Set Appliance State:
Mains Power Off
CH Demand
Boiler CH thermostat set to 50°C
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow the boiler to reach 50°C and the burner to shut down.
Increase the boilers CH thermostat to Maximum (factory set 80°C).
Observe the appliance it should re fire after approximately 3 minutes.
Note:
Both anticycle and maximum temperature settings are adjustable in the boiler parameters if the boiler does not behave as described above it is advisable to check the parameters, refer to ADAPT for guidance.
Increase the boilers CH thermostat to Maximum (factory set 80°C).
Observe the appliance it should re fire after approximately 3 minutes.
Note:
Both anticycle and maximum temperature settings are adjustable in the boiler parameters if the boiler does not behave as described above it is advisable to check the parameters, refer to ADAPT for guidance.