Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
IDEAL MINI C24 HE
GLOBALLY REPLACED
OBSERVATION BOILER STANDBY
ENSURE NO DEMAND FOR
OBSERVATION PUMP RUNS
DHW TEMPERATURE SELECTOR SET TO MAX
OBSERVATION FAN RUNS
DHW TEMPERATURE SELECTOR SET TO MAX
TYPE OF DIAGNOSTIC PROCEDURE
PLEASE SELECT FROM O
OBSERVATION BURNER IGNITION
DHW TEMPERATURE SELECTOR SET TO MAX
PRESSURE BURNER MIN
ATTACH PRESSURE GAUG
OPERATION DHW
DHW TEMPERATURE SELECTOR SET TO MAX
SEQUENCE OF OPERATION
NO LONGER USED
FUSE FURTHER INVESTIGATION
OUTSIDE MODEL
FAULT CODE 202 - DHW OPERATION
OUTSIDE MODEL
FAULT CODE 202 - CH OPERATION
OUTSIDE MODEL
FAULT CODE 220 - FROST PROTECTION
OUTSIDE MODEL
FAULT CODE 210 - PUMP PROVING FAULT
OUTSIDE MODEL
FAULT CODE 021 - FAULTY DHW THERMISTOR
OUTSIDE MODEL
FAULT CODE 022 - FAULTY CH THERMISTOR
OUTSIDE MODEL
FAULT CODE 111 - PCB FAULT
OUTSIDE MODEL
OBSERVATION DHW MODULATION
ADJUST DHW FLOW RATE
OPERATION CH
CH TEMPERATURE CONTROL SET TO MAX
OBSERVATION CH MODULATION
CH TEMPERATURE CONTROL SET TO MAX
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE OUTLET TEST POINT
FAULT CODE FOR SINGLE PCB
OUTSIDE MODEL
ALTERNATIVE FLOW SWITCH TEST TREE
OUTSIDE MODEL
PRESSURE BURNER MAXIMUM
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE OUTLET TEST POINT
DHW TEMPERATURE SELECTOR SET TO MAX
PRESSURE IGNITION
{GAINPCBACS}
ATTA
FAULT CODE 002
CABLE - PUMP
OPERATION CH RADS DO NOT HEAT
SYSTEM PRESSURE
OPERATION CH RADS DO NOT HEAT
TAP 3/4IN - CH
OPERATION CH RADS DO NOT HEAT
MOTOR - PUMP
OPERATION CH RADS DO NOT HEAT
CABLE - PUMP
OPERATION CH RADS DO NOT HEAT
SERVICE KIT - DIVERTER VALVE
OPERATION CH RADS DO NOT HEAT
KIT - BY-PASS
OPERATION CH - RADS COOL
TEMPERATURE PROBE
FAULT CODE 002
RECUPERATOR
OBSERVATION BOILER RESPONDS TO CH DEMAND - OPEN CIRCUIT TO EXT CONTROLS
CABLE - POWER SUPPLY & EXT CONTROL
OBSERVATION BOILER RESPONDS TO CH DEMAND - WITHOUT INTEGRAL TIMER
CABLE - POWER SUPPLY & EXT CONTROL
OBSERVATION BOILER RESPONDS TO CH DEMAND - WITH INTEGRAL TIMER
CABLE - TIME SWITCH
OBSERVATION BURNER IGNITION - NOT ESTABLISHING - SHORTING TO EARTH
ELECTRODE - DETECTION
OBSERVATION BURNER IGNITION - NO SPARKING
SWITCH - AIR PRESSURE
OBSERVATION BURNER IGNITION - NO SPARKING
TUBE (AIR PRESSURE SWITCH)
OBSERVATION BURNER IGNITION - NO SPARKING
TEST POINT - AIR PRESSURE SWITCH
OBSERVATION BURNER IGNITION - NO SPARKING
HEAT EXCHANGER - MAIN
OBSERVATION BURNER IGNITION - NO SPARKING
RECUPERATOR
OPERATION DHW - DHW COOL RADS COOL
INLET PRESSURE
OPERATION DHW - DHW TOO COOL DHW SENSOR
TEMPERATURE PROBE
OBSERVATION BURNER IGNITION - NOT ESTABLISHING - NO RECT VOLTAGE
PCB - FULL SEQUENCE CONTROL DEVICE
OBSERVATION BURNER IGNITION - NOT IGNITING
PCB AND GAS VALVE
OBSERVATION BURNER IGNITION - NO IGNITION
HEAT EXCHANGER - MAIN
OBSERVATION BURNER IGNITION - NO IGNITION
THERMOSTAT 105DEG C - OVERHEAT
OBSERVATION BURNER IGNITION - NO IGNITION
THERMOSTAT - FLUE - LIMIT
OBSERVATION BOILER RESPONDS TO CH DEMAND - WITOUT INTEGRAL TIMER - IGNORING CH DEMAND
PCB - ELECTRONIC CONTROL
OPERATION DHW - TOO COOL RADS HEAT
PCB - ELECTRONIC CONTROL
OPERATION CH RADS DO NOT HEAT
PCB - ELECTRONIC CONTROL
OBSERVATION PUMP OVERRUN
PCB - ELECTRONIC CONTROL
FAULT CODE 002 - WILL NOT RESET
PCB - ELECTRONIC CONTROL
FAULT CODE 002 - NO VOLTAGE TO DIVERTER
PCB - ELECTRONIC CONTROL
FAULT CODE 022
PCB - ELECTRONIC CONTROL
FAULT CODE 021
PCB - ELECTRONIC CONTROL
FAULT CODE 210 - NO POWER TO PUMP
PCB - ELECTRONIC CONTROL
FAULT CODE 111
PCB - ELECTRONIC CONTROL
OBSERVATION BOILER STANDBY - STANDBY LED DOES NOT FLASH - FAULTY LED
PCB - ELECTRONIC CONTROL
OBSERVATION BOILER STANDBY - STANDBY LED DOES NOT FLASH - NO POWER TO PUMP
PCB - ELECTRONIC CONTROL
OBSERVATION PUMP RUNS - IGNORING DHW DEMAND
PCB - ELECTRONIC CONTROL
FUSE INVESTIGATION
CABLE - ELECTRONIC CONTROL PCB IGNITION DEVICE
FAULT CODE 202 - DHW
CABLE - DHW FLOW SWITCH AND TEMP...
