Next: &nff, !f1987
ATTACH PRESSURE GAUG
Next: &nff, f1989
SENSOR - TEMPERATURE - DHW
Next: End
SET - CABLES (STEPPER MOTOR)
Next: End
SET - CABLES (STEPPER MOTOR)
Next: End
SENSOR - TEMPERATURE
Next: End
SENSOR - TEMPERATURE - DHW
Next: End
SYSTEM PRESSURE
Next: End
PRIMARY HEAT EXCHANGER
Next: End
SENSOR - TEMPERATURE
Next: End
SENSOR - TEMPERATURE - DHW
Next: End
PRIMARY HEAT EXCHANGER
Next: End
HARNESS PUMP DC
Next: End
LEAD - IGNITION
Next: End
HARNESS PUMP DC
Next: End
HARNESS PUMP DC
Next: End
DIVERTER VALVE ASSEMBLY
Next: End
PLATE - BEARING
Next: End
SET - CABLES (MAIN)
Next: End
SET - CABLES (MAIN)
Next: End
PLATE - BEARING
Next: End
LIMITER - TEMPERATURE (OVERHEAT THERMOSTAT)
Next: End
LIMITER - TEMPERATURE (SENSOR - FLUE)
Next: End
PLATE - BEARING
Next: End
LIMITER - TEMPERATURE (OVERHEAT THERMOSTAT)
Next: End
LIMITER - TEMPERATURE (SENSOR - FLUE)
Next: End
SENSOR - TEMPERATURE - DHW
Next: End
IMPULSE TUBE GAS VALVE
Next: End
PLATE - BEARING
Next: End
WATER COMPONENTS
Next: End
SET - ELECTRODES
Next: End
IMPULSE TUBE GAS VALVE
Next: End
IMPULSE TUBE GAS VALVE
Next: End
SET - CABLES (MAIN)
Next: End
SET - CABLES (MAIN)
Next: End
SET - ELECTRODES
Next: End
PLATE - BEARING
Next: End
SET - ELECTRODES
Next: End
PCB FACTORY RESET
Next: End
SENSOR - TEMPERATURE
Next: End
SENSOR - TEMPERATURE
Next: End
FLOW SENSOR ASSEMBLY
Next: End
MOTOR - DIVERTER VALVE
Next: End
SENSOR - TEMPERATURE - DHW
Next: End
SENSOR - TEMPERATURE
Next: End
SET - CABLES (MAIN)
Next: End
ELECTRICAL SAFETY CHECKS
Next: End
PLATE - BEARING
Next: End
ELECTRICAL SAFETY CHECKS
Next: End
FUSE (FUSED SPUR)
Next: End
PCB MAIN FUSE T2.5H
Next: End
LIMITER - TEMPERATURE (OVERHEAT THERMOSTAT)
Next: End
LIMITER - TEMPERATURE (SENSOR - FLUE)
Next: End
SYSTEM PRESSURE
Next: End
SYSTEM PRESSURE
Next: End
SENSOR - TEMPERATURE - DHW
Next: End
SENSOR - TEMPERATURE
Next: End
SECONDARY HEAT EXCHANGER
Next: End
SYSTEM PRESSURE
Next: End
SENSOR - TEMPERATURE
Next: End
SENSOR - TEMPERATURE
Next: End
EXPANSION VESSEL
Next: End
SYSTEM PRESSURE
Next: End
LIMITER - TEMPERATURE (OVERHEAT THERMOSTAT)
Next: End
LIMITER - TEMPERATURE (SENSOR - FLUE)
Next: End
SYSTEM PRESSURE
Next: End
SENSOR - TEMPERATURE
Next: End
LIMITER - TEMPERATURE (OVERHEAT THERMOSTAT)
Next: End
SENSOR - TEMPERATURE - DHW
Next: End
SENSOR - TEMPERATURE
Next: End
SET - CABLES (MAIN)
Next: End
SENSOR - TEMPERATURE
Next: End
SENSOR - TEMPERATURE - DHW
Next: End
RESET BUTTON STICKING
Next: End
LEAD - IGNITION
Next: End
SET - CABLES (MAIN)
Next: End
LIMITER - TEMPERATURE (SENSOR - FLUE)
Next: End
FILTER - INSERT - DHW
Next: End
SECONDARY HEAT EXCHANGER
Next: End
DIVERTER VALVE ASSEMBLY
Next: End
MOTOR - DIVERTER VALVE
Next: End
MOTOR - DIVERTER VALVE
Next: End
MOTOR - DIVERTER VALVE
Next: End
MOTOR - DIVERTER VALVE
Next: End
SET - CABLES (MAIN)
Next: End
SET - CABLES (MAIN)
Next: End
SECONDARY HEAT EXCHANGER
Next: End
INTERNAL CLOCK/WIRELESS CONTROL
Next: End
HOLIDAY MODE LED
Next: End
HOLIDAY MODE LED
Next: End
PRIMARY HEAT EXCHANGER
Next: End
SECONDARY HEAT EXCHANGER
Next: End
FILTER - INSERT - DHW
Next: End
FLOW SENSOR ASSEMBLY
Next: End
ADAPTOR - FLOW SENSOR
Next: End
SET - CABLES (MAIN)
Next: End
SET - CABLES (MAIN)
Next: End
SECONDARY HEAT EXCHANGER
Next: End
SET - ELECTRODES
Next: End
SET - ELECTRODES
Next: End
RESULT AS EXPECTED
Next: End
RESULT AS EXPECTED
Next: End
RESULT AS EXPECTED
Next: End
MOTOR - DIVERTER VALVE
Next: End
