WORCESTER GREENSTAR 24I JUNIOR LPG

WARNING - IMPORTA

Next: &1, *

WORCESTER GREENSTAR 24I JUNIOR LPG


CASE REMOVAL<

Next: &470, !f2

DHW FLOW RATE

Next: &1325, f6

DHW OPERATION

Next: &148, ?96, ?98, ?100, ?102, ?671

CH OPERATION

Next: &173, ?149, ?151, ?715, ?847

CENTRAL HEATING MODULATION

ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT

Next: &177, f174

PRE-HEAT

ENSURE THE ECO BUTTON IS OFF
RUN THE HOT WATER UNTIL THE SECONDARY HEAT EXCHANGER IS COOL

Next: &183, f178

PUMP OVERRUN

SET TEMPERATURE CONTROL TO MID POSITION

Next: &185, !f184

SYPHON OPERATION

ON/OFF SWITCH ON

Next: &nff, !f186

CH DEMAND

Next: &1517, f263

DHW BURNER IGNITION & ESTABLISH

ECO MODE ON (NO PREHEAT)

Next: &262, ?318, ?322, ?986, ?1327

ENHANCED FAULT CODES

SELECT APPROPRIATE F

Next: &1052, !f467

TYPE OF DIAGNOSTIC PROCEDURE

PLEASE SELECT FROM O

Next: &3, !f471

MAXIMUM OUTPUT MODE

INSTRUCTIONS TO S

Next: &nff, !f701

FURTHER INVESTIGATION OVERHEAT

NOT USED

Next: &nff, f911

NORMAL OPERATION

NOT USED

Next: &nff, !f1045

POWER UP

Next: &5, f1053

FURTHER INVESTIGATION FUSE BLOWN

NOT USED

Next: &nff, f1075

INSPECTION INTERNAL BOILER

Next: &317, !f1326

PUMP RUNNING

REMOVE PUMP VENT SCR

Next: &1523, f1518

FAN PRESSURE TEST

ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT

Next: &1529, f1524

INLET PRESSURE

ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT ON GAS VALVE

Next: &1531, !f1530

COMBUSTION ANALYSIS MAX AND MIN

UNCLIP DIVERTER VALVE HEAD FROM THE BODY AND LEAVE IN A SAFE POSITION

Next: &95, ?1532, ?1534

COMBUSTION ANALYSIS MAX AND MIN CH

UNCLIP DIVERTER VALVE HEAD FROM THE BODY AND LEAVE IN A SAFE POSITION

Next: &nff, ?1566, ?1568

CH OPERATION PERFORMANCE TEST FAIL

OUTSIDE OF MODEL

Next: &nff, f1571

BURNER BAFFLES OUT

FLUE

Next: End

BURNER BAFFLES OUT

BURNER

Next: End

DOES NOT ESTABLISH

BURNER

Next: End

DHW TO COOL

BURNER

Next: End

OVERHEAT OCCURED

NORMAL OPERATION

Next: End

FLUE OVERHEAT

BURNER

Next: End

FLUE OVERHEAT

PRIMARY HEAT EXCHANGER

Next: End

BLOWN STAND BY MODE AT POWER UP

FUSE (FUSED SPUR)

Next: End

LED AT POWER UP

PCB

Next: End

FURTHER INVESTIGATION FUSE F1

FAN ASSEMBLY

Next: End

FURTHER INVESTIGATION

TRANSFORMER

Next: End

FURTHER INVESTIGATION

GAS VALVE

Next: End

FAN DOES NOT RUN

Z REDIRECTION

Next: End

BLOWN STANDBY MODE

FUSE - MAINS

Next: End

BLOWN STANDBY MODE

FUSE

Next: End

FURTHER IN VESTIGATION F2

Z DIRECTION

Next: End

BURNER IGNITION

TRANSFORMER

Next: End

IGNITION

WATER LEAK

Next: End

FAN RUNS

AIR PRESSURE SWITCH

Next: End

FAN RUNS

SENSOR OVER HEAT

Next: End

BURNER IGNITION

SENSOR - FLUE (LIMITER - TEMPERATURE)

Next: End

GAS VALVE

PCB

Next: End

FAN REDUCES AND STOPS

PCB

Next: End

FAN REDUCES AND STOPS

BURNER

Next: End

BURNER IGNITES

SYPHON

Next: End

BURNER IGNITES

INLET PRESSURE

Next: End

GAS VALVE BURNER IGNITES

HARNESS - MAINS

Next: End

BURNER DOES NOT IGNITE

BURNER

Next: End

SPARKING

PCB

Next: End

BURNER IGNITES

HARNESS ELECTRODE SPARK

Next: End

BURNER IGNITES

ELECTRODE

Next: End

DOES NOT IGNITE

PRIMARY HEAT EXCHANGER

Next: End

DHW COOL

PUMP

Next: End

DHW COOL RADS COOL

HARNESS - PUMP

Next: End

ABOVE 135 VAC

HARNESS FAN

Next: End

STSLOW THEN TO TO HIGH SPEED

HARNESS FAN

Next: End

BELOW 124 VAC

HARNESS FAN

Next: End

PREHEAT

SENSOR - TEMPERATURE - DHW

Next: End

OVERHEAT

DIRECTION CHOICE OR CONTINUE

Next: End

OVERHEAT

SENSOR - PRIMARY (CONTROL)