OBSERVATION BOILER STANDBY - PUMP RUNS WITH NO DEMAND
CABLE - DHW FLOW SWITCH AND TEMP...
OPERATION DHW - NOISY
TEMPERATURE PROBE
OPERATION DHW - NOISY - RUNNING SLOW
MOTOR - PUMP
OPERATION DHW - NOISY
RECUPERATOR
OPERATION DHW - FLUE STAT TRIPS
HEAT EXCHANGER - MAIN
OPERATION DHW - FLUE STAT TRIPS
RECUPERATOR
OBSERVATION BOILER STANDBY - STANDBY LED DOES NOT FLASH
FUSE 1.6A - DELAYED
FAULT CODE - NOT FOR APPLIANCE
Z REDIRECT
OPERATION CH - FLUE STAT TRIPS
HEAT EXCHANGER - MAIN
OPERATION CH - FLUE STAT TRIPS
RECUPERATOR
ALTERNATIVE FLOW SWITCH TEST
CABLE - DHW FLOW SWITCH AND TEMP...
OBSERVATION PUMP RUNS
CABLE - DHW FLOW SWITCH AND TEMP...
ALTERNATIVE FLOW SWITCH TEST
FLOW SWITCH - MAGNETIC
FAULT CODE 210 - RUNNING SLOW
MOTOR - PUMP
FAULT CODE 210
DIAPHRAGM - PRESSURE SWITCH - CH
FAULT CODE 210 SPINDLE SEIZED
DIAPHRAGM - PRESSURE SWITCH - CH
OBSERVATION BURNER IGNITION - NOT ESTABLISHING
WIRE - DETECTION TO TRAP
OBSERVATION BURNER IGNITION - IGNITES BUT BAFFLES
INLET PRESSURE
OBSERVATION BURNER IGNITION - IGNITES BUT BAFFLES
HEAT EXCHANGER - MAIN
OBSERVATION BURNER IGNITION - NO SPARKING
ELECTRODE - IGNITION
OPERATION DHW - DHW RUNS HOT COLD
MOTOR - PUMP
OPERATION DHW - DHW RUNS HOT COLD DHW SENSOR
TEMPERATURE PROBE
OPERATION DHW - DHW RUNS HOT COLD PRIMARY SENSOR
TEMPERATURE PROBE
OPERATION DHW - DHW RUNS HOT COLD DROPPING OUT
MOTOR - PUMP
OPERATION DHW - DHW RUNS HOT COLD DHW SENSOR DROPPING OUT
TEMPERATURE PROBE
OPERATION DHW - DHW RUNS HOT COLD PRIMARY SENSOR DROPPING OUT
TEMPERATURE PROBE
OPERATION DHW - DHW RUNS HOT COLD DROPPING OUT
RECUPERATOR
OBSERVATION BURNER IGNITION - NOT ESTABLISHING
ELECTRODE - DETECTION
OPERATION DHW - DHW RUNS HOT COLD
SWITCH - AIR PRESSURE
OPERATION DHW - DHW RUNS HOT COLD
TUBE (AIR PRESSURE SWITCH)
OPERATION DHW - DHW RUNS HOT COLD
TEST POINT - AIR PRESSURE SWITCH
OPERATION DHW - DHW RUNS HOT COLD - CUTS OUT
HEAT EXCHANGER - MAIN
OBSERVATION BURNER IGNITION - NOT ESTABLISHING
CABLE - FLAME DETECTION ELECTRODE
OPERATION DHW - DHW RUNS HOT COLD - APS
RECUPERATOR
OPERATION DHW - DHW RUNS HOT COLD
THERMOSTAT 105DEG C - OVERHEAT
PRESSURE BURNER MAX - DHW SENSOR
TEMPERATURE PROBE
PRESSURE BURNER MAX
KNOB
PRESSURE BURNER MAXIMUM
INLET PRESSURE
INFORMATION CASE REMOVAL
Z REDIRECT
PRESSURE IGNITION
PCB - IGNITION RATE
FAULT CODE 120
DIP SWITCH SETTINGS
FAULT CODE 211
DIP SWITCH SETTINGS
OBSERVATION FAN RUNS
MOTOR - PUMP
OBSERVATION FAN RUNS
DIAPHRAGM - PRESSURE SWITCH - CH
OBSERVATION FAN RUNS SPINDLE SEIZED
DIAPHRAGM - PRESSURE SWITCH - CH
OBSERVATION FAN RUNS
KIT - MICROSWITCH
OBSERVATION FAN RUNS - PRIMARY SENSOR
TEMPERATURE PROBE
OBSERVATION FAN RUNS - DHW SENSOR
TEMPERATURE PROBE
OBSERVATION FAN RUNS
CABLE - ELECTRONIC CONTROL PCB IGNITION DEVICE
OBSERVATION BURNER IGNITION - NOT ESTABLISHING
INLET PRESSURE
OBSERVATION FAN RUNS
FUSE 3 15AF
OBSERVATION FAN RUNS
TUBE (AIR PRESSURE SWITCH)
OBSERVATION FAN RUNS
VENTURI
OBSERVATION FAN RUNS - FAN
CABLE - FAN
OBSERVATION BURNER IGNITION - IGNITES BUT BAFFLES
CABLE - CH FLOW SWITCH TEMPERATURE...
