RAVENHEAT RSF 82E - SIT
G.C. NUMBER 47 581 1
CH PUMP OVERRUNS
SELECTOR SWITCH TO H
CH MODULATION
{ISOLATEMAINSPOWER}<
SYSTEM PRESSURE RISE
SELECTOR SWITCH TO H
CH OPERATION
{ISOLATEMAINSPOWER}<
CH IGNITION
SELECTOR SWITCH TO H
DHW MODULATION
{ISOLATEMAINSPOWER}<
DHW BURNER CROSSLIGHTS (PRESSURE TO MAXIMUM)
{ISOLATEMAINSPOWER}<
DHW DEMAND FAN RUNS
SELECTOR SWITCH TO H
DHW PUMP RUNS
SELECTOR SWITCH TO H
DHW DEMAND
{ISOLATEMAINSPOWER}
SYSTEM CHECKS
{ISOLATEMAINSPOWER}
RAVENHEAT RSF 82E - SIT
{ISOLATEMAINSPOWER}<
PILOT IGNITES
SELECTOR SWITCH TO H
DHW OPERATION
SELECTOR SWITCH IN O
INFORMATION BOILER TYPES
PLEASE NOTE THIS BOI
BURNER CROSS LIGHTS BUT BAFFLES OUT
SENSOR - DHW/CH
BURNER CROSS LIGHTS BUT DIES OUT
GAS INLET PRESSURE
BURNER CROSS LIGHTS BUT DIES OUT
SENSOR - DHW/CH
BURNER PRESSURE LOW
SENSOR - DHW/CH
MOD SOL
GAS VALVE (MODULATING SOLENOID)
BURNER PRESSURE LOW
GAS INLET PRESSURE
DOESN'T CROSS LIGHT, PRESSURE ABSENT
CABLE - ELECTRODE
DOESN'T CROSS LIGHT, PRESSURE ABSENT
ELECTRODE
GV 2
GAS VALVE (MAIN GAS VALVE)
DOESN'T CROSS LIGHT, PRESSURE ABSENT
GAS INLET PRESSURE
DHW MODULATION
POTENTIOMETER - DHW/CH
ELEC CHECKS
ELECTRICAL SAFETY CHECKS
DHW MODULATION
SENSOR - DHW/CH
FUSE F1
FUSE F1 (500MA)
CH IGNITION
SWITCH - MAIN CIRCUIT
SYSTEM CHECKS
SYSTEM CHECKS
CH DEMAND CONTROL LINK VOLTAGE (IN)
PCB - CONTROL
CH POT
POTENTIOMETER - DHW/CH
BOILER NOISY, KETTLING
DIVERTER VALVE
BOILER COLD, RADIATORS COLD
SENSOR - DHW/CH
BOILER COLD, RADIATORS COLD
POTENTIOMETER - DHW/CH
BOILER UP TO TEMP, RADIATORS COLD
DIVERTER VALVE
EXP VESS
EXPANSION VESSEL
CH MODULATION
POTENTIOMETER - DHW/CH
CH MODULATION
SENSOR - DHW/CH
CH PUMP OVERRUNS
SENSOR - DHW/CH
DHW FLOW RATE
DIVERTER VALVE (FLOW ADJUSTER)
INLET FILTER
INLET FILTER
FLOW REGULATOR
FLOW REGULATOR
DHW RUNS HOT AND COLD BURNER CYCLES ON AND OFF
PILOT BURNER
DHW SENSOR (FULL DEMAND)
SENSOR - DHW/CH
DHW RUNS HOT AND COLD BURNER CYCLES ON AND OFF
POTENTIOMETER - DHW/CH
DHW TOO COOL RADIATORS COLD
SENSOR - DHW/CH
DHW TOO COOL RADIATORS COLD
POTENTIOMETER - DHW/CH
DHW BURNER CROSSLIGHTS - PRESSURE LOW
SENSOR - DHW/CH
DHW BURNER CROSSLIGHTS - PRESSURE LOW
POTENTIOMETER - DHW/CH
DIV DIAPHRAGM
DIVERTER VALVE DIAPHRAGM
DHW OPERATION - RUNS HOT COLD
SENSOR - DHW/CH
DHW OPERATION - DHW COOL RADS COOL
SENSOR - DHW/CH
APS VOLTAGE COM
PCB - IGNITION - SIT
DIV SPINDLE
DIVERTER VALVE SPINDLE
PILOT IGNITES
AIR PRESSURE SWITCH TUBES
PILOT IGNITES
FLUE VENTURI
PILOT IGNITES
FLUE
ELECTRODE LEAD
CABLE - ELECTRODE
