Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to DC Volts Set meter to measure DC Volts
CH Demand
Attach temperature clamp to flow pipe
Set boiler temperature control to maximum
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow appliance to fire and system to heat.
Measure for dc voltage between overheat stat and pcb connection as illustrated.
(There are different versions of pcb used in this appliance)
Expected voltage between 30 - 40 vdc.
Note.
To speed up the process reduce the heating circuit by turning some rads off.
Observe both temperature and voltage readings.
Choose from the following observations.
BOILER MAINTAINS OR SHUTS DOWN AT 75 - 90°C, VOLTAGE PRESENT

VOLTAGE DISAPPEARS, BOILER GOES TO OVERHEAT, TEMP 90°C or BELOW
VOLTAGE PRESENT, TEMP AT 90°C AND BOILER STILL FIRED