RESULT AS EXPECTED
Next: End
RESULT AS EXPECTED
Next: End
RESULT AS EXPECTED
Next: End
RESULT AS EXPECTED
Next: End
RESULT AS EXPECTED
Next: End
RESULT AS EXPECTED
Next: End
RESULT AS EXPECTED
Next: End
RESULT AS EXPECTED
Next: End
RESULT AS EXPECTED
Next: End
RESULT AS EXPECTED
Next: End
GAS VALVE - NO PRESSURE DROP
Next: End
SET - CABLES (MAIN)
Next: End
PRIMARY HEAT EXCHANGER
Next: End
EXPANSION VESSEL PIPE
Next: End
SET - CABLES (MAIN)
Next: End
SECONDARY HEAT EXCHANGER
Next: End
PRIMARY HEAT EXCHANGER
Next: End
FLOW SENSOR ASSEMBLY
Next: End
SET - CABLES (MAIN)
Next: End
SET - CABLES (MAIN)
Next: End
SET - CABLES (MAIN)
Next: End
SET - CABLES (MAIN)
Next: End
CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS ( FAN DOES RUN)
Next: !p11
CHARACTERISTIC TEST FROM DHW OPERATION
Next: p480
CHARACTERISTIC TEST FROM PERFORMANCE TEST MAX AND MIN
Next: p1422
CHARACTERISTIC TEST FROM PERFORMANCE TEST MAX AND MIN
Next: !p1088
CHARACTERISTIC TEST FROM DHW OPERATION
Next: p646
CHARACTERISTIC TEST FROM DHW OPERATION
Next: p113
CHARACTERISTIC TEST FROM DHW OPERATION
Next: p115
CHARACTERISTIC TEST FROM PRESSURE FAN MAXIMUM OUTPUT
Next: p1447
CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS ( FAN DOES RUN)
Next: !p13
CHARACTERISTIC TEST FROM PRESSURE FAN MAXIMUM OUTPUT
Next: !p1202
CHARACTERISTIC TEST FROM VOLTAGE DIVERTER VALVE PCB DROP RETURN TO 15V
Next: p1218
CHARACTERISTIC TEST FROM VOLTAGE DIVERTER VALVE PCB DROP RETURN TO 15V
Next: !p1220
CHARACTERISTIC TEST FROM VOLTAGE DIVERTER VALVE PCB DROP RETURN TO 15V
Next: p1243
CHARACTERISTIC TEST FROM VOLTAGE DIVERTER VALVE PCB DROP RETURN TO 15V
Next: !p1245
CHARACTERISTIC TEST FROM DHW OPERATION
Next: p1281
CHARACTERISTIC TEST FROM PUMP OVERRUN
Next: !p1338
CHARACTERISTIC TEST FROM PUMP OVERRUN
Next: p1711
CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS ( FAN DOES RUN)
Next: !p15
CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS ( FAN DOES RUN)
Next: !p1437
CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS ( FAN DOES RUN)
Next: !p1439
CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS ( FAN DOES RUN)
Next: !p1441
CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS ( FAN DOES RUN)
Next: !p1519
CHARACTERISTIC TEST FROM CH OPERATION
Next: p594
CHARACTERISTIC TEST FROM INSPECTION BURNER AND ELECTRODE ASSEMBLY
Next: !p1650
CHARACTERISTIC TEST FROM CH OPERATION
Next: p166
CHARACTERISTIC TEST FROM INSPECTION BURNER AND ELECTRODE ASSEMBLY
Next: !p1652
CHARACTERISTIC TEST FROM CH OPERATION
Next: p168
CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)
Next: !p1723
CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)
Next: p1888
CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)
Next: !p1735
CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)
Next: p1882
CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB) - NEW STYLE
Next: p1753
CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB) - NEW STYLE
Next: p1755
CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB)
Next: p1765
CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB)
Next: p1767
CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)
Next: !p1785
CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)
Next: p1898
CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)
Next: !p1797
CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)
Next: p1892
CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB) - NEW STYLE