OBSERVATION BURNER IGNITION - IGNITES BUT BAFFLES
PCB - ELECTRONIC CONTROL
PRESSURE BURNER MAXIMUM
CABLE - CH FLOW SWITCH TEMPERATURE...
PRESSURE BURNER MAXIMUM
PCB - ELECTRONIC CONTROL
OPERATION DHW - DHW COOL RADS COOL
CABLE - CH FLOW SWITCH TEMPERATURE...
OPERATION DHW - DHW COOL RADS COOL OBSERVATION BURNER IGNITION - IGNITES BUT BAFFLES
PCB - ELECTRONIC CONTROL
FAULT CODE 002
CABLE - CH FLOW SWITCH TEMPERATURE...
FAULT CODE 002 - GAS VALVE VOLTAGE
PCB - ELECTRONIC CONTROL
PRESSURE BURNER MAX AND MIN
INLET PRESSURE
PRESSURE MIN
Z REDIRECT
PRESSURE BURNER MIN
ELECTRODE - IGNITION
PRESSURE BURNER MIN
BURNER
FAULT CODE 220
PCB - ELECTRONIC CONTROL
OBSERVATION BURNER IGNITION - NOT IGNITING
ELECTRODE - IGNITION
OBSERVATION BURNER IGNITION - NOT IGNITING - LOW PRESSURE
INLET PRESSURE
OBSERVATION BURNER IGNITION - NOT IGNITING - NO PRESSURE
INLET PRESSURE
OBSERVATION BURNER IGNITION - NOT IGNITING
CABLE - PUMP
OBSERVATION BOILER STANDBY - FAULT CODES 2
Z REDIRECT
OPERATION DHW - DHW TOO HOT DHW SENSOR
TEMPERATURE PROBE
OPERATION DHW - DHW TOO COOL
MOTOR - PUMP
SEQUENCE OF OPERATION
Z REDIRECT
OBSERVATION BOILER SELF CHECK - PUMP RUNS WITH NO DEMAND
OPEN TAP OR LEAK
OBSERVATION RESET CLOCK
Z REDIRECT
OBSERVATION BOILER SELF CHECK - PUMP RUNS WITH NO DEMAND
CLOCK BATTERY
OBSERVATION BOILER SELF CHECK - PUMP RUNS WITH NO DEMAND
CABLE - TIME SWITCH
OBSERVATION DHW FLOW RATE
TAP 1/2IN - DHW
OBSERVATION PUMP RUNS
CABLE - PUMP
FAULT CODE 202 DHW
OPEN TAP OR LEAK
OBSERVATION BOILER STANDBY - PUMP RUNS WITH NO DEMAND
FROST PROTECTION
FAULT CODE 202 CH
Z REDIRECT
FAULT CODE 202 CH
CLOCK BATTERY
FAULT CODE 202 CH
CABLE - TIME SWITCH
FAULT CODE 220
FROST PROTECTION
FAULT CODE 220 - PRIMARY SENSOR
TEMPERATURE PROBE
OBSERVATION BOILER STANDBY - PRIMARY SENSOR - PUMP RUNS WITH NO DEMAND
TEMPERATURE PROBE
FAULT CODE 002 - PRIMARY SENSOR - WILL NOT RESET
TEMPERATURE PROBE
FAULT CODE 002
MOTOR - PUMP
FAULT CODE 002 - DHW SENSOR - CUTS OUT
TEMPERATURE PROBE
FAULT CODE 002
INLET PRESSURE
FAULT CODE 002 - DHW SENSOR - DOES NOT MODULATE
TEMPERATURE PROBE
FAULT CODE 212
Z REDIRECT
FAULT CODE 021 - DHW SENSOR
TEMPERATURE PROBE
FAULT CODE 022 - PRIMARY SENSOR
TEMPERATURE PROBE
FAULT CODE 210
CABLE - PUMP
TYPE OF DIAGNOSTIC PROCEDURE
Z REDIRECT
FAULT CODE 210
KIT - MICROSWITCH
OBSERVATION DHW - DHW TOO COOL
RECUPERATOR
OBSERVATION DHW FLOW RATE
MAINS WATER SUPPLY / TAP
OBSERVATION DHW MODULATION - DHW SENSOR
TEMPERATURE PROBE
OBSERVATION CH MODULATION - PRIMARY SENSOR
TEMPERATURE PROBE
OBSERVATION DHW FLOW RATE
FLOW SWITCH - MAGNETIC
FUSE INVESTIGATION - LEAK
ACTUATOR AND KIT - DIVERTER VALVE
FUSE INVESTIGATION
ACTUATOR - DIVERTER VALVE
FUSE INVESTIGATION - SHORT CIRCUIT
MOTOR - PUMP
FUSE INVESTIGATION - SHORT CIRCUIT
GAS VALVE
EXCESSIVE SYSTEM PRESSURE
EXPANSION VESSEL
OPERATION DHW - TOO COOL RADS HEAT
CABLE - PUMP
FAULT CODE 002
ACTUATOR - DIVERTER VALVE
OPERATION CH RADS DO NOT HEAT
ACTUATOR - DIVERTER VALVE
FAULT CODE 002
HEAT EXCHANGER - MAIN
FAULT CODE 002
HEAT EXCHANGER - DHW
OBSERVATION BURNER IGNITION - NOT ESTABLISHING - SHORTING TO EARTH
CABLE - FLAME DETECTION ELECTRODE
OBSERVATION BURNER IGNITION - NO SPARKING
GASKET - INLET - FAN
OBSERVATION BURNER IGNITION - NO SPARKING
GASKET - FAN OUTLET
OBSERVATION PUMP RUNS
FLOW SWITCH - MAGNETIC
OBSERVATION PUMP RUNS
FLOW SWITCH - DHW
OPERATION DHW - DHW COOL
INJECTOR
OPERATION DHW - DHW COOL RADS COOL]
GAS VALVE ADJUSTMENT
OPERATION DHW - DHW COOL RADS COOL
GAS VALVE
OPERATION DHW - DHW TOO COOL
PCB - ELECTRONIC CONTROL
OBSERVATION BURNER IGNITION - NOT ESTABLISHING - IGNORING RECT VOLTAGE
PCB - FULL SEQUENCE CONTROL DEVICE
OBSERVATION BURNER IGNITION
PCB AND CABLE - PUMP TO DIVERTER VALVE TO...