ELECTRODE
ELECTRODE
GV 1 PILOT
GAS VALVE (PILOT)
GAS INLET PRES
GAS INLET PRESSURE
PILOT INJECTOR
PILOT INJECTOR
GAS VALVE 1 VOLTAGE
PCB - IGNITION - SIT
PILOT IGNITES - POOR FLAME PICTURE
PILOT INJECTOR
PILOT IGNITES - POOR FLAME PICTURE
GAS INLET PRESSURE
PILOT IGNITES
PRESSURE SWITCH - AIR
INFO BOILER TYPE
Z REDIRECT
FUSE F2
FUSE F2 (2A)
DHW PUMP RUNS
PCB - CONTROL
SYSTEM PRESS
SYSTEM PRESSURE
DIVERTER VALVE MICROSWITCH
DIVERTER VALVE MICROSWITCH
OH THERMOSTAT
THERMOSTAT - OVERHEAT
CH SENSOR
SENSOR - DHW/CH
DHW SENSOR
SENSOR - DHW/CH
DHW POT
POTENTIOMETER - DHW/CH
AIR PRESSURE SWITCH TUBES
AIR PRESSURE SWITCH TUBES
FLUE VENTURI
FLUE VENTURI
FLUE
FLUE
FUSE F3
FUSE F3 (4AMP)
BURNER INJECTOR
BURNER INJECTOR
HEAT EX FLUE
HEAT EXCHANGER (FLUEWAYS)
BURNER CROSS LIGHTS BUT DIES OUT
HEAT EXCHANGER (FLUEWAYS)
GAS INLET PRESSURE (FULL DEMAND)
GAS VALVE (MODULATING SOLENOID)
DOESN'T CROSS LIGHT, PRESSURE ABSENT
PCB - IGNITION - SIT
GAS INLET PRESSURE (FULL DEMAND)
GAS VALVE (MAIN GAS VALVE)
DHW MODULATION
GAS VALVE (MODULATING SOLENOID)
DHW MODULATION
PCB - CONTROL
CONTROL LINK
CONTROL LINK
POTENITOMETER RESISTANCE CH
PCB - CONTROL
BOILER NOISY, KETTLING
HEAT EXCHANGER
BOILER COLD, RADIATORS COLD
PCB - CONTROL
CH MODULATION
PCB - CONTROL
CH PUMP OVERRUNS
PCB - CONTROL
DHW NOISY, KETTLING
HEAT EXCHANGER
HEAT EX LO FLO
HEAT EXCHANGER LOW FLOW
DHW TOO COOL RADIATORS HOT WITH NO CH DEMAND
DIVERTER VALVE
DHW RUNS HOT AND COLD BURNER CYCLES ON AND OFF
PCB - CONTROL
DHW TOO COOL RADIATORS COLD
HEAT EXCHANGER
DHW TOO COOL RADIATORS COLD
BURNER INJECTOR
BURNER PRESSURE LOW
PCB - CONTROL
DIV VALVE
DIVERTER VALVE
PILOT IGNITES - RESISTANCE OK
GAS VALVE (PILOT)
PILOT IGNITES - POOR FLAME PICTURE
BURNER - POLIDORO PA525F - PILOT NG
SEL SWITCH
SWITCH - MAIN CIRCUIT
SYS PRES SW
PRESSURE SWITCH - LOW WATER
PUMP
PUMP
CONTROL PCB
PCB - CONTROL
POTENTIOMETER RESISTANCE DHW
PCB - CONTROL
AIR PRESSURE SWITCH
PRESSURE SWITCH - AIR
FAN
FAN
IGN PCB
PCB - IGNITION - SIT
BURNER CROSS LIGHTS BUT DIES OUT
CHARACTERISTIC TEST FROM DHW BURNER CROSSLIGHTS (PRESSURE TO MAXIMUM)
BURNER PRESSURE LOW
CHARACTERISTIC TEST FROM DHW BURNER CROSSLIGHTS (PRESSURE TO MAXIMUM)
DOESN'T CROSS LIGHT, OUTLET PRESSURE PRESENT
CHARACTERISTIC TEST FROM DHW BURNER CROSSLIGHTS (PRESSURE TO MAXIMUM)
DOESN'T CROSS LIGHT, PRESSURE ABSENT
CHARACTERISTIC TEST FROM DHW BURNER CROSSLIGHTS (PRESSURE TO MAXIMUM)
BOILER NOISY, KETTLING
CHARACTERISTIC TEST FROM CH OPERATION
BOILER COLD, RADIATORS COLD