Next: p1849
CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB) - NEW STYLE
Next: p1851
CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB)
Next: p1861
CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB)
Next: p1863
CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH
Next: p20
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1910
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1912
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1914
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1916
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1918
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1920
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1922
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1924
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1926
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1928
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1930
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1932
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1934
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: !p1936
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1938
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
Next: p1940
CHARACTERISTIC TEST FROM VOLTAGE DIVERTER VALVE PCB DROP RETURN TO 15V
Next: p1948
CHARACTERISTIC TEST FROM VOLTAGE DIVERTER VALVE PCB DROP RETURN TO 15V
Next: !p1950
CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH
Next: p22
CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH
Next: p270
CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH
Next: p327
CHARACTERISTIC TEST FROM MODE OF FAN OPERATION
Next: p387
CHARACTERISTIC TEST FROM MODE OF FAN OPERATION
Next: p1748
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
Next: p445
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
Next: !p444
CHARACTERISTIC TEST FROM DHW OPERATION
Next: p582
CHARACTERISTIC TEST FROM DIFFERENTIAL FLOW RETURN CH OPERATION
Next: !p600
CHARACTERISTIC TEST FROM DIFFERENTIAL FLOW RETURN CH OPERATION
Next: !p602
CHARACTERISTIC TEST FROM CH OPERATION
Next: p634
CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS
Next: !p765
13/01/2023 07:24:25
Next: End
{ONOFFSWITCHON}
N
Next: !p1216, ?1217, ?1219
{ONOFFSWITCHON}
N
Next: !p1241, ?1242, ?1244
GAIN ACCESS TO THE P
Next: p1262, f1253
REMOVE THE DC PUMP CONNECTOR FROM THE PCB AND MAKE SAFE
Next: p1254, !f1255
REMOVE CONNECTOR FROM PRIMARY SENSOR
ENSURE PRIMARY HEAT EXCHANGER IS BELOW 60° C
Next: !p1269, !f1270
REMOVE ORANGE WIRES FROM DHW SENSOR
Next: !p1278, !f1279
GAIN ACCESS TO PCB (USE ISOLATION MAT AS REQUIRED)
EXTERNAL CONTROLS CALLING FOR HEAT
Next: p1296, f1297
GAIN ACCESS TO PCB (USE ISOLATION MAT AS REQUIRED)
Next: !p1298, !f1299
{ONOFFSWITCHON}
CH BOILER THERMOSTAT SET TO MAX
Next: !p1302, !f1303
GAIN ACCESS TO PCB (USE ISOLATION MAT AS REQUIRED)
Next: !p1306, !f1307
ATTACH TEMPERATURE PROBES AS INDICATED BY THE RED ARROWS
Next: !p1322, !f1323
DISCONNECT FAN CONNECTOR AT FAN
Next: !p1460, f1874
REMOVE ST9 CONNECTOR
Next: p1595, f1467
REMOVE THE LEADS FRO
Next: !p1468, !f1469
REMOVE THE LEADS FRO
Next: !p1472, !f1473
REMOVE CONTROL BOX C
Next: !p1522, f1523
DISCONNECT RED LEADS FROM THE OVERHEAT THERMOSTAT
Next: p1524, !f1525
DISCONNECT RED LEADS FROM THE OVERHEAT THERMOSTAT
Next: p1551, !f1552
REMOVE THE LARGE 20 WAY CONNECTOR (ST9) FROM THE RIGHT HAND SIDE OF THE PCB.
