERATION CH SHUTS DOWN BEFORE TEMP
LIMITER - TEMPERATURE (FLUE STAT)
OPERATION CH INSUFFICIENT HEAT
NOZZLE (INJECTOR)
OPERATION CH INSUFFICIENT HEAT
HOSE - GAS
OBSERVATION PUMP OVERRUN CH
CONTROL BOX - SKIN MID
OBSERVATION PUMP OVERRUN DOES NOT OVERRUN
CONTROL BOX - SKIN MID
OPERATION DHW INSUFFICIENT HEAT
MOTOR - DIVERTER VALVE
OPERATION DHW INSUFFICIENT HEAT
DIVERTER VALVE ASSEMBLY
FAULT CODE H11
CONTROL BOX - SKIN MID
FAULT CODE H11
HARNESS - LOW VOLTAGE
FAULT CODE 210 E9
CONTROL BOX - SKIN MID
FAULT CODE 210 E9
HARNESS - LOW VOLTAGE
FAULT CODE 210 E9
OVERHEAT - FLUE
FAULT CODE 210 E9
FLUEWAYS
FAULT 210 E9
LIMITER - TEMPERATURE (FLUE STAT)
FAULT CODE 221 E9
CONTROL BOX - SKIN MID
FAULT CODE 231 FD
Z REDIRECT
FAULT CODE 233 9U
CONTROL BOX - SKIN MID
FAULT CODE 223 E2
CONTROL BOX - SKIN MID
FAULT CODE D4 (STATUS 271) DISPLAYED SHORTLY AFTER IGNITION
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION
ALTERNATIVE TO VOLTAGE SPARK GENERATOR AT PCB
CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE
ALTERNATIVE TO OBSERVATION FAULT CODE AT SHUTDOWN
CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE
ALTERNATIVE TO TEMPERATURE DIFFERENTIAL SAFETY AND FLOW
CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE
ALTERNATIVE TO OBSERVATION RECTIFICATION CURRENT
CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE
ALTERNATIVE TO OBSERVATION SPARK GENERATOR OUTPUT
CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE
ALTERNATIVE TO OPERATION PREHEAT
CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE
ALTERNATIVE TO TEMPERATURE DIFFERENTIAL SAFETY AND FLOW DHW
CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE
FLOW SENSOR BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
FILTER BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
FLOW REGULATOR BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
NOZZLES BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
ADAPTOR BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
ALTERNATIVE TO VOLTAGE DIVERTER VALVE AT PCB
CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE
ALTERNATIVE TO OBSERVATION DIVERTER MOVEMENT IN OP CH RADS DO NOT HEAT
CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE
COMBUSTION TEST FAILED
CHARACTERISTIC TEST FROM COMBUSTION TEST MAX AND MINIMUM
BOILER DROPS OUT ON MINIMUM RATE
CHARACTERISTIC TEST FROM COMBUSTION TEST MAX AND MINIMUM
ALTERNATIVE TO OBSERVATION DIVERTER MOVEMENT
CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE
ALTERNATIVE TO OBSERVATION DIVERTER MOVEMENT IN OP CH INSUFF HEAT
CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE
SPARKING HEARD BUT NO IGNITION
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION
NO PRESSURE DROP OBSERVED
CHARACTERISTIC TEST FROM PRESSURE GAS INLET AND DROP
PRESSURE DROPS BELOW 16 5MB
CHARACTERISTIC TEST FROM PRESSURE GAS INLET AND DROP
INJECTOR BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
INJECTOR BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
NO SPARKING HEARD
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION
APPROX 90V AC MEASURED
CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT
VOLTAGE LESS THAN 30V AC MEASURED
CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT
BURNER IGNITES SMOOTHLY BUT DOES NOT ESTABLISH (SPARKING CONTINUES)
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION
BOILER ATTEMPTS TO FIRE AFTER SELF CHECK
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
PUMP RUNS CONTINUOUSLY AFTER SELF CHECK
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
BURNER IGNITES BUT BAFFLES OUT OR IS NOISY
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION
INJECTOR BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
SPARKING HEARD BUT NO IGNITION OR IGNITION INTERMITTENT
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION FAULT CODE 229
