Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove diverter valve actuator from diverter valve assembly
(this can be done without draining boiler)
(this can be done without draining boiler)
Measurement:
Confirm diverter valve spindle is not stiff or seized.
It should be possible to be pushed in easily (approximately 1cm) and move freely back into its original position.
It should be possible to be pushed in easily (approximately 1cm) and move freely back into its original position.
Isolate as per TOPs P4
and refit as necessary