Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove the electrode assembly
Measurement:
Inspect flame sense electrode and check for continuity across the flame sensing electrode.
Thoroughly check for damaged or cracked insulation and that the tip is not damaged or distorted.
Note:
Due to the electrode gasket being disturbed during this inspection, a new electrode assembly must be fitted even if it is deemed to be satisfactory
Thoroughly check for damaged or cracked insulation and that the tip is not damaged or distorted.
Note:
Due to the electrode gasket being disturbed during this inspection, a new electrode assembly must be fitted even if it is deemed to be satisfactory

Isolate as per TOPs P4
and refit as necessary