Next: End

OVERHEAT

SENSOR - FLUE (LIMITER - TEMPERATURE)

Next: End

OVERHEAT

SENSOR OVER HEAT

Next: End

OVERHEAT 2

SENSOR - FLUE (LIMITER - TEMPERATURE)

Next: End

DHW SENSOR

SENSOR - TEMPERATURE - DHW

Next: End

DHW COOL RADS COOLPUMP RUNNING PRE TEST

HARNESS - PUMP

Next: End

PRIMARY PRE TEST FAN PRESSURE

PRIMARY HEAT EXCHANGER

Next: End

PRIMARY TEST

INLET PRESSURE

Next: End

DHW NOISEY

BYPASS INTERNAL VALVE

Next: End

HEAT EXCHANGER NOISY

HARNESS - PUMP

Next: End

INTERNAL CLOCK2DHW NOISY

PCB

Next: End

INTERNAL CLOCKDHW NOISY

PCB

Next: End

CH OP PT FAIL FAN PRESSURE FAIL

PRIMARY HEAT EXCHANGER

Next: End

TURBINE

HARNESS - MAINS

Next: End

FAN DOES NOT RUN

SENSOR - PRIMARY (CONTROL)

Next: End

FAN DOES NOT RUN

SENSOR - TEMPERATURE - DHW

Next: End

FAN RUNS

HARNESS FAN

Next: End

FAN VOLTAGE PCB

PCB

Next: End

FAN DOES NOT RUN

HARNESS FAN

Next: End

FAN DOES NOT RUN

Z REDIRECTION

Next: End

FAN DOES NOT RUN

CODE PLUG

Next: End

BURNER IGNITION

SENSOR - PRIMARY (CONTROL)

Next: End

DHW COOL RADS HOT

HARNESS - STEPPER MOTOR

Next: End

STEPPERBOILER REACHES TEMP RADS DO NOT HEAT

HARNESS - STEPPER MOTOR

Next: End

CH MODULATION

SENSOR - PRIMARY (CONTROL)

Next: End

PUMP OVERRUN

PCB

Next: End

SYPHON

SYPHON

Next: End

ELECTRICAL SAFETY

ELECTRICAL SAFETY CHECKS

Next: End

INTERNAL CLOCK

PCB

Next: End

INTERNAL CLOCK2

PCB

Next: End

DOES NOT ESTABLISH

INLET PRESSURE

Next: End

FLAME SENSE BURNER IGNITES

HARNESS - MAINS

Next: End

BURNER IGNITES

ELECTRODE ASSEMBLY

Next: End

SYSTEM CHECKS

SYSTEM CHECKS

Next: End

FAULT CODES

ENHANCED FAULT CODES

Next: End

FOR TYPE DIAG PROCEDURE

DIRECTION CHOICE OR CONTINUE

Next: End

BURNER DOES NOT ESTABLISH

SYPHON

Next: End

DHW COOL RADIATORS COOL

SENSOR - TEMPERATURE - DHW

Next: End

DHW TOO COOL

BYPASS INTERNAL VALVE

Next: End

DHW TOO COOL

SENSOR - TEMPERATURE - DHW

Next: End

HOT THEN COLD

SECONDARY HEAT EXCHANGER

Next: End

DHW HOT THEN COLD

SENSOR - PRIMARY (CONTROL)

Next: End

DHW HOT THEN COLD

PUMP

Next: End

MAXIMUM OUTPUT INSTRUCTIONS

MAXIMUM OUTPUT INSTRUCTIONS

Next: End

EXPANSION VESSEL

EXPANSION VESSEL

Next: End

DHW COOL

SYSTEM PRESSURE

Next: End

DHW NOISY

SYSTEM PRESSURE

Next: End

DHW HOT THEN COLD

SYSTEM PRESSURE

Next: End

CH NOISY

PUMP

Next: End

CH NOISY

SENSOR - PRIMARY (CONTROL)