BURNER IGNITES SMOOTHLY BUT DOES NOT ESTABLISH OR ESTABLISHES INTERMITTENTLY
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION FAULT CODE 229
BURNER IGNITES BUT BAFFLES OUT OR IS NOISY
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION
INJECTOR BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
APPROX 90V AC MEASURED
CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT
VOLTAGE LESS THAN 30V AC MEASURED
CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT
NO PRESSURE DROP OBSERVED
CHARACTERISTIC TEST FROM PRESSURE GAS INLET AND DROP
PRESSURE DROPS BELOW 16 5MB
CHARACTERISTIC TEST FROM PRESSURE GAS INLET AND DROP
INJECTOR BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
INJECTOR BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
COMBUSTION TEST FAILED
CHARACTERISTIC TEST FROM COMBUSTION TEST MAX AND MINIMUM
BOILER DROPS OUT ON MINIMUM RATE
CHARACTERISTIC TEST FROM COMBUSTION TEST MAX AND MINIMUM
ALTERNATIVE TO TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH
CHARACTERISTIC TEST FROM ALTERNATIVE TEST LIST USED IF DISPLAY NOT AVAILABLE
FLOW RATE NOT OBTAINABLE
CHARACTERISTIC TEST FROM OPERATION DHW
BOILER CUTS OUT OR HOT WATER RUNS HOT COLD
CHARACTERISTIC TEST FROM OPERATION DHW
PUMP DOES NOT RUN
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
FAN DOES NOT RUN
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK NO DISPLAY
FAN PULSES 3 TIMES AT INCREASING SPEEDS THEN RUNS FOR 2 MINUTES
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK NO DISPLAY
FAN RUNS AT A CONSTANT SPEED FOR 2 MINUTES
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK NO DISPLAY
BOILER ATTEMPTS TO FIRE AFTER SELF CHECK
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
PUMP RUNS CONTINUOUSLY AFTER SELF CHECK
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
EXCESSIVE SYSTEM PRESSURE RISE
CHARACTERISTIC TEST FROM OPERATION CH
DHW TOO COOL, RADIATORS HOT
CHARACTERISTIC TEST FROM OPERATION DHW
BOILER REACHES TEMPERATURE, RADIATORS DO NOT HEAT OR ONLY GET WARM
CHARACTERISTIC TEST FROM OPERATION CH
FLOW SENSOR BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
FILTER BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
FLOW REGULATOR BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
NOZZLES BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
ADAPTOR BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
INJECTOR BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
PUMP DOES NOT OVERRUN ON DHW
CHARACTERISTIC TEST FROM OBSERVATION PUMP OVERRUN
DIVERTER DOES NOT MOVE ON EITHER TEST
CHARACTERISTIC TEST FROM OBSERVATION DIVERTER MOTOR MOVEMENT
DISPLAY CHANGES TO ECO MODE WITH CLOCK SYMBOL
CHARACTERISTIC TEST FROM OPERATION PREHEAT
APPLIANCE WILL NOT LEAVE ECO MODE
CHARACTERISTIC TEST FROM OPERATION PREHEAT
DISPLAY SHOWS PREHEAT BUT DOES NOT FIRE
CHARACTERISTIC TEST FROM OPERATION PREHEAT
LOWER CONDENSATE SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS
DIVERTER ONLY MOVES WHEN REMOVED FROM HOUSING
CHARACTERISTIC TEST FROM OBSERVATION DIVERTER MOTOR MOVEMENT
UPPER CONDENSATE SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS
INNER FLUE SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS
LOWER CONDENSATE SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS
UPPER CONDENSATE SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS
INNER FLUE SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS
INJECTOR BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
GAS SUPPLY TUBE BLOCKED RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS
LOWER CONDENSATE SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS
UPPER CONDENSATE SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS
INNER FLUE SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS
LOWER CONDENSATE SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS
UPPER CONDENSATE SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS
INNER FLUE SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS
INJECTOR BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
GAS SUPPLY TUBE BLOCKED RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION FLUE SEALS
BOILER SHUTS DOWN BEFORE REACHING TEMPERATURE
CHARACTERISTIC TEST FROM OPERATION CH
DHW TOO COOL, RADS COOL, BOILER STAYS LIT
CHARACTERISTIC TEST FROM OPERATION DHW
DHW TOO HOT
CHARACTERISTIC TEST FROM OPERATION DHW
PUMP DOES NOT RUN
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
DISPLAY SHOWS ZERO FLOW RATE
CHARACTERISTIC TEST FROM OBSERVATION DHW MIN FLOW RATE
DISPLAY SHOWS FLOW RATE LESS THAN 2 LITRES A MINTUE
CHARACTERISTIC TEST FROM OBSERVATION DHW MIN FLOW RATE
FLOW SENSOR BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
FILTER BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
FLOW REGULATOR BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
NOZZLES BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
ADAPTOR BLOCKED AND/OR POOR CONDITION
CHARACTERISTIC TEST FROM INSPECTION FLOW COMPONENTS
BOILER REMAINS LIT BUT BOILER AND RADIATORS ONLY GET WARM
CHARACTERISTIC TEST FROM OPERATION CH
INJECTOR BLOCKED OR RESTRICTED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
GAS SUPPLY TUBE BLOCKED, RESTRICTED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION GAS SUPPLY TUBE
PUMP OVERRUNS EXCESSIVELY
CHARACTERISTIC TEST FROM OBSERVATION PUMP OVERRUN
PUMP OVERRUNS FOR LESS THAN 3 MINUTES ON CH OR DOES NOT OVERRUN
CHARACTERISTIC TEST FROM OBSERVATION PUMP OVERRUN
DIVERTER DOES NOT MOVE ON EITHER TEST
CHARACTERISTIC TEST FROM OBSERVATION DIVERTER MOTOR MOVEMENT
DIVERTER ONLY MOVES WHEN REMOVED FROM HOUSING
CHARACTERISTIC TEST FROM OBSERVATION DIVERTER MOTOR MOVEMENT
FLUE TEMPERATURE REACHES APPROX 95°C OR HIGHER
CHARACTERISTIC TEST FROM TEMPERATURE EXHAUST GAS (FAULT CODE)
RETURNS TO FAULT CODE, FLUE TEMPERATURE BELOW 95°C
CHARACTERISTIC TEST FROM TEMPERATURE EXHAUST GAS (FAULT CODE)
24/04/2023 10:56:28 2303_2_50_1 21/06/2023 13:18:01
27/04/2023 13:30:24
RESISTANCE SENSOR RETURN AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE HARNESS RETURN SENSOR
DISCONNECT PLUG FROM
RESISTANCE HARNESS FAN
DISCONNECT FAN CONNECTOR FROM FAN
INFORMATION SERVICE REMINDER
H13 IS THE CODE TO I
INSPECTION RECTIFICATION LEADS
{GAINPCBACS}
REMOVE BOILER CASING
DISCONNECT THE AIR INTAKE
OBSERVATION BOILER RESET FAULT 278 F0
ENSURE APPLIANCE IS COOL
RESISTANCE SENSOR FLOW AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
RESISTANCE SENSOR SAFETY
DISCONNECT WIRES FROM SAFETY SENSOR
RESISTANCE HARNESS RETURN SENSOR
DISCONNECT PLUG FROM
RESISTANCE SENSOR DHW
DISCONNECT WIRES FROM DHW SENSOR
RESISTANCE HARNESS DHW INLET SENSOR
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
OBSERVATION BOILER RESET 375 376 F4
ENSURE APPLIANCE IS COOL
RESISTANCE SENSOR DHW INLET
DISCONNECT PLUG FROM DHW INLET SENSOR
RESISTANCE SENSOR DHW INLET
DISCONNECT PLUG FROM DHW INLET SENSOR
RESISTANCE SENSOR SAFETY AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE SENSOR SAFETY
DISCONNECT WIRES FROM SAFETY SENSOR
RESISTANCE SENSOR FLOW AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
INFORMATION APPLIANCE OVERHEAT
DUE TO THE DESIGN OF
OBSERVATION IS OUTDOOR TEMPERATURE SENSOR FITTED
GAIN ACCESS TO LOWER PCB PANEL
RESISTANCE SENSOR DHW INLET
DISCONNECT PLUG FROM DHW INLET SENSOR
RESISTANCE GAS VALVE AND HARNESS
DISCONNECT CONNECTOR X4 FROM THE PCB
RESISTANCE GAS VALVE
DISCONNECT PLUG FROM GAS VALVE
RESISTANCE IGNITION LEAD
DISCONNECT THE IGNIT
RESISTANCE GAS VALVE
DISCONNECT PLUG FROM GAS VALVE
VOLTAGE SPARK GENERATOR AT PCB
{GAINPCBACS}
RESISTANCE RECTIFICATION ELECTRODE TO EARTH
DISCONNECT LEAD FROM RECTIFICATION ELECTRODE
OBSERVATION DISCONNECT CH LINK