CHARACTERISTIC TEST FROM CH OPERATION
BOILER UP TO TEMP, RADIATORS COLD
CHARACTERISTIC TEST FROM CH OPERATION
DHW NOISY, (KETTLING)
CHARACTERISTIC TEST FROM DHW OPERATION
DHW TOO COOL RADS COLD
CHARACTERISTIC TEST FROM DHW OPERATION
DHW TOO COOL, RADIATORS / FLOW PIPE BEGIN TO HEAT WITH NO CH DEMAND
CHARACTERISTIC TEST FROM DHW OPERATION
DHW RUNS HOT AND COLD, BURNER CYCLES ON AND OFF
CHARACTERISTIC TEST FROM DHW OPERATION
PILOT DOES NOT IGNITE
CHARACTERISTIC TEST FROM PILOT IGNITES
PILOT IGNITES BUT WITH POOR FLAME PICTURE
CHARACTERISTIC TEST FROM PILOT IGNITES
BURNER CROSS LIGHTS BUT BAFFLES OUT
CHARACTERISTIC TEST FROM DHW BURNER CROSSLIGHTS (PRESSURE TO MAXIMUM)
01/11/2017 11:13:53 1710_1_50_1 09/01/2018 09:09:46
20/11/2017 15:10:54
DHW SENSOR
{ISOLATEMAINSPOWER}
DISCONNECT PLUG FROM DHW SENSOR (BLUE LEADS)
ELECTRODE LEAD INSPECTION
{ISOLATEMAINSPOWER}
DHW MODULATION VOLTAGE
SELECTOR SWITCH IN O
DHW POTENTIOMETER RESISTANCE
{ISOLATEMAINSPOWER}<
EXTERNAL CONTROLS (VOLTAGE OUT)
{ISOLATEMAINSPOWER}<
EXTERNAL CONTROLS (VOLTAGE IN)
SELECTOR SWITCH TO H
FUSE F1 RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE CONTROL BOX COVER
REMOVE FUSE F1 FROM PCB
CH DEMAND CONTROL LINK VOLTAGE (IN)
{ISOLATEMAINSPOWER}<
FLOW ADJUSTER
{ISOLATEMAINSPOWER}
CH POTENTIOMETER RESISTANCE
{ISOLATEMAINSPOWER}<
CH SENSOR
{ISOLATEMAINSPOWER}
DISCONNECT PLUG FROM CH SENSOR (RED LEADS)
DIVERTER VALVE DIAPHRAGM
{ISOLATEMAINSPOWER}
WATER OFF
DISCHARGE AND DRAIN BOILER
DHW POTENTIOMETER RESISTANCE
{ISOLATEMAINSPOWER}<
AIR PRESSURE SWITCH VOLTAGE (COM)
{ISOLATEMAINSPOWER}<
SELECTOR SWITCH (OUTPUT)
{ISOLATEMAINSPOWER}<
FUSE F2 RESISTANCE
{ISOLATEMAINSPOWER}
REMOVE FUSE F2 FROM THE MAIN PCB
DIVERTER VALVE MICROSWITCH RESISTANCE
{ISOLATEMAINSPOWER}<
VOLTAGE TO IGNITION BOARD
{ISOLATEMAINSPOWER}<
OVERHEAT THERMOSTAT RESISTANCE
{ISOLATEMAINSPOWER}
SELECTOR SWITCH TO OFF POSITION
AIR PRESSURE SWITCH TUBES
{ISOLATEMAINSPOWER}
FUSE F3 RESISTANCE
{ISOLATEMAINSPOWER}<
GAS INLET PRESSURE (FULL DEMAND)
{ISOLATEMAINSPOWER}<
GAS VALVE 3 VOLTAGE
SELECTOR SWITCH IN O
GAS VALVE 2 VOLTAGE
{ISOLATEMAINSPOWER}<
GAS VALVE 3 VOLTAGE
SELECTOR SWITCH IN O
GAS VALVE 3 VOLTAGE
SELECTOR SWITCH IN O
GAS VALVE 3 RESISTANCE
{ISOLATEMAINSPOWER}
DISCONNECT VIOLET LEADS FROM THE MODULATING SOLENOID
GAS INLET PRESSURE (FULL DEMAND)
{ISOLATEMAINSPOWER}<
GAS VALVE 2 RESISTANCE
{ISOLATEMAINSPOWER}<
ELECTRODE INSPECTION
{ISOLATEMAINSPOWER}
GAS INLET PRESSURE (FULL DEMAND)
{ISOLATEMAINSPOWER}<
DHW SENSOR