Next: End

CH NOISY

SYSTEM PRESSURE

Next: End

RADS DO NOT HEAT

SYSTEM PRESSURE

Next: End

RADS DO NOT HEAT

PUMP

Next: End

RADS DO NOT HEAT

ISOLATION VALVES

Next: End

OVERHEAT FURTHER INVESTIGATION

Z REDIRECTION

Next: End

FAN RUNS OVERHEAT 1

AIR PRESSURE SWITCH

Next: End

FAN RUNS OVERHEAT 1

SENSOR OVER HEAT

Next: End

OVERHEAT

SYSTEM PRESSURE

Next: End

OVERHEAT

PUMP

Next: End

RADS COLD

BYPASS INTERNAL VALVE

Next: End

BURNER BAFFLES OUT

SYPHON

Next: End

BURNER BAFFLES OUT

INLET PRESSURE

Next: End

BURNER BAFFLES OUT

GAS VALVE

Next: End

BURNER BAFFLES OUT

PRIMARY HEAT EXCHANGER

Next: End

BURNER DOES NOT EST

PRIMARY HEAT EXCHANGER

Next: End

DHW COOL RAD COOL

PRIMARY HEAT EXCHANGER

Next: End

APS/FLUE/OH OVERHEAT 1

HARNESS - MAINS

Next: End

BURNER IGNITION OVERHEAT 1

SENSOR - FLUE (LIMITER - TEMPERATURE)

Next: End

FURTHER INVESTIGATION FUSED SPUR

Z DIRECTION

Next: End

DHW COOL RADIATORS HOT

DIVERTER VALVE ASSEMBLY

Next: End

FURTHER INVESTIGATION FUSE F1

HARNESS - PUMP

Next: End

FURTHER INVESTIGATION FUSE F1

HARNESS FAN

Next: End

FLOW RATE

INLET FILTER

Next: End

FURTHER INVESTIGATION

HARNESS - MAINS

Next: End

FURTHER INVESTIGATION

PCB

Next: End

FURTHER INVESTIGATION F1

Z DIRECTION

Next: End

FURTHER INVESTIGATION F3

Z DIRECTION

Next: End

TRANSFORMER

PCB

Next: End

FLOW RATE

FLOW REGULATOR

Next: End

BURNER DOES NOT IGNITE

Z REDIRECTION

Next: End

APS/FLUE/OH

HARNESS - MAINS

Next: End

FAN REDUCES STOPS

AIR PRESSURE SWITCH

Next: End

FAN REDUCES AND STOPS

PRIMARY HEAT EXCHANGER

Next: End

VOLTAGE GAS VALVE

PCB

Next: End

NO VOLTAGE

PCB

Next: End

BURNER IGNITES

GAS VALVE

Next: End

BURNER DOES NOT IGNITE2

PRIMARY HEAT EXCHANGER

Next: End

BURNER DOES NOT IGNITE

GAS VALVE

Next: End

DHW TOO COOL

PCB

Next: End

CH NOISY

PCB

Next: End

CH NOISY

PRIMARY HEAT EXCHANGER

Next: End

CH NOISY

Next: End

DHW COOL RADIATORS COOL

PUMP

Next: End

SLOW THEN TO HIGH SPEED

FAN ASSEMBLY

Next: End

BELOW 124 VAC

FAN ASSEMBLY

Next: End

FLOW RATE

NOZZLES

Next: End

OVERHEAT

PCB

Next: End

BOILER GOES TO OVERHEAT

SENSOR OVER HEAT

Next: End

FAN RUNSOVERHEAT

AIR PRESSURE SWITCH

Next: End

DHW TOO HOT

PCB

Next: End

DHW TOO HOT

HARNESS - MAINS

Next: End

FAN PRESSURE PRIMARY TEST

FLUE

Next: End

CO2 SETTINGS INCORRECT

GAS VALVE SETTING RETEST

Next: End

DROPS OUT ON MINIMUM

GAS VALVE SETTING

Next: End

HEAT EXCHANGER NOISY

PRIMARY HEAT EXCHANGER

Next: End

HEAT EXCHANGER NOISY

PUMP

Next: End

CH OPERATION DHWDHW NOISY

HEATING CONTROLS

Next: End

CH DEMAND 1DHW NOISY

INTERNAL CLOCK

Next: End

CH OPERATION (DHW)DHW NOISY

HEATING CONTROLS

Next: End

PT FROM CH SEQUENCECO2 SETTINGS INCORRECT

GAS VALVE SETTING RETEST

Next: End

PT FROM CH SEQUENCEDROPS OUT ON MINIMUM

GAS VALVE SETTING

Next: End

CH OP PT FAIL

GAS VALVE SETTING RETEST

Next: End

ELECTRICAL

FLOW SENSOR TURBINE

Next: End

FAN SIGNAL

PCB

Next: End

FLOW SENSOR FAN RUNS 2

HARNESS - MAINS

Next: End

DHW SENSOR FAN DOES NOT RUN

HARNESS - MAINS

Next: End

FAN DOES NOT RUN

PCB

Next: End

DOES NOT RUN

FAN ASSEMBLY

Next: End

FAN RUNS

FAN ASSEMBLY

Next: End

FAN DOES NOT RUN

LOCKOUT

Next: End

FAN RUNS RESISTANCE

PCB

Next: End

FLOW SENSOR FAN RUNS

HARNESS - MAINS

Next: End

DHW COOL RADS HOT MECHANICAL FAULT

DIVERTER VALVE MOTOR

Next: End

DHW COOL RADS HOT ELECTRICAL FAULT

DIVERTER VALVE MOTOR

Next: End

CH MODULATION

PCB

Next: End

PRE-HEAT

PCB

Next: End

CH OPERATION (DHW)