Next: p1658, f1659
REMOVE THE ORANGE LE
Next: !p1660, !f1661
{ONOFFSWITCHON}
Next: p1844, f1780
MOVE CONNECTOR ST5 U
Next: p1721, ?1722, ?1724
MOVE CONNECTOR ST5 T
Next: p1751, ?1752, ?1754
MOVE CONNECTOR ST5 U
Next: p1783, ?1784, ?1786
REMOVE ORANGE WIRES FROM PRIMARY SENSOR
ENSURE PRIMARY HEAT EXCHANGER IS BELOW 60° C
Next: !p185, !f186
MOVE CONNECTOR ST5 T
Next: p1847, ?1848, ?1850
REMOVE CONTROL BOX COVER IF NECESSARY, USE ISOLATION MAT AS REQUIRED
Next: p200, f201
REMOVE FUSE FROM FUSED SPUR
Next: !p202, f203
REMOVE CONTROL BOX COVER IF NECESSARY
Next: p273, f274
DISCONNECT RED LEADS FROM THE OVERHEAT THERMOSTAT
Next: p390, !f391
DRAIN THE DOMESTIC H
Next: p7, ?8, ?10, ?12, ?14
ENSURE BOILER IS COOL
Next: p708, f709
REMOVE CONTROL BOX C
Next: !p710, f711
DISCONNECT RED LEADS FROM THE OVERHEAT THERMOSTAT
Next: p712, !f713
GAIN ACCESS TO THE P
Next: p1411, f721
REMOVE THE DC PUMP CONNECTOR FROM THE PCB AND MAKE SAFE
Next: p722, !f775
ATTACH TEMPERATURE PROBES AS INDICATED BY THE RED ARROWS
Next: !p734, f735
DISCONNECT RED LEADS
Next: !p1039, !f762
REMOVE PUMP CONNECTOR FROM PCB
Next: p1457, f821
DISCONNECT THE PUMP HARNESS AT THE PUMP AND THE PCB
Next: !p822, !f823
REMOVE ST9 CONNECTOR
Next: !p874, f875
REMOVE ORANGE WIRES FROM DHW SENSOR
Next: !p876, !f877
REMOVE ST9 CONNECTOR
Next: !p880, f881
REMOVE CONNECTOR FROM PRIMARY SENSOR
ENSURE PRIMARY HEAT EXCHANGER IS BELOW 60° C
Next: !p882, !f883
DISCONNECT THE INLIN
Next: !p905, !f906
REMOVE CONNECTOR FROM PRIMARY SENSOR
ENSURE PRIMARY HEAT EXCHANGER IS BELOW 60° C
Next: !p909, !f910
REMOVE ORANGE WIRES FROM DHW SENSOR
Next: !p912, !f913
LOWER THE FACIA PANEL
Next: !p929, !f928
REMOVE PCB COVER AS NECESSARY
Next: p933, !f932
GAIN ACCESS TO PCB AS NECESSARY
Next: p980, !f979
REMOVE THE DIVERTER
Next: !p118, f1215
REMOVE ORANGE WIRES FROM DHW SENSOR
Next: !p116, !f117
NO DEMAND
PREHEAT SWITCHED OFF (ECO BUTTON ILLUMINATED)
REMOVE CONNECTOR ST17 FROM PCB
Next: p1221, !f1222
REMOVE THE CONNECTOR
Next: !p1223, !f1224
NO DEMAND
PREHEAT SWITCHED OFF (ECO BUTTON ILLUMINATED)
REMOVE CONNECTOR ST17 FROM PCB
Next: p1246, !f1247
REMOVE THE CONNECTOR
Next: !p1248, !f1249
DISCONNECT THE PUMP HARNESS AT THE PUMP AND THE PCB