OBSERVATION BURNER IGNITION - NO IGNITION
PCB - ELECTRONIC CONTROL
OBSERVATION BURNER IGNITION - NO SPARKING - WEAK SPARK
PCB - FULL SEQUENCE CONTROL DEVICE
OBSERVATION BURNER IGNITION - NO SPARKING - NO SPARK
PCB - FULL SEQUENCE CONTROL DEVICE
OBSERVATION BURNER IGNITION - NO IGNITION
RECUPERATOR
OBSERVATION BURNER IGNITION - NO IGNITION - TRIPPING EARLY
THERMOSTAT - FLUE - LIMIT
OPERATION DHW - DHW TOO HOT
PCB - ELECTRONIC CONTROL
OBSERVATION DHW MODULATION
PCB - ELECTRONIC CONTROL
OPERATION CH - RADS COOL
PCB - ELECTRONIC CONTROL
OBSERVATION CH MODULATION
PCB - ELECTRONIC CONTROL
FAULT CODE 202 DHW
PCB - ELECTRONIC CONTROL
FAULT CODE 002 - DISPLAYING AT LOW TEMP
PCB - ELECTRONIC CONTROL
FAULT CODE 002 - NOT MODULATING ON DHW SENSOR
PCB - ELECTRONIC CONTROL
FAULT CODE 210 - IGNORING PUMP PROVING SWITCH
PCB - ELECTRONIC CONTROL
FAULT CODE 210 - NO POWER TO FLOW SWITCH
PCB - ELECTRONIC CONTROL
OBSERVATION BOILER STANDBY - PUMP RUNS WITH NO DEMAND - STUCK ON DHW DEMAND
PCB - ELECTRONIC CONTROL
OBSERVATION BOILER STANDBY - PUMP RUNS WITH NO DEMAND - STUCK IN FROST PROTECTION
PCB - ELECTRONIC CONTROL
OBSERVATION PUMP RUNS - NO POWER TO FLOW SWITCH
PCB - ELECTRONIC CONTROL
OBSERVATION BOILER STANDBY - STANDBY LED DOES NOT FLASH
CABLE - POWER SUPPLY & EXT CONTROL
FURTHER INVESTIGATION
FUSE BLOWN
FUSE INVESTIGATION
PCB - FULL SEQUENCE CONTROL DEVICE
FUSE FURTHER INVESTIGATION - INTERNAL SHORT
PCB - ELECTRONIC CONTROL
FAULT CODE 021
CABLE - DHW FLOW SWITCH AND TEMP...
OPERATION DHW - NOISY
GAUGE - TEMPERATURE PRESSURE
OPERATION DHW - NOISY
SYSTEM PRESSURE
OPERATION DHW - NOISY
THERMOSTAT 105DEG C - OVERHEAT
OPERATION DHW - NOISY
HEAT EXCHANGER - DHW
FAULT CODE 122
HEAT EXCHANGER - MAIN
OPERATION DHW - FLUE STAT TRIPS
THERMOSTAT - FLUE - LIMIT
FAULT CODE - NOT FOR APPLIANCE
PCB - ELECTRONIC CONTROL
OBSERVATION BURNER IGNITION - NO IGNITION
NO FAULT FLUE OVERHEAT
OPERATION CH - FLUE STAT TRIPS
THERMOSTAT - FLUE - LIMIT
ALTERNATIVE FLOW SWITCH TEST
FLOW SWITCH - DHW
FAULT CODE 210
GAUGE - TEMPERATURE PRESSURE
FAULT CODE 210
SYSTEM PRESSURE
FAULT CODE 210
KIT - FLOW GROUP
FAULT CODE 210 SPINDLE SEIZED
KIT - FLOW GROUP
OBSERVATION BURNER IGNITION - NOT ESTABLISHING
CONDENSATE TRAP
OBSERVATION BURNER IGNITION - IGNITES BUT BAFFLES
GAS VALVE ADJUSTMENT
OBSERVATION BURNER IGNITION - NO SPARKING
CABLE - IGNITION ELECTRODE
OBSERVATION BURNER IGNITES - IGNITES BUT BAFFLES
GASKET - INLET - FAN
OBSERVATION BURNER IGNITES - IGNITES BUT BAFFLES
GASKET - FAN OUTLET
OPERATION DHW - DHW RUNS HOT COLD
GAUGE - TEMPERATURE PRESSURE
OPERATION DHW - DHW RUNS HOT / COLD
SYSTEM PRESSURE
OPERATION DHW - DHW RUNS HOT COLD - MODULATING INCORRECTLY
PCB - ELECTRONIC CONTROL
OPERATION DHW - DHW RUNS HOT COLD
HEAT EXCHANGER - DHW
OPERATION DHW - DHW RUNS HOT COLD
HEAT EXCHANGER - MAIN
OPERATION DHW - DHW RUNS HOT COLD DROPPING OUT
GAUGE - TEMPERATURE PRESSURE
OPERATION DHW - DHW RUNS HOT / COLD DROPPING OUT
SYSTEM PRESSURE
OPERATION DHW - DHW RUNS HOT COLD - CUTTING POWER TO IGN PCB
PCB - ELECTRONIC CONTROL
OPERATION DHW - DHW RUNS HOT COLD DROPPING OUT
HEAT EXCHANGER - DHW
OPERATION DHW - DHW RUNS HOT COLD DROPPING OUT
HEAT EXCHANGER - MAIN
OPERATION DHW - DHW RUNS HOT COLD
GASKET - INLET - FAN
OPERATION DHW - DHW RUNS HOT COLD
GASKET - FAN OUTLET
OPERATION DHW - DHW RUNS HOT COLD - BURNER PRESSURE OK
PCB - FULL SEQUENCE CONTROL DEVICE
PRESSURE BURNER MAXIMUM
GAS VALVE ADJUSTMENT
PRESSURE BURNER MAXIMUM - MINIMUM OUT
GAS VALVE
FAULT CODE 211
PCB - ELECTRONIC CONTROL
FAULT CODE 120
PCB - ELECTRONIC CONTROL
OBSERVATION FAN RUNS
GAUGE - TEMPERATURE PRESSURE
OBSERVATION FAN RUNS
SYSTEM PRESSURE
OBSERVATION FAN RUNS
KIT - FLOW GROUP
OBSERVATION FAN RUNS SPINDLE SEIZED
KIT - FLOW GROUP
OBSERVATION FAN RUNS - NO POWER TO FLOW SWITCH
PCB - ELECTRONIC CONTROL
OBSERVATION FAN RUNS - PUMP PROVING MICROSWITCH
CABLE - CH FLOW SWITCH TEMPERATURE...