HEATING CONTROLS

Next: End

CH DEMAND 1

INTERNAL CLOCK

Next: End

CH OPERATION DHW

HEATING CONTROLS

Next: End

FLAME SENSE

PCB

Next: End

MODULATION

GAS VALVE

Next: End

DHW TOO COOL 2

PCB

Next: End

DHW COOL RADIATORS COOL

SECONDARY HEAT EXCHANGER

Next: End

DHW HOT THEN COLD

PCB

Next: End

FLOW RATE

SECONDARY HEAT EXCHANGER

Next: End

DHW TOO COOL 3

PCB

Next: End

HEAT EXCHANGER NOISY

SECONDARY HEAT EXCHANGER

Next: End

EXCESSIVE SYSTEM PRESSURE

EXPANSION VESSEL PIPE

Next: End

RADS DO NOT HEAT

Next: End

FURTHER INVESTIGATION OVERHEAT

Z REDIRECTION

Next: End

FLOW RATE

FLOW SENSOR TURBINE

Next: End

GAS VALVE OVERHEAT 1

PCB

Next: End

BURNER DOES NOT IGNITE OVERHEAT 1

Z REDIRECTION

Next: End

INLET FILTER BLOCKED AND/OR IN POOR CONDITION

CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS

Next: !p11

DHW COOL, RADIATORS HOT

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p101

DHW TOO HOT

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p1512

FLOW REGULATOR BLOCKED AND/OR IN POOR CONDITION

CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS

Next: !p13

BURNER DOES NOT IGNITE

CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH

Next: p1328

AFTER 12/14 SECONDS FAN SPEED INCREASES

CHARACTERISTIC TEST FROM MODE OF FAN OPERATION

Next: p1332

AFTER 4/5 SECONDS FAN REDUCES AND STOPS

CHARACTERISTIC TEST FROM MODE OF FAN OPERATION

Next: p1334

NOZZLES BLOCKED AND/OR IN POOR CONDITION

CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS

Next: !p15

TEMPERATURE DIFFERENTIAL CORRECT LOCAL BOILING

CHARACTERISTIC TEST FROM DIFFERENTIAL FLOW RETURN

Next: !p1454

DIFFERENTIAL OK SYSTEM NOISE

CHARACTERISTIC TEST FROM DIFFERENTIAL FLOW RETURN

Next: !p1456

VOLTAGE BETWEEN 125 VAC AND 135 VAC

CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB)

Next: p1473

VOLTAGE BELOW 124 VAC

CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB)

Next: p1475

BOILER NOISY

CHARACTERISTIC TEST FROM CH OPERATION

Next: p779

BOILER REACHES TEMPERATURE, RADIATORS DO NOT HEAT

CHARACTERISTIC TEST FROM CH OPERATION

Next: p796

CO2 SETTINGS INCORRECT

CHARACTERISTIC TEST FROM COMBUSTION ANALYSIS MAX AND MIN

Next: !p1533

BURNER DROPS OUT IN MINIMUM MODE

CHARACTERISTIC TEST FROM COMBUSTION ANALYSIS MAX AND MIN

Next: !p1535

OPERATION IS NOISY

CHARACTERISTIC TEST FROM CH OPERATION (DHW OPERATION)

Next: p1541

BOILER DOES NOT REACT TO CH DEMAND

CHARACTERISTIC TEST FROM CH OPERATION (DHW OPERATION)

Next: p1552

CO2 SETTINGS INCORRECT

CHARACTERISTIC TEST FROM COMBUSTION ANALYSIS MAX AND MIN

Next: !p1567

BURNER DROPS OUT IN MINIMUM MODE

CHARACTERISTIC TEST FROM COMBUSTION ANALYSIS MAX AND MIN

Next: !p1569

240 VOLTS ACROSS PURPLE BROWN OTHERS NOT AS ABOVE

CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)

Next: p1596

240 VOLTS ACROSS PURPLE/BROWN ABSENT

CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)