Next: !p1256, !f1257
REMOVE ST9 CONNECTOR
Next: p1271, f1268
REMOVE ST9 CONNECTOR
Next: p1407, f1277
ATTACH TEMPERATURE PROBES AS INDICATED BY THE RED ARROWS
Next: p1286, !f1287
REMOVE CONNECTOR FROM PRIMARY SENSOR
ENSURE PRIMARY HEAT EXCHANGER IS BELOW 60° C
Next: p1288, !f1289
REMOVE ORANGE WIRES FROM DHW SENSOR
Next: !p1290, !f1291
GAIN ACCESS TO PCB (USE ISOLATION MAT AS REQUIRED)
EXTERNAL CONTROLS CALLING FOR HEAT
Next: p1304, f1305
REMOVE AND DISCONNECT THE INTERNAL CLOCK OR WIRELESS RECEIVER ASSEMBLY FROM THE BOILER
Next: !p1300, f1301
{ONOFFSWITCHON}
CH BOILER THERMOSTAT SET TO MAX
Next: !p1308, !f1309
ENSURE PLATE HEAT EX
Next: p1316, !f1574
ATTACH TEMPERATURE PROBES AS INDICATED BY THE RED ARROWS
DHW THERMOSTAT TO MAX
Next: p1528, f1321
REMOVE CONDENSE TRAP
Next: !p1680, !f1342
REMOVE THE IGNITION HARNESS FROM THE PCB
AND THE SPARK ELECTRODES
Next: p1493, !f1346
REMOVE CONDENSE TRAP
Next: p1589, !f1409
REMOVE CONDENSE TRAP
Next: !p1414, !f1413
REMOVE THE DIVERTER VALVE ACTUATOR FROM THE DIVERTER VALVE BODY
Next: p1416, !f1417
REMOVE AIR INTAKE MANIFOLD FROM THE FAN
Next: !p1423, !f1424
DRAIN THE DOMESTIC H
Next: !p1446, ?1436, ?1438, ?1440, ?1518
REMOVE FLUE WAYS INSPECTION PLATE
Next: p1451, !f1452
REMOVE FAN ASSEMBLY
Next: !p1453, !f1454
DISCONNECT FAN CONNECTOR ST5 FROM THE PCB
Next: p1458, f1459
REMOVE THE BACK PLATE OF THE CONTROL BOX AND THE TRANSFORMER FROM THE PCB
Next: p1462, !f1463
REMOVE ST9 CONNECTOR
Next: p1592, f1471
ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT
Next: p1494, f1495
REMOVE AIR INTAKE MANIFOLD FROM THE FAN
Next: p1645, !f1503
REMOVE FLUE WAYS INSPECTION PLATE
Next: p1498, !f1499
REMOVE FAN ASSEMBLY
Next: !p1500, !f1501
DISCONNECT THE RED LEADS FROM THE FLUE TEMPERATURE THERMOSTAT
Next: !p1526, !f1527
REMOVE CONTROL BOX C
Next: p1536, f1550
ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT
Next: p1537, f1538
REMOVE AIR INTAKE MANIFOLD FROM THE FAN
Next: p1977, !f1546
REMOVE FLUE WAYS INSPECTION PLATE
Next: p1541, !f1542
REMOVE FAN ASSEMBLY
Next: !p1543, !f1544
DISCONNECT THE RED LEADS FROM THE FLUE TEMPERATURE THERMOSTAT
Next: !p1553, !f1554
REMOVE ORANGE WIRES FROM DHW SENSOR
Next: p1313, !f1573
REMOVE DC CONNECTOR FROM PUMP.
