Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Gain access to PCB (use Insulation Mat as required)
Disconnect external controls from connector CN5 & make safe
No demands
Disconnect external controls from connector CN5 & make safe
No demands
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
With external controls disconnected does the boiler still attempt to fire after self-check & purge cycle has completed?
Cancel the purge cycle if required as per previous test.
Cancel the purge cycle if required as per previous test.
Isolate as per TOPs P4
and refit as necessary