Next: !p1598

VOLTAGES DO NOT BEHAVE AS DESCRIBED ABOVE ON ONE OR MORE TESTS

CHARACTERISTIC TEST FROM VOLTAGE DIVERTER VALVE PCB DROP RETURN TO 15V

Next: p1629

15 VDC PRESENT BUT VOLTAGE DOESNT CHANGE

CHARACTERISTIC TEST FROM VOLTAGE DIVERTER VALVE PCB DROP RETURN TO 15V

Next: !p1631

VOLTAGES DO NOT BEHAVE AS DESCRIBED ABOVE ON ONE OR MORE TESTS

CHARACTERISTIC TEST FROM VOLTAGE DIVERTER VALVE PCB DROP RETURN TO 15V

Next: p1639

15 VDC PRESENT BUT VOLTAGE DOESNT CHANGE

CHARACTERISTIC TEST FROM VOLTAGE DIVERTER VALVE PCB DROP RETURN TO 15V

Next: !p1641

BURNER IGNITES BUT DOES NOT ESTABLISH

CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH

Next: p319

FAN DOES NOT RUN

CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH

Next: p1270

DIFFERENTIAL TO HIGH

CHARACTERISTIC TEST FROM DIFFERENTIAL PLATE HEAT EX

Next: !p666

DIFFERENTIAL TO LOW

CHARACTERISTIC TEST FROM DIFFERENTIAL PLATE HEAT EX

Next: p668

DHW RUNS HOT THEN COLD

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p761

EXCESSIVE SYSTEM PRESSURE RISE

CHARACTERISTIC TEST FROM CH OPERATION

Next: p716

FLOW SENSOR BLOCKED AND/OR IN POOR CONDITION

CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS

Next: !p9

OPERATION SATISFACTORY BUT BOILER GOES TO OVERHEAT

CHARACTERISTIC TEST FROM CH OPERATION

Next: p848

HEAT EXCHANGER NOISY

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p720

DHW TOO COOL, RADIATORS COLD

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p733

BURNER IGNITES BUT BAFFLES OUT

CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH

Next: p987

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: !p1023, !f1014

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: !p1026, !f1027

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: !p1042, !f1043

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: p1048, !f1049

VOLTAGE MAINS POWER INPUT TO APPLIANCE

{GAINPCBACS}

Next: p1054, f1055

RESISTANCE FUSE (FUSED SPUR)

REMOVE FUSE FROM FUSED SPUR

Next: !p1056, f1057

FUSE FURTHER INVESTIGATION

Next: !p1058, !f1059

HARNESS GAS VALVE

REMOVE THE CONNECTOR

Next: !p1107, !f1108

RESISTANCE PUMP

DISCONNECT THE PUMP CONNECTOR

Next: !p1082, !f1083

RESISTANCE FAN

DISCONNECT FAN CONNECTOR AT FAN

Next: !p1086, !f1087

FUSE F1

REMOVE CONTROL BOX COVER IF NECESSARY

Next: p1273, f1274

FUSE FURTHER INVESTIGATION F1

Next: !p1275, !f1276

FUSE FURTHER INVESTIGATION F3

Next: !p1279, !f1280

FUSE FURTHER INVESTIGATION F2

Next: !p1283, !f1284

AIR PRESSURE SWITCH

Next: p1337, f1338

RESISTANCE AIR PRESSURE SWITCH

DISCONNECT ONE OF THE ORANGE LEADS FROM THE AIR PRESSURE SWITCH.

Next: !p1339, !f1340

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: !p1351, !f1352

VOLTAGE GAS VALVE

REMOVE THE GAS VALVE CONNECTORS FROM THE GAS VALVE

Next: p1363, f1364

RESISTANCE GAS VALVE SOLENOID MAIN AND HARNESS

DISCONNECT ST9 CONNE

Next: !p1365, f1366

RESISTANCE GAS VALVE HARNESS

REMOVE THE CONNECTOR

Next: !p1367, !f1368

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: !p1371, !f1372

PUMP VOLTAGE

{GAINPCBACS}

Next: p1459, !f1460

RESISTANCE FLUE OH STAT

DISCONNECT ONE OF THE ORANGE LEADS FROM THE OVERHEAT STAT

Next: !p1506, !f1507

DHW SENSOR

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: !p1515, !f1516

PUMP VOLTAGE

{GAINPCBACS}

Next: p1519, !f1520

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: p1525, !f1526

PUMP VOLTAGE

{GAINPCBACS}

Next: p1548, !f1549

EXTERNAL CONTROLS VOLTAGE (RETURN)

{GAINPCBACS}
EXTERNAL CONTROLS CALLING FOR HEAT

Next: p1555, f1556

EXTERNAL CONTROL VOLTAGE (SEND)

Next: !p1557, !f1558

EXTERNAL CONTROL VOLTAGE (SEND)

Next: !p1563, !f1564

FAN PRESSURE TEST

ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT

Next: !p1572, f1573

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: p1574, !f1575

VOLTS TO TURBINE

REMOVE CONTROL BOX COVER IF NECESSARY

Next: !p1581, f1582

HARNESS CONTINUITY (TURBINE)