OBSERVATION FAN RUNS - NO POWER TO IGNITION PCB
PCB - ELECTRONIC CONTROL
OBSERVATION FAN RUNS - NO POWER TO FAN
PCB - FULL SEQUENCE CONTROL DEVICE
OBSERVATION FAN RUNS - APS
CABLE - FAN
OBSERVATION FAN RUNS
SWITCH - AIR PRESSURE
PRESSURE BURNER MAXIMUM - MAX OUT RESIST
GAS VALVE
PRESSURE BURNER MAXIMUM - MAX OUT
GAS VALVE
FAULT CODE 002 - MAX OUT RESIST
GAS VALVE
FAULT CODE 002 - MAX OUT
GAS VALVE
PRESSURE BURNER MAX AND MIN
GAS VALVE ADJUSTMENT
PRESSURE BURNER MIN
INJECTOR
OBSERVATION BOILER STANDBY - FAULT CODES 1
Z REDIRECT
OPERATION DHW - DHW TOO COOL
GAUGE - TEMPERATURE PRESSURE
OPERATION DHW - DHW TOO COOL
SYSTEM PRESSURE
OPERATION DHW - DHW TOO COOL
HEAT EXCHANGER - DHW
OBSERVATION PUMP RUNS
MOTOR - PUMP
OBSERVATION BOILER STANDBY - PUMP RUNS WITH NO DEMAND
FLOW SWITCH - DHW
FAULT CODE 202 DHW
FLOW SWITCH - MAGNETIC
FAULT CODE 202 DHW
FLOW SWITCH - DHW
FAULT CODE 202 CH - WITH INTEGRAL TIMER BLANK
TIME SWITCH
FAULT CODE 202 CH - PUMP RUNS WITH NO DEMAND
TIME SWITCH
FAULT CODE 111
Z REDIRECT
FAULT CODE 002
GAS VALVE ADJUSTMENT
FAULT CODE 002 - MINIMUM OUT
GAS VALVE
FAULT CODE 002
NO FAULT FOUND
FAULT CODE 022
Z REDIRECT
FAULT CODE 021
Z REDIRECT
OBSERVATION BOILER STANDBY - PUMP RUNS WITH NO DEMAND
FLOW SWITCH - MAGNETIC
FAULT CODE 022
CABLE - CH FLOW SWITCH TEMPERATURE...
FAULT CODE 210 - NOT RUNNING
MOTOR - PUMP
FAULT CODE 210
CABLE - CH FLOW SWITCH TEMPERATURE...