Next: !p1590, !f1591
REPLACE THE BLOWN FU
Next: !p1593, !f1594
REPLACE THE BLOWN FU
Next: !p1596, !f1597
REMOVE GAS VALVE IMPULSE TUBE
Next: p1602, !f1600
ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT
Next: p1603, f1604
REMOVE AIR INTAKE MANIFOLD FROM THE FAN
Next: p1611, !f1612
REMOVE FLUE WAYS INSPECTION PLATE
Next: p1607, !f1608
REMOVE FAN ASSEMBLY
Next: !p1609, !f1610
ATTACH U GAUGE TO INLET PRESSURE TEST POINT
ENSURE NO OTHER GAS APPLIANCES ARE IN OPERATION
Next: p1639, !f1640
REMOVE THE ELECTRODE
Next: !p1643, !f1644
REMOVE GAS VALVE IMPULSE TUBE
Next: p1647, !f1646
REMOVE THE BURNER ASSEMBLY FROM THE APPLIANCE
Next: !p1648, ?1649, ?1651
REMOVE GAS VALVE IMPULSE TUBE
Next: p1655, !f1654
GAIN ACCESS TO MAINS
Next: p1656, f1657
REMOVE THE ORANGE LE
Next: p1662, !f1663
REMOVE THE ELECTRODE
Next: !p1664, !f1665
ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT
Next: p1668, f1669
REMOVE AIR INTAKE MANIFOLD FROM THE FAN
Next: p1676, !f1677
REMOVE FLUE WAYS INSPECTION PLATE
Next: p1672, !f1673
REMOVE FAN ASSEMBLY
Next: !p1674, !f1675
REMOVE THE ELECTRODE
Next: !p1678, !f1679
Next: p1340, !f1717
MOVE CONNECTOR ST5 U
Next: p1732, ?1734, ?1736
DISCONNECT ELECTRICA
Next: p1728, !f1729
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: !p1726, !f1727
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: !p1730, !f1731
DISCONNECT ELECTRICA
Next: p1742, !f1743
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: p1738, !f1739
REMOVE AIR INTAKE HO
Next: !p1740, !f1741
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: p1744, !f1745
REMOVE AIR INTAKE HO
Next: !p1746, !f1747
MOVE CONNECTOR ST5 T
Next: p1762, ?1764, ?1766
REMOVE ORANGE WIRES FROM PRIMARY SENSOR
ENSURE PRIMARY HEAT EXCHANGER IS BELOW 60° C
Next: p177, !f178
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: !p1760, !f1761
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: !p1758, !f1759
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: !p1756, !f1757
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: p1774, !f1775
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: p1770, !f1771
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: !p1768, !f1769
REMOVE THE DIVERTER
Next: p1415, f1240
REMOVE AIR INTAKE HO
Next: !p1772, !f1773
REMOVE AIR INTAKE HO
Next: !p1776, !f1777
MOVE CONNECTOR ST5 U
Next: p1794, ?1796, ?1798
DISCONNECT ELECTRICA
Next: p1790, !f1791
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: !p1788, !f1789
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: !p1792, !f1793
DISCONNECT ELECTRICA
Next: p1806, !f1807
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: p1879, !f1801
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: p1808, !f1809
REMOVE AIR INTAKE HO
Next: !p1810, !f1811
MOVE CONNECTOR ST5 T
Next: p1858, ?1860, ?1862
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: !p1856, !f1857
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: !p1854, !f1855
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: !p1852, !f1853
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: p1870, !f1871
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: p1866, !f1867
DISCONNECT CONNECTOR ST5 FROM THE PCB
DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY
Next: !p1864, !f1865
REMOVE AIR INTAKE HO
Next: !p1868, !f1869
REMOVE AIR INTAKE HO
Next: !p1872, !f1873
REMOVE AIR INTAKE HO
Next: !p1877, !f1878
REMOVE AIR INTAKE HO
Next: !p1880, !f1881
REMOVE THE CONNECTOR
Next: p1737, !f1902
REMOVE THE CONNECTOR
Next: p1725, !f1903
REMOVE THE CONNECTOR
Next: p1799, !f1905
REMOVE THE CONNECTOR
Next: p1787, !f1904
DIAGNOSIS RELIES ON
Next: !p1975, !f1976
THE TABLE BELOW SHOW
Next: !p1973, !f1974
REMOVE ORANGE WIRES FROM PRIMARY SENSOR
ENSURE PRIMARY HEAT EXCHANGER IS BELOW 60° C
Next: !p1971, !f1972
REMOVE ORANGE WIRES FROM DHW SENSOR
Next: !p1969, !f1970
REMOVE ST9 CONNECTOR
Next: !p1967, !f1968
REMOVE THE GAS VALVE
Next: !p1965, !f1966
REMOVE ST9 CONNECTOR
Next: !p1963, !f1964
REMOVE PUMP CONNECTOR FROM PCB
Next: !p1961, !f1962
REMOVE THE DC PUMP CONNECTOR FROM THE PCB AND MAKE SAFE
Next: !p1959, !f1960
DISCONNECT FAN CONNECTOR AT FAN
Next: !p1957, !f1958
REMOVE THE BACK PLATE OF THE CONTROL BOX AND THE TRANSFORMER FROM THE PCB
Next: !p1955, !f1956
REMOVE ST17 CONNECTO
Next: !p1953, !f1954
{ONOFFSWITCHON}
N
Next: !p1945, ?1947, ?1949
REMOVE DC CONNECTOR FROM PUMP.