BREAK THE INLINE CONNECTOR IN THE TURBINE LEAD
DISCONNECT THE 20 WAY CONNECTOR FROM THE PCB

Next: !p1583, !f1584

RESISTANCE SENSOR TEMP FLOW

DISCONNECT PLUG (RE

Next: !p1587, !f1588

RESISTANCE DHW SENSOR

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: !p1591, !f1592

RESET OPERATION

ECO MODE ON
ENSURE NO DEMAND

Next: p1616, f1619

CODE PLUG

LOWER THE FACIA PANEL

Next: p1620, !f1621

RESISTANCE SENSOR TEMP FLOW

DISCONNECT PLUG (RE

Next: !p1624, !f1625

VOLTAGE DIVERTER VALVE PCB RETURN TO 15V

{GAINPCBACS}
NO DEMAND
ECO MODE ON (ILLUMINATED)

Next: !p1627, ?1628, ?1630

VOLTAGE DIVERTER VALVE PCB RETURN TO 15V

{GAINPCBACS}
NO DEMAND
ECO MODE ON (ILLUMINATED)

Next: !p1637, ?1638, ?1640

PRIMARY SENSOR (HIGH FLAME)

REMOVE RED WIRES FRO

Next: !p175, !f176

RESISTANCE SENSOR DHW

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: !p179, !f1482

EXTERNAL CONTROLS VOLTAGE (RETURN)

{GAINPCBACS}
EXTERNAL CONTROLS CALLING FOR HEAT

Next: p298, f299

EXTERNAL CONTROL VOLTAGE (SEND)

Next: !p292, !f290

EXTERNAL CONTROL VOLTAGE (SEND)

Next: !p302, !f303

ELECTRODE SENSE HARNESS

DISCONNECT FLAME SENSE LEAD FROM ELECTRODE
DISCONNECT CONNECTER ST9 FROM THE PCB

Next: !p396, !f397

CHECK FLOW COMPONENTS

DRAIN THE DOMESTIC H

Next: !p7, ?8, ?10, ?12, ?14

DHW SENSOR

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: !p1450, !f656

FLUEWAYS

ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT

Next: !p661, f1041

BOILER RESET

ENSURE BOILER HAS COOLED

Next: p923, f912

RESISTANCE SAFETY CIRCUIT

{GAINPCBACS}
DISCONNECT CONNECTOR FROM ST9 ON THE PCB

Next: !p913, f914

AIR PRESSURE SWITCH

Next: p915, f916

RESISTANCE AIR PRESSURE SWITCH

DISCONNECT ONE OF THE ORANGE LEADS FROM THE AIR PRESSURE SWITCH.

Next: !p917, !f918

DIVERTER VALVE ACTUATOR OPERATION

REMOVE THE DIVERTER

Next: !p106, f1626

INSPECTION HEAT EXCHANGER

REMOVE FAN/MANIFOLD

Next: !p1050, !f1051

FAN RUNS DHW DEMAND

Next: p1060, !f1139

FURTHER INVESTIGATION LED PROBLEM

Next: !p1072, !f1073

RESISTANCE PUMP AND HARNESS

REMOVE THE PUMP CONNECTOR ST4 FROM THE PCB

Next: p1080, f1081

RESISTANCE FAN AND HARNESS

DISCONNECT FAN CONNECTOR ST5 FROM THE PCB

Next: p1084, f1085

RESISTANCE TRANSFORMER

REMOVE THE BACKPLATE OF THE CONTROL BOX AND THE TRANSFORMER FROM THE PCB

Next: !p1109, !f1089

VOLTAGE AT PCB

{GAINPCBACS}

Next: p1271, f1272

VOLTAGE PUMP LINE

ENSURE NO DEMAND
ECO MODE ON

Next: p1578, f1605

FUSE F3

REMOVE CONTROL BOX C

Next: p1277, f1278

FUSE F2

REMOVE CONTROL BOX C

Next: p1281, f1282

TRANSFORMER RESISTANCE

REMOVE THE BACKPLATE OF THE CONTROL BOX AND THE TRANSFORMER FROM THE PCB

Next: !p1285, !f1286

MODE OF FAN OPERATION

Next: p1329, ?1331, ?1333

CONDENSATE PIPE

Next: p1357, !f1358

FAN VOLTAGE CONTROL (PCB)

{GAINPCBACS}
MOVE CONNECTOR ST5 TO EXPOSE TERMINALS ON PCB

Next: p1353, ?1472, ?1474

RESISTANCE SAFETY CIRCUIT

{GAINPCBACS}
DISCONNECT CONNECTOR FROM ST9 ON THE PCB

Next: p1335, f1336

AIR PRESSURE SWITCH FITTED

Next: p1345, !f1346

RESISTANCE OH STAT

DISCONNECT ONE OF THE ORANGE LEADS FROM THE OVERHEAT STAT

Next: p1341, !f1342

RESISTANCE FLUE OH STAT

DISCONNECT ONE OF THE ORANGE LEADS FROM THE OVERHEAT STAT

Next: !p1343, !f1344

AIR PRESSURE SWITCH (DEMAND)

Next: p1347, !f1348

FAN PRESSURE TEST

ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT

Next: !p1349, f1350

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR ST5 FORM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p1476, !f1477

