Set Appliance State:
Gas Off
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Attach U-gauge to gas inlet pressure test point
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Cancel purge cycle & If required, reset boiler.
Allow ignition sequence to commence and boiler to ignite and ramp up for DHW demand.
Inlet pressure should remain above N.G. 18 mb, L.P.G. 29 mb throughout (see note).
Allow ignition sequence to commence and boiler to ignite and ramp up for DHW demand.
Inlet pressure should remain above N.G. 18 mb, L.P.G. 29 mb throughout (see note).