Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove the electrode assembly
Note:
Due to the electrode gasket being disturbed during this inspection, a new electrode assembly must be fitted even if it is deemed to be satisfactory
Note:
Due to the electrode gasket being disturbed during this inspection, a new electrode assembly must be fitted even if it is deemed to be satisfactory
Measurement:
Inspect flame sense electrode.
Thoroughly check for damaged or cracked insulation and that the tip is not damaged or distorted.
Check for continuity at either sides of the sensing electrode.
Thoroughly check for damaged or cracked insulation and that the tip is not damaged or distorted.
Check for continuity at either sides of the sensing electrode.

Isolate as per TOPs P4
and refit as necessary