Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Disconnect the brown and blue leads at the inline connectors from the flue temperature thermostat
Measurement:
Measure resistance across the exposed sensor terminal leads.
The resistance depends on temperature and should
conform to the table below:
The resistance depends on temperature and should
conform to the table below:
| Temperature °C | Resistance in kOhms |
| 20 -30 | 10 - 8 |
| 30 - 40 | 8 - 6.2 |
| 40 - 50 | 6.2 -4.4 |
| 50 - 60 | 4.4 - 3.3 |

Isolate as per TOPs P4
and refit as necessary