OPERATION DHW - DHW TOO COOL
HEAT EXCHANGER - MAIN
OBSERVATION DHW FLOW RATE
HEAT EXCHANGER - DHW
OBSERVATION BURNER IGNITION - NOT IGNITING - LOW PRESSURE
GAS VALVE ADJUSTMENT
OBSERVATION BURNER IGNITION - NOT ESTABLISHING
GAS VALVE ADJUSTMENT
FUSE INVESTIGATION - SHORT TO DIVERTER VALVE
CABLE - PUMP
FUSE INVESTIGATION - SHORT CIRCUIT TO PUMP
CABLE - PUMP
FUSE INVESTIGATION - SHORT CIRCUIT TO FAN
CABLE - FAN
FUSE INVESTIGATION - SHORT CIRCUIT TO GAS VALVE
CABLE - PUMP
EXCESSIVE SYSTEM PRESSURE
PIPE - CONNECTION - EXPANSION VESSEL
OPERATION DHW - TOO COOL RADS HEAT
ACTUATOR - DIVERTER VALVE
OPERATION DHW - TOO COOL RADS HEAT
SERVICE KIT - DIVERTER VALVE
FAULT CODE 002
SERVICE KIT - DIVERTER VALVE
BOILER REACHES TEMPERATURE RADIATORS DO NOT HEAT SUFFICIENTLY
CHARACTERISTIC TEST FROM OPERATION CH
NO SPARKING OBSERVED
CHARACTERISTIC TEST FROM OBSERVATION SPARKING AT PCB
SPARKING PRESENT BUT WEAK OR INTERMITTENT
CHARACTERISTIC TEST FROM OBSERVATION SPARKING AT PCB
FAN INLET SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION VENTURI AND FAN SEALS
FAN OUTLET SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION VENTURI AND FAN SEALS
FAN VENTURI DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION VENTURI AND FAN SEALS
FAN CLOGGED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION VENTURI AND FAN SEALS
VOLTAGE AS ABOVE ON TEST 1 BUT WRONG ON TEST 2
CHARACTERISTIC TEST FROM VOLTAGE FLOW SWITCH AT PCB
VOLTAGE ABSENT ON TEST 1
CHARACTERISTIC TEST FROM VOLTAGE PUMP PROVING SWITCH AT PCB
PRESSURE REACHES MAXIMUM BUT THEN MODULATES DOWN
CHARACTERISTIC TEST FROM PRESSURE BURNER MAXIMUM (CONSTANT)
PRESSURE NEVER REACHES MAXIMUM
CHARACTERISTIC TEST FROM PRESSURE BURNER MAXIMUM (CONSTANT)
UNABLE TO SET MINIMUM PRESSURE CORRECTLY
CHARACTERISTIC TEST FROM ADJUSTMENT PRESSURE MAX AND MIN
MINIMUM SET CORRECTLY BUT UNABLE TO SET MAXIMUM
CHARACTERISTIC TEST FROM ADJUSTMENT PRESSURE MAX AND MIN
NO SPARKING PRESENT
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION
FLUE GAS TEMPERATURE ABOVE 100°C
CHARACTERISTIC TEST FROM TEMPERATURE FLUE
BOILER NOISY, KETTLES OR GOES TO LOCKOUT
CHARACTERISTIC TEST FROM OPERATION DHW
SYSTEM PRESSURE READS CORRECTLY BUT DOES NOT INCREASE
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SPINDLE ALREADY EXTENDED BEFORE PUMP RUNS
CHARACTERISTIC TEST FROM OBSERVATION PUMP PROVING SPINDLE
SPINDLE DOES NOT EXTEND AND FULLY ENGAGE MICROSWITCH
CHARACTERISTIC TEST FROM OBSERVATION PUMP PROVING SPINDLE
SYSTEM PRESSURE READS CORRECTLY BUT DOES NOT INCREASE
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
UNABLE TO SET MINIMUM PRESSURE CORRECTLY
CHARACTERISTIC TEST FROM ADJUSTMENT PRESSURE MAX AND MIN
MINIMUM SET CORRECTLY BUT UNABLE TO SET MAXIMUM
CHARACTERISTIC TEST FROM ADJUSTMENT PRESSURE MAX AND MIN
FAN INLET SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION VENTURI AND FAN SEALS
FAN OUTLET SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION VENTURI AND FAN SEALS
FAN VENTURI DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION VENTURI AND FAN SEALS
FAN CLOGGED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION VENTURI AND FAN SEALS
BURNER IGNITES SMOOTHLY BUT DOES NOT ESTABLISH (SPARKING CONTINUES)
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION
VOLTAGE ABSENT
CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT
SYSTEM PRESSURE READS CORRECTLY BUT DOES NOT INCREASE
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
VOLTAGE PRESENT BUT DOES NOT DROP
CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT
SYSTEM PRESSURE READS CORRECTLY BUT DOES NOT INCREASE
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
FAN INLET SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION VENTURI AND FAN SEALS
FAN OUTLET SEAL DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION VENTURI AND FAN SEALS
FAN VENTURI DAMAGED OR WORN
CHARACTERISTIC TEST FROM INSPECTION VENTURI AND FAN SEALS
FAN CLOGGED OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION VENTURI AND FAN SEALS
UNABLE TO SET MINIMUM PRESSURE CORRECTLY