REMOVE THE LINK BETWEEN L AND LR FOR CH
ENSURE CENTRAL HEATING TURNED OFF
RESISTANCE MAINS IN FURTHER INVESTIGATION
GAIN ACCESS TO THE LOWER PANEL OF THE PCB
RESISTANCE PUMP FURTHER INVESTIGATION
DISCONNECT CONNECTOR FROM PUMP
RESISTANCE GAS VALVE FURTHER INVESTIGATION
DISCONNECT PLUG FROM GAS VALVE
RESISTANCE FAN FURTHER INVESTIGATION
DISCONNECT CONNECTOR FROM FAN
RESISTANCE SPARK GENERATOR FURTHER INVESTIGATION
DISCONNECT CONNECTOR FROM SPARK GENERATOR
RESISTANCE MAINS IN FURTHER INVESTIGATION
GAIN ACCESS TO THE LOWER PANEL OF THE PCB
RESISTANCE PUMP FURTHER INVESTIGATION
DISCONNECT CONNECTOR FROM PUMP
RESISTANCE GAS VALVE FURTHER INVESTIGATION
DISCONNECT PLUG FROM GAS VALVE
RESISTANCE FAN FURTHER INVESTIGATION
DISCONNECT CONNECTOR FROM FAN
RESISTANCE SPARK GENERATOR FURTHER INVESTIGATION
DISCONNECT CONNECTOR FROM SPARK GENERATOR
OBSERVATION BURNER IGNITION FAULT CODE 229
ENSURE APPLIANCE IS SET TO ECO MODE
RESISTANCE RECTIFICATION ELECTRODE TO EARTH
DISCONNECT LEAD FROM RECTIFICATION ELECTRODE
RESISTANCE GAS VALVE AND HARNESS
DISCONNECT CONNECTOR X4 FROM THE PCB
RESISTANCE GAS VALVE
DISCONNECT PLUG FROM GAS VALVE
RESISTANCE IGNITION LEAD
DISCONNECT THE IGNIT
RESISTANCE GAS VALVE
DISCONNECT PLUG FROM GAS VALVE
RESISTANCE SENSOR DHW INLET AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE SENSOR DHW INLET
DISCONNECT PLUG FROM DHW INLET SENSOR
VOLTAGE CH DEMAND INTO BOILER
GAIN ACCESS TO LOWER PCB PANEL
RESISTANCE GAS VALVE TO EARTH
DISCONNECT PLUG FROM GAS VALVE
VOLTAGE PUMP AT PCB
{GAINPCBACS}
VOLTAGE PUMP AT PCB
{GAINPCBACS}
VOLTAGE PUMP AT PCB
{GAINPCBACS}
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH
CH TEMPERATURE CONTROL TO MAX
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH
CH TEMPERATURE CONTROL TO MAX
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH
CH TEMPERATURE CONTROL TO MAX
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH
CH TEMPERATURE CONTROL TO MAX
OBSERVATION DISCONNECT CH LINK
REMOVE THE LINK BETWEEN L AND LR FOR CH
ENSURE CENTRAL HEATING TURNED OFF
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
RESISTANCE SENSOR SAFETY
DISCONNECT WIRES FROM SAFETY SENSOR
RESISTANCE GAS VALVE TO EARTH
DISCONNECT PLUG FROM GAS VALVE
RESISTANCE SENSOR RETURN AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE HARNESS RETURN SENSOR
DISCONNECT PLUG FROM
RESISTANCE SENSOR FLUE
DISCONNECT WIRES FROM FLUE SENSOR
RESISTANCE SENSOR DHW INLET AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE SENSOR DHW INLET
DISCONNECT PLUG FROM DHW INLET SENSOR
VOLTAGE MAINS POWER IN FAULT CODE
GAIN ACCESS TO THE LOWER PANEL OF THE PCB
RESISTANCE SENSOR DHW
DISCONNECT WIRES FROM DHW SENSOR
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
RESISTANCE SENSOR RETURN AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE SENSOR SAFETY
DISCONNECT WIRES FROM SAFETY SENSOR
RESISTANCE SPARK GENERATOR (QADAI)
DISCONNECT CONNECTOR FROM SPARK GENERATOR
VOLTAGE SPARK GENERATOR AT PCB
{GAINPCBACS}
RESISTANCE PUMP (QADAI)
DISCONNECT CONNECTOR FROM PUMP
VOLTAGE PUMP AT PCB
{GAINPCBACS}
RESISTANCE FAN (QADAI)
DISCONNECT CONNECTOR FROM FAN
VOLTAGE FAN SELF CHECK
{GAINPCBACS}
VOLTAGE DIVERTER VALVE AT PCB
{GAINPCBACS}
DISCONNECT PLUG FROM DIVERTER VALVE AND MAKE SAFE
RESISTANCE GAS VALVE
DISCONNECT PLUG FROM GAS VALVE
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
VOLTAGE FLOW TURBINE INTO BOILER
{GAINPCBACS}
RESISTANCE SENSOR DHW INLET
DISCONNECT PLUG FROM DHW INLET SENSOR
RESISTANCE DIVERTER VALVE AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X7 FROM THE PCB
VOLTAGE DIVERTER VALVE AT PCB
{GAINPCBACS}
DISCONNECT PLUG FROM DIVERTER VALVE AND MAKE SAFE
RESISTANCE SENSOR RETURN AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE SENSOR FLUE
DISCONNECT WIRES FROM FLUE SENSOR
OBSERVATION DOES APPLIANCE RUN SELF CHECK
