FAULT CODES 2
None
Fault code
Cause
Action
(
click on appropriate action
)
F0
Internal fault
Control unit
F1
Max. flue gas temperature exceeded
Check heating system fill level, circulation pump & system
F2
Temperature limiter has responded
Check heating system fill level, circulation pump & system. Check the temperature limiter and connecting cables
F3
Flame signal is already present at burner start
Check ionisation electrode and connecting cable
F4
No flame signal detected
Check ignition operation
F8
Fuel valve closes too late
Check gas train, check both control paths
F9
Fan speed too low during burner start
Check fan, fan connecting cables and power supply to fan; check fan control.
FA
Fan idle state not reached
Check fan, fan connecting cables and power supply to fan; check fan control.
FC
Electrical fan control (control unit) faulty
Check fan connecting cable; replace if required, or replace control unit
FD
Fault, burner control unit
Check ignition electrodes and connecting cables. Check whether a strong interference (EMC) field exists near the appliance.
FF
Fault, burner control unit
Check ignition electrodes and connecting cables. Check whether a strong interference (EMC) field exists near the appliance.
----
⧌
Comms error control and programming unit
Not applicable for this boiler.
No navigation options available