CHARACTERISTIC TEST FROM ADJUSTMENT PRESSURE MAX AND MIN
MINIMUM SET CORRECTLY BUT UNABLE TO SET MAXIMUM
CHARACTERISTIC TEST FROM ADJUSTMENT PRESSURE MAX AND MIN
SPINDLE ALREADY EXTENDED BEFORE PUMP RUNS
CHARACTERISTIC TEST FROM OBSERVATION PUMP PROVING SPINDLE
SPINDLE DOES NOT EXTEND AND FULLY ENGAGE MICROSWITCH
CHARACTERISTIC TEST FROM OBSERVATION PUMP PROVING SPINDLE
SYSTEM PRESSURE READS CORRECTLY BUT DOES NOT INCREASE
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
VOLTAGE PRESENT ON TEST 1 BUT DOES NOT DROP ON TEST 2
CHARACTERISTIC TEST FROM VOLTAGE PUMP PROVING SWITCH AT PCB
VOLTAGE ABSENT ON TEST 1
CHARACTERISTIC TEST FROM VOLTAGE PUMP PROVING SWITCH AT PCB
SPARKING PRESENT BUT BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION
PRESSURE PRESENT BUT LOW
CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT
MINIMUM PRESSURE INCORRECT
CHARACTERISTIC TEST FROM PRESSURE BURNER MIN
MINIMUM PRESSURE OK BUT NOW BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM PRESSURE BURNER MIN
PRESSURE REMAINS AT 0MBAR
CHARACTERISTIC TEST FROM VOLTAGE RECTIFICATION CIRCUIT
BURNER IGNITES BUT BAFFLES AND/OR FLAME LIFTS OFF
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION
DHW COOL, RADIATORS REMAIN COLD
CHARACTERISTIC TEST FROM OPERATION DHW
DHW COOL, RADIATORS BEGIN TO HEAT
CHARACTERISTIC TEST FROM OPERATION DHW
DHW TOO HOT
CHARACTERISTIC TEST FROM OPERATION DHW
DHW RUNS HOT / COLD
CHARACTERISTIC TEST FROM OPERATION DHW
NO LEDS ILLUMINATED
CHARACTERISTIC TEST FROM OBSERVATION BOILER STANDBY
SYSTEM PRESSURE READS CORRECTLY BUT DOES NOT INCREASE
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
SYSTEM PRESSURE LOW
CHARACTERISTIC TEST FROM INSPECTION PRESSURE SYSTEM
NO EXTERNAL CONTROLS FITTED AND INTEGRAL TIMER DISPLAY IS ILLUMINATED
CHARACTERISTIC TEST FROM OBSERVATION ARE EXTERNAL CONTROLS FITTED
NO EXTERNAL CONTROLS FITTED AND INTEGRAL TIMER DISPLAY IS BLANK
CHARACTERISTIC TEST FROM OBSERVATION ARE EXTERNAL CONTROLS FITTED
PUMP DOES NOT RUN ON EITHER TEST
CHARACTERISTIC TEST FROM OBSERVATION PUMP RUNS (NO DEMAND)
PUMP RUNS ON TEST 1
CHARACTERISTIC TEST FROM OBSERVATION PUMP RUNS (NO DEMAND)
NO EXTERNAL CONTROLS FITTED AND INTEGRAL TIMER DISPLAY IS ILLUMINATED
CHARACTERISTIC TEST FROM OBSERVATION ARE EXTERNAL CONTROLS FITTED
NO EXTERNAL CONTROLS FITTED AND INTEGRAL TIMER DISPLAY IS BLANK
CHARACTERISTIC TEST FROM OBSERVATION ARE EXTERNAL CONTROLS FITTED
ADDITIONAL LIGHTS FLASHING OR ILLUMINATED / FAULT CODE SHOWING
CHARACTERISTIC TEST FROM OBSERVATION BOILER STANDBY
CH FLOW PIPE BEGINS TO HEAT
CHARACTERISTIC TEST FROM OPERATION DHW (FAULT CODE)
BURNER CUTS OUT AND/OR FAULT CODE REAPPEARS
CHARACTERISTIC TEST FROM OPERATION DHW (FAULT CODE)
UNABLE TO SET MINIMUM PRESSURE CORRECTLY
CHARACTERISTIC TEST FROM ADJUSTMENT PRESSURE MAX AND MIN
MINIMUM SET CORRECTLY BUT UNABLE TO SET MAXIMUM
CHARACTERISTIC TEST FROM ADJUSTMENT PRESSURE MAX AND MIN
PUMP RUNS WITH NO DEMAND OR BOILER FIRES WITH NO DEMAND
CHARACTERISTIC TEST FROM OBSERVATION BOILER STANDBY
VOLTAGE PRESENT ON TEST 1 BUT DOES NOT DROP ON TEST 2
CHARACTERISTIC TEST FROM VOLTAGE PUMP PROVING SWITCH AT PCB
VOLTAGE ABSENT ON TEST 1
CHARACTERISTIC TEST FROM VOLTAGE PUMP PROVING SWITCH AT PCB
BOILER AND RADIATOR TEMPERATURE LOW
CHARACTERISTIC TEST FROM OPERATION CH
EXCESSIVE SYSTEM PRESSURE RISE
CHARACTERISTIC TEST FROM OPERATION CH
25/10/2022 13:01:07 2108_1_50_1 21/11/2022 09:19:17
03/11/2022 09:00:31
VOLTAGE MAINS IN AT CONNECTOR
{GAINPCBACS}
VOLTAGE DIVERTER VALVE CH AT PCB
{GAINPCBACS}
TEMPERATURE DIFFERENTIAL CH
ATTACH TEMPERATURE P
INSPECTION RECUPERATOR HEAT EXCHANGER
BOILER PRIMARY CIRCUIT DRAINED
RESISTANCE FUSE (MAINS)
REMOVE THE FUSE FROM THE FUSED SPUR
INSPECTION CH POTENTIOMETER
{GAINPCBACS}
RESISTANCE HARNESS X1 TO EXTERNAL CONTROLS BLOCK
DISCONNECT CONNECTOR J1 FROM THE CONTROL PCB
RESISTANCE HARNESS AIR PRESSURE SWITCH
DISCONNECT CONNECTOR
RESISTANCE HARNESS FLOW SWITCH
DISCONNECT CONNECTOR FROM FLOW SWITCH
DISCONNECT CONNECTOR X6 FROM THE CONTROL PCB
RESISTANCE OVERHEAT CIRCUIT
DISCONNECT CONNECTOR J2 FROM THE IGNITION PCB