REMOVE THE OUTER CASING
VOLTAGE MAINS POWER IN
GAIN ACCESS TO THE LOWER PANEL OF THE PCB
RESISTANCE FUSE (MAINS FUSE)
REMOVE THE FUSE FROM THE FUSED SPUR
RESISTANCE HARNESS RETURN SENSOR
DISCONNECT PLUG FROM
TEMPERATURE EXHAUST GAS
CH TEMPERATURE CONTR
RESISTANCE SENSOR DHW
DISCONNECT WIRES FROM DHW SENSOR
RESISTANCE SENSOR FLUE AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X7 FROM THE PCB
RESISTANCE SENSOR FLUE
DISCONNECT WIRES FROM FLUE SENSOR
INSPECTION CODE PLUG
{GAINPCBACS}
RESISTANCE SENSOR FLOW AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
PRESSURE STANDING RETURN
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
OBSERVATION DISCONNECT RECTIFICATION LEADS
DISCONNECT THE RECTI
DISCONNECT FW100 CONTROLS
DISCONNECT FW100 OR
RESISTANCE SENSOR SAFETY AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE SENSOR RETURN AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE SENSOR DHW AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE SENSOR DHW INLET AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
TEMPERATURE DHW INLET
ATTACH TEMPERATURE CLAMP TO DHW INLET PIPE
OBSERVATION BOILER RESET
ENSURE APPLIANCE IS COOL
INFORMATION APPLIANCE OVERHEAT
DUE TO THE DESIGN OF
RESISTANCE SENSOR FLOW AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
OBSERVATION BOILER RESET
ENSURE APPLIANCE IS COOL
INFORMATION APPLIANCE OVERHEAT
DUE TO THE DESIGN OF
RESISTANCE SENSOR SAFETY
DISCONNECT WIRES FROM SAFETY SENSOR
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW DHW
DHW TEMPERATURE CONTROL TO MAX
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
RESISTANCE SENSOR SAFETY
DISCONNECT WIRES FROM SAFETY SENSOR
RESISTANCE SENSOR SAFETY
DISCONNECT WIRES FROM SAFETY SENSOR
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
RESISTANCE SENSOR SAFETY
DISCONNECT WIRES FROM SAFETY SENSOR
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW DHW
DHW TEMPERATURE CONTROL TO MAX
RESISTANCE SENSOR SAFETY
DISCONNECT WIRES FROM SAFETY SENSOR
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
VOLTAGE SPARK GENERATOR AT PCB (NO DISPLAY)
{GAINPCBACS}
VOLTAGE RECTIFICATION CIRCUIT (NO DISPLAY)
{GAINPCBACS}
RESISTANCE RECTIFICATION LEAD (NO DISPLAY)
{GAINPCBACS}
INSPECTION FLOW COMPONENTS
HOT WATER CIRCUIT ISOLATED AND DRAINED
RESISTANCE SENSOR DHW
DISCONNECT WIRES FROM DHW SENSOR
VOLTAGE DIVERTER VALVE AT PCB (DISTANT FUSE SPUR)
{GAINPCBACS}
DISC
DISCONNECT OUTDOOR SENSOR
DISCONNECT THE PLUG FOR THE OUTDOOR TEMPERATURE SENSOR (BLUE CONNECTOR) AND MAKE SAFE
OBSERVATION DIVERTER MOVEMENT (DISTANT FUSE SPUR) NO CH
DISCONNECT THE CONNECTOR TO THE GAS VALVE AND MAKE SAFE
INSPECTION RECTIFICATION ELECTRODE
SLIDE THE SPARK GENE
RESISTANCE SENSOR DHW INLET AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
OBSERVATION DIVERTER MOVEMENT OFF ONLY (DISTANT FUSE SPUR)
DISCONNECT THE CONNE
OBSERVATION DIVERTER MOVEMENT (DISTANT FUSE SPUR) POOR CH
DISCONNECT THE CONNECTOR TO THE GAS VALVE AND MAKE SAFE
TEMPERATURE DHW INLET
ATTACH TEMPERATURE CLAMP TO DHW INLET PIPE
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW DHW
DHW TEMPERATURE CONTROL TO MAX
TEMPERATURE INTEGRAL BYPASS
ATTACH TEMPERATURE PROBE TO CH FLOW PIPE
RESISTANCE SENSOR FLOW AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
PRESSURE FAN LOCKOUT
1. ATTACH FGA
PRESSURE GAS INLET AND DROP
ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT
INSPECTION AIR INTAKE FAN
REMOVE THE FAN AIR INTAKE FROM THE FAN
INSPECTION GAS SUPPLY TUBE
UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
RESISTANCE HARNESS GAS VALVE
DISCONNECT THE PLUG FROM THE GAS VALVE
INSPECTION GAS SUPPLY TUBE
UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE
OBSERVATION SPARK GENERATOR OUTPUT
REMOVE THE AIR INTAK
INSPECTION ELECTRODE ASSEMBLY
SLIDE THE SPARK GENE
RESISTANCE GAS VALVE AND HARNESS