INLET PRESSURE

ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT ON GAS VALVE

Next: p1359, !f1360

PRESSURE GAS INLET DROP

ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT ON GAS VALVE

Next: p1361, f1362

SPARKING PRESENT TEST

REMOVE SPARK LEADS F

Next: p1373, !f1374

FAN PRESSURE TEST

ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT

Next: !p1369, f1370

ELECTRODE SPARK HARNESS

REMOVE THE IGNITION HARNESS CONNECTION FROM THE ELECTRODES TOP OF THE BURNER AND FROM THE PCB

Next: p1375, !f1376

INSPECTION SPARK ELECTRODE

REMOVE THE ELECTRODE ASSEMBLY

Next: p1377, !f1378

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: p1379, !f1380

INSPECTION HEAT EXCHANGER

REMOVE FAN/MANIFOLD

Next: !p1381, !f1382

PUMP RUNNING

REMOVE PUMP VENT SCR

Next: p646, f1411

DIFFERENTIAL FLOW RETURN

TEMPERATURE CONTROL SET TO MAXIMUM
ATTACH TEMPERATURE CLAMPS TO FLOW AND RETURN PIPES

Next: !p1452, ?1453, ?1455

PUMP HARNESS CONTINUITY

REMOVE THE PUMP PLUG FROM THE PUMP AND THE PUMP HARNESS CONNECTOR FROM THE PCB

Next: !p1461, !f1462

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR ST5 FORM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p1478, !f1479

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR ST5 FORM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p1480, !f1481

RUN BOILER TO MAX TEMP-DOES OVERHEAT OCCUR

ATTACH TEMPERATURE CLAMP TO FLOW PIPE
SET BOILER TEMPERATURE CONTROL TO MAXIMUM

Next: p1491, f1503

COOL APPLIANCE

ENSURE ALL RADS ARE TURN ON
ATTACH TEMPERATURE CLAMP TO FLOW PIPE

Next: p1499, !f1500

PRIMARY SENSOR (HIGH FLAME)

REMOVE RED WIRES FRO

Next: !p1501, !f1502

RESISTANCE OH STAT

DISCONNECT ONE OF THE ORANGE LEADS FROM THE OVERHEAT STAT

Next: p1508, !f1509

RESISTANCE FLUE OH STAT

DISCONNECT ONE OF THE ORANGE LEADS FROM THE OVERHEAT STAT

Next: !p1510, !f1511

RESISTANCE DHW SENSOR AND HARNESS

DISCONNECT CONNECTOR FROM ST9 ON THE PCB

Next: !p1513, f1514

PUMP HARNESS CONTINUITY

REMOVE THE PUMP PLUG FROM THE PUMP AND THE PUMP HARNESS CONNECTOR FROM THE PCB

Next: !p1521, !f1522

INSPECTION HEAT EXCHANGER

REMOVE FAN/MANIFOLD

Next: !p1527, !f1528

PUMP LIMPET TEST

Next: p1542, f1547

BYPASS - INTERNAL (DHW NOISY)

ENSURE RADS ARE OPEN AND WATER CAN CIRCULATE AROUND
THE SYSTEM

Next: !p1544, !f1545

PUMP HARNESS CONTINUITY

REMOVE THE PUMP PLUG FROM THE PUMP AND THE PUMP HARNESS CONNECTOR FROM THE PCB

Next: !p1550, !f1551

INTERNAL OR EXTERNAL CONTROLS

Next: p1553, f1554

EXTERNAL CONTROLS VOLTAGE (RETURN)

{GAINPCBACS}
EXTERNAL CONTROLS CALLING FOR HEAT

Next: !p1561, f1562

INTERNAL CLOCK

REMOVE AND DISCONNECT THE INTERNAL CLOCK ASSEMBLY FROM THE BOILER.

Next: !p1559, !f1560

INSPECTION HEAT EXCHANGER

REMOVE FAN/MANIFOLD

Next: !p1576, !f1577

VOLTS FROM TURBINE

REMOVE CONTROL BOX COVER IF NECESSARY

Next: p1579, f1580

RESISTANCE SENSOR TEMP FLOW AND HARNESS

DISCONNECT CONNECTOR FROM ST9 ON THE PCB

Next: p1585, f1586

RESISTANCE DHW SENSOR AND HARNESS

DISCONNECT CONNECTOR FROM ST9 ON THE PCB

Next: p1589, f1590

VOLTAGE FAN (AT PCB)

MOVE CONNECTOR ST5 U

Next: p1593, ?1595, ?1597

VOLTAGE FAN (PCB DEMAND)

DISCONNECT FAN ELECTRICAL CONNECTOR FROM THE FAN
ASSEMBLY, POSITION IN A SAFE PLACE

Next: p1601, !f1602

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR ST5 FORM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p1599, !f1600

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR ST5 FORM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p1603, !f1604