Next: !p1943, !f1944
TURN HOT WATER TAP ON WITH A FLOW RATE OF APPROXIMATELY 3 L/MIN
Next: !p1941, !f1942
NO DEMAND
PREHEAT SWITCHED OFF (ECO BUTTON ILLUMINATED)
REMOVE CONNECTOR ST17 FROM PCB
Next: !p1951, !f1952
REMOVE THE LEADS FRO
Next: !p1978, !f1979
REMOVE FLUE WAYS INSPECTION PLATE
Next: p1994, !f1995
REMOVE FAN ASSEMBLY
Next: !p1996, !f1997
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT ON GAS VALVE
Next: p1653, !f90
{ONOFFSWITCHON}
Next: p408, ?386, ?394
GAIN ACCESS TO PCB (USE ISOLATION MAT AS REQUIRED)
Next: p898, f272
REMOVE CONTROL BOX C
Next: p277, f278
REMOVE CONTROL BOX C
Next: p281, f282
REMOVE THE BACK PLATE OF THE CONTROL BOX AND THE TRANSFORMER FROM THE PCB
Next: !p285, !f286
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT ON GAS VALVE
Next: p1598, !f331
REMOVE CONTROL BOX C
Next: !p388, f389
DISCONNECT THE RED LEADS FROM THE FLUE TEMPERATURE THERMOSTAT
Next: !p392, !f393
REMOVE THE GAS VALVE
Next: p1535, f1521
REMOVE SPARK LEADS F
Next: p61, !f400
REMOVE ORANGE WIRES FROM DHW SENSOR
Next: p586, !f589
REMOVE ORANGE WIRES FROM PRIMARY SENSOR
ENSURE PRIMARY HEAT EXCHANGER IS BELOW 60° C
Next: p587, !f590
ATTACH TEMPERATURE PROBES AS INDICATED BY THE RED ARROWS
DHW THERMOSTAT TO MAX
Next: !p591, !f593
REMOVE ORANGE WIRES FROM PRIMARY SENSOR
ENSURE PRIMARY HEAT EXCHANGER IS BELOW 60° C
Next: p597, !f605
ATTACH TEMPERATURE PROBES AS INDICATED BY THE RED ARROWS
Next: !p598, ?599, ?601
REMOVE ORANGE WIRES FROM PRIMARY SENSOR
ENSURE PRIMARY HEAT EXCHANGER IS BELOW 60° C
Next: !p610, !f611
ATTACH U GAUGE TO INLET PRESSURE TEST POINT
Next: p1344, ?441, ?443
BOILER DRAINED AND DISCHARGED
Next: !p635, !f636
DISCONNECT THE RED LEADS FROM THE FLUE TEMPERATURE THERMOSTAT
Next: !p714, !f715
DISCONNECT THE PUMP HARNESS AT THE PUMP AND THE PCB
Next: !p779, !f768
ATTACH TEMPERATURE PROBES AS INDICATED BY THE RED ARROWS
DHW THERMOSTAT TO MAX
Next: p732, f733
ATTACH TEMPERATURE P
Next: p738, f739
REMOVE ORANGE WIRES FROM PRIMARY SENSOR
ENSURE PRIMARY HEAT EXCHANGER IS BELOW 60° C
Next: !p742, !f743
LOWER THE FACIA PANEL
Next: p900, !f899
TURN HOT WATER TAP ON WITH A FLOW RATE OF APPROXIMATELY 3 L/MIN
Next: p901, f902
REMOVE ST9 CONNECTOR
Next: p907, f908
REMOVE ST9 CONNECTOR
Next: p1718, f911
NO DEMANDS
Next: !p992, !f993
REMOVE THE IGNITION HARNESS FROM THE PCB
AND THE SPARK ELECTRODES
Next: p981, !f984
REMOVE THE ORANGE LE
Next: p982, !f985
REMOVE THE BACK PLATE OF THE CONTROL BOX AND THE TRANSFORMER FROM THE PCB
Next: !p983, !f986
System Information
- Total Tests: 731