DISCONNECT CONNECTOR X4 FROM THE PCB
OBSERVATION DISCONNECT SPARK ELECTRODE LEAD
REMOVE THE AIR INTAK
RESISTANCE HARNESS PCB TO SPARK GENERATOR
DISCONNECT PLUG FROM THE SPARK GENERATOR
RESISTANCE IGNITION LEAD (OPEN CIRCUIT CHECK)
DISCONNECT THE IGNIT
PRESSURE FAN LOCKOUT
1. ATTACH FGA
INSPECTION AIR INTAKE FAN
REMOVE THE FAN AIR INTAKE FROM THE FAN
VOLTAGE RECTIFICATION CIRCUIT
{GAINPCBACS}
ATTACH A CROCODILE CLIP TO THE RECTIFICATION LEAD
RESISTANCE RECTIFICATION LEAD
{GAINPCBACS}
DISC
RESISTANCE HARNESS RECTIFICATION GROUND
DISCONNECT X5 FROM THE PCB
DISCONNECT THE FLAME SENSE LEAD FROM THE SAFETY SENSOR
RESISTANCE RECTIFICATION CIRCUIT TO EARTH
{GAINPCBACS}
DISCONNECT CONNECTOR X5 FROM THE PCB
INSPECTION RECTIFICATION ELECTRODE
SLIDE THE SPARK GENE
TEMPERATURE FLOW (BOILER FIRING)
REMOVE AIR INTAKE FROM APPLIANCE
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
OBSERVATION DISCONNECT FLOW TURBINE (DEMAND CHECK)
DISCONNECT FLOW TURBINE FROM ITS INLINE CONNECTOR AND MAKE SAFE
ENSURE CENTRAL HEATING TURNED OFF
VOLTAGE CH DEMAND INTO BOARD (NO DEMAND)
GAIN ACCESS TO LOWER PCB PANEL
ENSURE CENTRAL HEATING TURNED OFF
TEMPERATURE FLOW (PUMP RUNNING)
REMOVE AIR INTAKE FROM APPLIANCE
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
RESISTANCE FROST PROTECTION
GAIN ACCESS TO LOWER PCB PANEL
PRESSURE FAN LOCKOUT
1. ATTACH FGA
INSPECTION GAS SUPPLY TUBE
UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH
CH TEMPERATURE CONTROL TO MAX
INSPECTION CH TEMP SETTING
CH TEMPERATURE CONTROL KNOB SET TO MAX
RESISTANCE PUMP AND HARNESS FURTHER INVESTIGATION
{GAINPCBACS}
DISCONNECT CONNECTOR X11 FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS FURTHER INVESTIGATION
DISCONNECT CONNECTOR X4 FROM THE PCB
RESISTANCE FAN AND HARNESS FURTHER INVESTIGATION
DISCONNECT CONNECTOR X3 FROM THE PCB
RESISTANCE SPARK GENERATOR AND HARNESS FURTHER INVESTIGATION
DISCONNECT CONNECTOR X3 AND FROM THE PCB
RESISTANCE PUMP AND HARNESS FURTHER INVESTIGATION
{GAINPCBACS}
DISCONNECT CONNECTOR X11 FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS FURTHER INVESTIGATION
DISCONNECT CONNECTOR X4 FROM THE PCB
RESISTANCE FAN AND HARNESS FURTHER INVESTIGATION
DISCONNECT CONNECTOR X3 FROM THE PCB
RESISTANCE SPARK GENERATOR AND HARNESS FURTHER INVESTIGATION
DISCONNECT CONNECTOR X3 AND FROM THE PCB
PRESSURE FAN MAX RATE
ATTACH FGA TO FAN PR
INSPECTION BURNER ASSEMBLY
REMOVE THE FAN HOOD ASSEMBLY
PRESSURE FAN MAX RATE
ATTACH FGA TO FAN PR
PRESSURE FAN LOCKOUT
1. ATTACH FGA
PRESSURE FAN LOCKOUT
1. ATTACH FGA
PRESSURE FAN LOCKOUT
1. ATTACH FGA
INSPECTION AIR INTAKE FAN
REMOVE THE FAN AIR INTAKE FROM THE FAN
INSPECTION GAS SUPPLY TUBE
UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE
INSPECTION HOUSING BURNER
REMOVE THE BURNER HOUSING FROM THE BOILER ASSEMBLY
REMOVE THE SILENCER FROM THE BURNER HOUSING
INSPECTION AIR INTAKE FAN
REMOVE THE FAN AIR INTAKE FROM THE FAN
VOLTAGE RECTIFICATION CIRCUIT
{GAINPCBACS}
ATTACH A CROCODILE CLIP TO THE RECTIFICATION LEAD
RESISTANCE RECTIFICATION LEAD
{GAINPCBACS}
DISC
RESISTANCE HARNESS RECTIFICATION GROUND
DISCONNECT X5 FROM THE PCB
DISCONNECT THE FLAME SENSE LEAD FROM THE SAFETY SENSOR
RESISTANCE RECTIFICATION CIRCUIT TO EARTH
{GAINPCBACS}
DISCONNECT CONNECTOR X5 FROM THE PCB
INSPECTION RECTIFICATION ELECTRODE
SLIDE THE SPARK GENE
PRESSURE GAS INLET AND DROP
ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT
INSPECTION AIR INTAKE FAN
REMOVE THE FAN AIR INTAKE FROM THE FAN
INSPECTION GAS SUPPLY TUBE
UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
RESISTANCE HARNESS GAS VALVE
DISCONNECT THE PLUG FROM THE GAS VALVE
INSPECTION GAS SUPPLY TUBE
UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE
OBSERVATION SPARK GENERATOR OUTPUT
REMOVE THE AIR INTAK
INSPECTION ELECTRODE ASSEMBLY
SLIDE THE SPARK GENE
PRESSURE GAS INLET
ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT
INSPECTION RECTIFICATION ELECTRODE
SLIDE THE SPARK GENE
RESISTANCE GAS VALVE AND HARNESS
DISCONNECT CONNECTOR X4 FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS TO EARTH
DISCONNECT CONNECTOR X4 FROM THE PCB
DISCONNECT INTERNAL CONTROLS CH
DISCONNECT THE INTEG
RESISTANCE HARNESS PUMP
DISCONNECT THE PLUG FROM THE PUMP
RESISTANCE HARNESS PUMP
DISCONNECT THE PLUG FROM THE PUMP
OBSERVATION PUMP RUNS
ENSURE APPLIANCE IS SET TO ECO MODE
DHW TEMPERATURE CONTROL TO MAX
RESISTANCE HARNESS PUMP
DISCONNECT THE PLUG FROM THE PUMP
INSPECTION HOUSING BURNER
REMOVE THE BURNER HOUSING FROM THE BOILER ASSEMBLY
REMOVE THE SILENCER FROM THE BURNER HOUSING
INSPECTION BURNER ASSEMBLY
REMOVE THE FAN HOOD ASSEMBLY
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH
CH TEMPERATURE CONTROL TO MAX
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW DHW
DHW TEMPERATURE CONTROL TO MAX
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH
CH TEMPERATURE CONTROL TO MAX
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH
CH TEMPERATURE CONTROL TO MAX
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW DHW
DHW TEMPERATURE CONTROL TO MAX
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW CH
CH TEMPERATURE CONTROL TO MAX
OBSERVATION BOILER SELF CHECK NO DISPLAY
ENSURE CENTRAL HEATING TURNED OFF
INFORMATION SET BOILER TO ECO
BECAUSE IT IS NOT PO
VOLTAGE PUMP AT PCB
{GAINPCBACS}
INSPECTION CODE PLUG
{GAINPCBACS}
VOLTAGE FAN SELF CHECK
{GAINPCBACS}
RESISTANCE SENSOR FLOW AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
TEMPERATURE FLOW (BOILER FIRING)
REMOVE AIR INTAKE FROM APPLIANCE
TEMPERATURE FLOW (PUMP RUNNING)
REMOVE AIR INTAKE FROM APPLIANCE
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
RESISTANCE FROST PROTECTION
GAIN ACCESS TO LOWER PCB PANEL
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
OBSERVATION DISCONNECT FLOW TURBINE (DEMAND CHECK)
DISCONNECT FLOW TURBINE FROM ITS INLINE CONNECTOR AND MAKE SAFE
ENSURE CENTRAL HEATING TURNED OFF
VOLTAGE CH DEMAND INTO BOARD (NO DEMAND)
GAIN ACCESS TO LOWER PCB PANEL
ENSURE CENTRAL HEATING TURNED OFF
RESISTANCE SENSOR SAFETY AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS TO EARTH
DISCONNECT CONNECTOR X4 FROM THE PCB
RESISTANCE HARNESS FAN
DISCONNECT FAN CONNECTOR FROM FAN
RESISTANCE HARNESS CODE PLUG
DISCONNECT THE CONNECTOR FROM THE CODE PLUG
VOLTAGE FAN SELF CHECK
{GAINPCBACS}
RESISTANCE HARNESS FAN
DISCONNECT FAN CONNECTOR FROM FAN
RESISTANCE HARNESS PUMP
DISCONNECT THE PLUG FROM THE PUMP
OBSERVATION DIVERTER MOTOR MOVEMENT (REMOVED)
REMOVE DIVERTER MOTOR FROM ITS HOUSING AND PLACE IN A SAFE LOCATION TO OBSERVE ITS MOVEMENT
OBSERVATION PUMP RUNS
ENSURE APPLIANCE IS SET TO ECO MODE
DHW TEMPERATURE CONTROL TO MAX
OBSERVATION FAN RUNS
ENSURE APPLIANCE IS SET TO ECO MODE
DHW TEMPERATURE CONTROL TO MAX
VOLTAGE FLOW TURBINE INTO BOILER
{GAINPCBACS}
INSPECTION FLOW COMPONENTS
HOT WATER CIRCUIT ISOLATED AND DRAINED
RESISTANCE HARNESS FLOW TURBINE
DISCONNECT THE INLINE PLUG FROM THE FLOW SENSOR
RESISTANCE SENSOR FLOW AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE SENSOR DHW
DISCONNECT WIRES FROM DHW SENSOR
RESISTANCE SENSOR SAFETY
DISCONNECT WIRES FROM SAFETY SENSOR
RESISTANCE SENSOR FLUE AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X7 FROM THE PCB
TEMPERATURE DHW INLET
ATTACH TEMPERATURE CLAMP TO DHW INLET PIPE
PRESSURE FAN MAX RATE
ATTACH FGA TO FAN PR
RESISTANCE SENSOR DHW
DISCONNECT WIRES FROM DHW SENSOR
INSPECTION BURNER ASSEMBLY
REMOVE THE FAN HOOD ASSEMBLY
RESISTANCE SENSOR RETURN AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
INSPECTION GAS SUPPLY TUBE
UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE
TEMPERATURE DIFFERENTIAL SAFETY AND FLOW DHW
DHW TEMPERATURE CONTROL TO MAX
VOLTAGE PREHEAT DEMAND INTO BOILER
