Set Appliance State:
Mains Power Off
Boiler On
System calling for heat
System calling for heat
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Look for signs of sparking through inspection window or listen for clicking sound from Full Sequence Board.
Note:
Ensure electrode is free from damage and there is a spark gap of 3-5mm positioned directly over the burner.
Note:
Ensure electrode is free from damage and there is a spark gap of 3-5mm positioned directly over the burner.