{ISOLATEMAINSPOWER}
DISCONNECT PLUG FROM DHW SENSOR (BLUE LEADS)
CH DEMAND CONTROL LINK VOLTAGE (OUT)
{ISOLATEMAINSPOWER}<
CH SELECTOR SWITCH RESISTANCE
{ISOLATEMAINSPOWER}<
POTENTIOMETER RESISTANCE CH
{ISOLATEMAINSPOWER}<
DIVERTER VALVE CH POSITION
SELECTOR SWITCH TO H
CH SENSOR
{ISOLATEMAINSPOWER}
DISCONNECT PLUG FROM CH SENSOR (RED LEADS)
DIVERTER VALVE CH POSITION
SELECTOR SWITCH TO H
CH POTENTIOMETER RESISTANCE
{ISOLATEMAINSPOWER}<
INLET FILTER
{ISOLATEMAINSPOWER}
WATER OFF
CH SENSOR
{ISOLATEMAINSPOWER}
DISCONNECT PLUG FROM CH SENSOR (RED LEADS)
FLOW REGULATOR
{ISOLATEMAINSPOWER}
WATER OFF
DHW SENSOR
{ISOLATEMAINSPOWER}
DISCONNECT PLUG FROM DHW SENSOR (BLUE LEADS)
PILOT BURNER INSPECTION
{ISOLATEMAINSPOWER}
DHW SENSOR
{ISOLATEMAINSPOWER}
DISCONNECT PLUG FROM DHW SENSOR (BLUE LEADS)
DHW POTENTIOMETER RESISTANCE
{ISOLATEMAINSPOWER}<
CH SENSOR
{ISOLATEMAINSPOWER}
DISCONNECT PLUG FROM CH SENSOR (RED LEADS)
DHW POTENTIOMETER RESISTANCE
{ISOLATEMAINSPOWER}<
CH SENSOR
{ISOLATEMAINSPOWER}
DISCONNECT PLUG FROM CH SENSOR (RED LEADS)
CH SENSOR
{ISOLATEMAINSPOWER}
DISCONNECT PLUG FROM CH SENSOR (RED LEADS)
DIVERTER VALVE SPINDLE
{ISOLATEMAINSPOWER}
WATER OFF
DISCHARGE AND DRAIN BOILER
AIR PRESSURE SWITCH AIR DETECT
{ISOLATEMAINSPOWER}<
ELECTRODE LEAD INSPECTION
{ISOLATEMAINSPOWER}
AIR PRESSURE SWITCH TUBES
{ISOLATEMAINSPOWER}
FLUE VENTURI
{ISOLATEMAINSPOWER}
ELECTRODE INSPECTION
{ISOLATEMAINSPOWER}
GAS VALVE 1 RESISTANCE
{ISOLATEMAINSPOWER}<
GAS INLET PRESSURE
{ISOLATEMAINSPOWER}<
PILOT INJECTOR
{ISOLATEMAINSPOWER}
GAS VALVE 1 VOLTAGE
{ISOLATEMAINSPOWER}<
GAS INLET PRESSURE
{ISOLATEMAINSPOWER}<
PILOT INJECTOR
{ISOLATEMAINSPOWER}
PRESSURE APS SWITCHING
{ISOLATEMAINSPOWER}<
SYSTEM PRESSURE SWITCH RESISTANCE
{ISOLATEMAINSPOWER}<
MAINS POWER IN
{ISOLATEMAINSPOWER}
REMOVE PLASTIC COVER FROM CONTROL BOX
SELECTOR SWITCH (INPUT)
{ISOLATEMAINSPOWER}
REMOVE PLASTIC COVER FROM CONTROL BOX
SELECTOR SWITCH IN OFF POSITION
PUMP VOLTAGE
{ISOLATEMAINSPOWER}<
AIR PRESSURE SWITCH RESISTANCE (NORMALLY CLOSED)
{ISOLATEMAINSPOWER}
REMOVE PLASTIC COVER FROM THE IGNITION CONTROL PCB ATTACHED TO THE GAS VALVE
CH SENSOR
{ISOLATEMAINSPOWER}
DISCONNECT PLUG FROM CH SENSOR (RED LEADS)
DHW SENSOR
{ISOLATEMAINSPOWER}
DISCONNECT PLUG FROM DHW SENSOR (BLUE LEADS)
POTENTIOMETER RESISTANCE DHW
{ISOLATEMAINSPOWER}<
FLUE VENTURI
{ISOLATEMAINSPOWER}
FAN VOLTAGE
SELECTOR SWITCH TO H
System Information
- Total Tests: 225
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control