GAIN ACCESS TO LOWER PCB PANEL
EXTERNAL CONTROLS (IF FITTED) CALLING FOR PREHEAT
DISCONNECT INTERNAL CONTROLS PREHEAT
DISCONNECT THE INTEG
VOLTAGE DIVERTER VALVE AT PCB
{GAINPCBACS}
DISCONNECT PLUG FROM DIVERTER VALVE AND MAKE SAFE
INSPECTION AIR INLET INTEGRITY
DHW TEMPERATURE CONT
INSPECTION AIR INTAKE FAN
REMOVE THE FAN AIR INTAKE FROM THE FAN
INSPECTION GAS SUPPLY TUBE
UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE
INSPECTION BURNER ASSEMBLY
REMOVE THE FAN HOOD ASSEMBLY
INSPECTION AIR INLET INTEGRITY
DHW TEMPERATURE CONT
INSPECTION AIR INTAKE FAN
REMOVE THE FAN AIR INTAKE FROM THE FAN
INSPECTION GAS SUPPLY TUBE
UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE
RESISTANCE HARNESS DIVERTER VALVE
DISCONNECT THE PLUG FROM THE DIVERTER MOTOR
DISCONNECT COMFORT CONTROLS
{GAINPCBACS}
DISCONNECT PLUG MARKED "EMS" ON LEFT HAND SIDE OF BOILER WIRING AND MAKE SAFE
INSPECTION MIXING UNIT ASSEMBLY
DISCONNECT THE FAN C
INSPECTION BURNER ASSEMBLY
REMOVE THE FAN HOOD ASSEMBLY
INSPECTION MIXING UNIT ASSEMBLY
DISCONNECT THE FAN C
INSPECTION BURNER ASSEMBLY
REMOVE THE FAN HOOD ASSEMBLY
INSPECTION MIXING UNIT ASSEMBLY
DISCONNECT THE FAN C
INSPECTION BURNER ASSEMBLY
REMOVE THE FAN HOOD ASSEMBLY
INSPECTION MIXING UNIT ASSEMBLY
DISCONNECT THE FAN C
INSPECTION BURNER ASSEMBLY
REMOVE THE FAN HOOD ASSEMBLY
INSPECTION MIXING UNIT ASSEMBLY
DISCONNECT THE FAN C
INSPECTION BURNER ASSEMBLY
REMOVE THE FAN HOOD ASSEMBLY
INSPECTION MIXING UNIT ASSEMBLY
DISCONNECT THE FAN C
INSPECTION MIXING UNIT ASSEMBLY
DISCONNECT THE FAN C
INSPECTION MIXING UNIT ASSEMBLY
DISCONNECT THE FAN C
INSPECTION MIXING UNIT ASSEMBLY
DISCONNECT THE FAN C
RESISTANCE HARNESS DIVERTER VALVE
DISCONNECT THE PLUG FROM THE DIVERTER MOTOR
INSPECTION CH TEMP SETTING
CH TEMPERATURE CONTROL KNOB SET TO MAX
RESISTANCE SENSOR DHW
DISCONNECT WIRES FROM DHW SENSOR
PRESSURE GAS INLET
ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT
RESISTANCE SENSOR DHW
DISCONNECT WIRES FROM DHW SENSOR
RESISTANCE SENSOR SAFETY
DISCONNECT WIRES FROM SAFETY SENSOR
RESISTANCE SENSOR FLUE AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X7 FROM THE PCB
INFORMATION BLANK DISPLAY
THE DISPLAY FOR THIS
RESISTANCE FUSE (PCB)
REMOVE THE FUSE FROM ITS HOUSING
OBSERVATION DISCONNECT X5 AT PCB
{GAINPCBACS}
DISCONNECT CONNECTOR X5 AT THE PCB AND MAKE SAFE
(THIRD CONNECTOR FROM THE LEFT)
OBSERVATION DISCONNECT FLOW TURBINE
DISCONNECT FLOW TURB
INSPECTION FLOW COMPONENTS
HOT WATER CIRCUIT ISOLATED AND DRAINED
VOLTAGE FLOW TURBINE INTO BOILER
{GAINPCBACS}
RESISTANCE HARNESS FLOW TURBINE
DISCONNECT THE INLINE PLUG FROM THE FLOW SENSOR
OBSERVATION FAULT CODE AT SHUTDOWN
CH TEMPERATURE CONTROL KNOB TO MAX
RESISTANCE SENSOR FLOW
REMOVE THE AIR INTAKE FROM THE FAN
DISCONNECT WIRES FROM FLOW SENSOR
RESISTANCE SENSOR SAFETY
DISCONNECT WIRES FROM SAFETY SENSOR
RESISTANCE SENSOR RETURN AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
PRESSURE GAS INLET
ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT
INSPECTION GAS SUPPLY TUBE
UNSCREW THE GAS SUPPLY TUBE FROM THE GAS VALVE
VOLTAGE DIVERTER VALVE AT PCB
{GAINPCBACS}
DISCONNECT PLUG FROM DIVERTER VALVE AND MAKE SAFE
RESISTANCE HARNESS DIVERTER VALVE
DISCONNECT THE PLUG FROM THE DIVERTER MOTOR
RESISTANCE SENSOR DHW AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
OBSERVATION BOILER RESET
ENSURE APPLIANCE IS COOL
TEMPERATURE EXHAUST GAS (FAULT CODE)
CH TEMPERATURE CONTR
RESISTANCE SENSOR SAFETY
DISCONNECT WIRES FROM SAFETY SENSOR
RESISTANCE SENSOR SAFETY AND HARNESS
{GAINPCBACS}
DISCONNECT CONNECTOR X6 FROM THE PCB
RESISTANCE HARNESS CODE PLUG
DISCONNECT THE CONNECTOR FROM THE CODE PLUG
VOLTAGE PUMP AT PCB
{GAINPCBACS}
RESISTANCE HARNESS PUMP
DISCONNECT THE PLUG FROM THE PUMP
System Information
- Total Tests: 1167
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control