FAN RUNS

Next: !p1617, !f1618

RESISTANCE SENSOR TEMP FLOW AND HARNESS

DISCONNECT CONNECTOR FROM ST9 ON THE PCB

Next: !p1622, f1623

VOLTAGE DIVERTER MOTOR SUPPLY PCB

NO DEMAND
ECO MODE ON (ILLUMINATED)
REMOVE CONNECTOR ST17 FROM PCB

Next: p1632, !f1633

DIVERTER VALVE HARNESS CONTINUITY

DISCONNECT THE ST17

Next: !p1634, !f1635

VOLTAGE DIVERTER MOTOR SUPPLY PCB

NO DEMAND
ECO MODE ON (ILLUMINATED)
REMOVE CONNECTOR ST17 FROM PCB

Next: p1642, !f1643

DIVERTER VALVE HARNESS CONTINUITY

DISCONNECT THE ST17

Next: !p1644, !f1645

EXTERNAL CONTROLS VOLTAGE (RETURN)

{GAINPCBACS}
EXTERNAL CONTROLS CALLING FOR HEAT

Next: !p288, f287

INTERNAL CLOCK

REMOVE AND DISCONNECT THE INTERNAL CLOCK ASSEMBLY FROM THE BOILER.

Next: !p300, !f301

INLET PRESSURE

ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT ON GAS VALVE

Next: p392, !f393

RECTIFICATION VOLTAGE

DISCONNECT FLAME SENSE LEAD (GREEN LEAD) FROM
SENSE ELECTRODE AND SECURE IT AS SHOWN

Next: p542, f395

ELECTRODE SENSE

REMOVE THE ELECTRODE ASSEMBLY

Next: !p1116, !f399

CONDENSATE PIPE

Next: p553, !f550

FAN PRESSURE TEST

ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT

Next: p394, f1025

PUMP LIMPET TEST

Next: p647, !f1419

FAN SPEED

Next: p653, f654

COMBUSTION CHECK

PREPARE THE BOILER F

Next: p659, f660

DIFFERENTIAL PLATE HEAT EX

ATTACH TEMPERATURE PROBES TO FLOW AND RETURN PIPES OF THE PRIMARY HEAT EXCHANGER AS ILLUSTRATED

Next: !p663, ?665, ?667

CH BYPASS CHECK-DHW

ATTACH FGA TEMPERATURE PROBES TO THE BYPASS TUBE AND FLOW PIPE FROM HEAT EXCHANGER

Next: !p702, !f670

DHW SENSOR

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: p678, !f674

DIFFERENTIAL PLATE HEAT EX

ATTACH TEMPERATURE PROBES TO FLOW AND RETURN PIPES OF THE PRIMARY HEAT EXCHANGER AS ILLUSTRATED

Next: !p675, !f677

PRIMARY SENSOR (HIGH FLAME)

REMOVE RED WIRES FRO

Next: p673, !f682

PUMP LIMPET TEST

Next: p672, !f697

CH OPERATION

Next: !p704, ?1537, ?1539

INSPECTION VESSEL PRESSURE

CLOSE FLOW AND RETURN ISOLATION VALVES
DISCHARGE PRIMARY SYSTEM WATER

Next: !p718, !f719

INSPECTION PRESSURE SYSTEM

Next: p703, !f760

INSPECTION PRESSURE SYSTEM

Next: p1383, !f759

INSPECTION PRESSURE SYSTEM

Next: p683, !f771

PUMP LIMPET TEST

Next: p775, !f776

PRIMARY SENSOR (HIGH FLAME)

REMOVE RED WIRES FRO

Next: p1451, !f778

INSPECTION PRESSURE SYSTEM

Next: p774, !f785

INSPECTION PRESSURE SYSTEM

Next: p152, !f804

PUMP LIMPET TEST

Next: p815, !f811

BYPASS (INTERNAL)

ENSURE RADS ARE OPEN AND WATER CAN CIRCULATE AROUND THE SYSTEM

Next: !p834, !f934

DIVERTER VALVE ACTUATOR OPERATION

REMOVE THE DIVERTER

Next: p805, f1636

BOILER RESET

ENSURE BOILER HAS COOLED

Next: !p849, !f910

RESISTANCE OH STAT

DISCONNECT ONE OF THE ORANGE LEADS FROM THE OVERHEAT STAT

Next: p919, !f920

RESISTANCE FLUE OH STAT

DISCONNECT ONE OF THE ORANGE LEADS FROM THE OVERHEAT STAT

Next: !p1047, f1046

INSPECTION PRESSURE SYSTEM

Next: p924, !f925

PUMP LIMPET TEST

Next: p1490, !f926

CONDENSATE PIPE

Next: p989, !f988

INLET PRESSURE

ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT ON GAS VALVE

Next: p990, !f991

FAN PRESSURE TEST

ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT

Next: p992, f1010

INSPECTION FLUE

Next: !p1020, !f1011

System Information

  • Total Tests: 429
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control