ENSURE APPLIANCE IS COOL
RESISTANCE GAS VALVE AT GAS VALVE
DISCONNECT LEAD FROM GAS VALVE
TEMPERATURE FLUE
CH TEMPERATURE CONTR
INSPECTION HARNESS CONTROL PCB TO IGNITION PCB
{GAINPCBACS}
TEMPERATURE DIFFERENTIAL CH
ATTACH TEMPERATURE P
INSPECTION RECUPERATOR HEAT EXCHANGER
BOILER PRIMARY CIRCUIT DRAINED
OBSERVATION CONFIRM PCB TYPE
{GAINPCBACS}
RESISTANCE HARNESS FLOW SWITCH
DISCONNECT CONNECTOR FROM FLOW SWITCH
DISCONNECT CONNECTOR X6 FROM THE CONTROL PCB
PRESSURE GAS INLET
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
ENSURE APPLIANCE IS COOL
TEMPERATURE DIFFERENTIAL CH
ATTACH TEMPERATURE P
INSPECTION RECUPERATOR HEAT EXCHANGER
BOILER PRIMARY CIRCUIT DRAINED
TEMPERATURE DIFFERENTIAL CH
ATTACH TEMPERATURE P
INSPECTION RECUPERATOR HEAT EXCHANGER
BOILER PRIMARY CIRCUIT DRAINED
RESISTANCE AIR PRESSURE SWITCH WITH KIT
DISCONNECT WIRES AND
RESISTANCE SENSOR DHW
DISCONNECT CONNECTOR FROM THE DHW THERMISTOR
INSPECTION DIP SWITCHES
{GAINPCBACS}
PRESSURE GAS INLET
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
ENSURE APPLIANCE IS COOL
INSPECTION DIP SWITCHES
{GAINPCBACS}
VOLTAGE CONTROL PCB DEMAND TO IGNITION PCB
{GAINPCBACS}
RESISTANCE FUSE (IGNITION PCB)
REMOVE INTERNAL FUSE FROM IGNITION PCB (BOTTOM LEFT OF PCB)
RESISTANCE AIR PRESSURE SWITCH (NORMALLY CLOSED)
DISCONNECT WIRES FROM AIR PRESSURE SWITCH
RESISTANCE HARNESS GAS VALVE MODUREG
DISCONNECT CONNECTOR J7 FROM THE CONTROL PCB
RESISTANCE HARNESS GAS VALVE MODUREG
DISCONNECT CONNECTOR J7 FROM THE CONTROL PCB
RESISTANCE HARNESS GAS VALVE MODUREG
DISCONNECT CONNECTOR J7 FROM THE CONTROL PCB
RESISTANCE HARNESS GAS VALVE MODUREG
DISCONNECT CONNECTOR J7 FROM THE CONTROL PCB
TEMPERATURE DIFFERENTIAL CH
ATTACH TEMPERATURE P
RESISTANCE HARNESS FLOW SWITCH (OPEN CIRCUIT)
DISCONNECT THE FLOW
INSPECTION HARNESS CLOCK
REMOVE CLOCK HARNESS FROM PCB
OBSERVATION ISOLATE DHW
ISOLATE COLD MAINS SUPPLY TO APPLIANCE BY TURNING THE BLUE ISOLATION VALVE 90° CLOCKWISE
OBSERVATION DISCONNECT FLOW SWITCH
LIFT THE FLOW SWITCH AWAY FROM ITS HOUSING AND MAKE SAFE
RESISTANCE HARNESS FLOW SWITCH (OPEN CIRCUIT)
DISCONNECT THE FLOW
OBSERVATION ARE EXTERNAL CONTROLS FITTED
DOES THE SYSTEM HAVE
INSPECTION HARNESS CLOCK
REMOVE CLOCK HARNESS FROM PCB
RESISTANCE SENSOR PRIMARY
DISCONNECT CONNECTOR FROM THE PRIMARY THERMISTOR
VOLTAGE FLOW SWITCH AT PCB
{GAINPCBACS}
PRESSURE GAS INLET
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
ENSURE APPLIANCE IS COOL
RESISTANCE SENSOR DHW
DISCONNECT CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE SENSOR PRIMARY AND HARNESS
DISCONNECT CONNECTOR J7 FROM THE CONTROL PCB
RESISTANCE SENSOR PRIMARY
DISCONNECT CONNECTOR FROM THE PRIMARY THERMISTOR
OBSERVATION DISCONNECT FLOW SWITCH
LIFT THE FLOW SWITCH AWAY FROM ITS HOUSING AND MAKE SAFE
RESISTANCE SENSOR DHW AND HARNESS
DISCONNECT CONNECTOR J6 FROM THE CONTROL PCB
RESISTANCE SENSOR DHW
DISCONNECT CONNECTOR FROM THE DHW THERMISTOR
OBSERVATION PUMP RUNS (FAULT CODE)
DHW TEMPERATURE SELECTOR SET TO MAX
CH TEMPERATURE SELECTOR SET TO MAX
INSPECTION RECUPERATOR HEAT EXCHANGER
BOILER PRIMARY CIRCUIT DRAINED
OBSERVATION MAINS WATER FLOW RATE
TURN COLD WATER TAP ON
INSPECTION DHW POTENTIOMETER
{GAINPCBACS}
INSPECTION CH POTENTIOMETER
{GAINPCBACS}
INSPECTION DIVERTER VALVE ACTUATOR
REMOVE DIVERTER VALV
RESISTANCE DIVERTER VALVE ACTUATOR AND HARNESS
DISCONNECT CONNECTOR J3 FROM THE CONTROL PCB
RESISTANCE DIVERTER VALVE ACTUATOR
REMOVE DIVERTER VALVE ACTUATOR AND DISCONNECT ELECTRICAL CONNECTOR
RESISTANCE PUMP
REMOVE PLUG FROM TOP OF PUMP
RESISTANCE FAN
DISCONNECT WIRES TO THE FAN
RESISTANCE GAS VALVE SOLENOIDS WITH EARTH CHECK
DISCONNECT LEAD FROM GAS VALVE
VOLTAGE DIVERTER VALVE DHW AT PCB
{GAINPCBACS}
VOLTAGE DIVERTER VALVE DHW AT PCB
{GAINPCBACS}
OBSERVATION DIVERTER VALVE MOVEMENT (CH)
REMOVE DIVERTER VALV
INSPECTION DIVERTER VALVE SPINDLE
REMOVE DIVERTER VALV
RESISTANCE HARNESS DIVERTER VALVE
DISCONNECT CONNECTOR J3 FROM THE CONTROL PCB
TEMPERATURE DIFFERENTIAL INTERNAL BYPASS
ENSURE RADIATORS ARE
RESISTANCE SENSOR PRIMARY
DISCONNECT CONNECTOR FROM THE PRIMARY THERMISTOR
OBSERVATION DISCONNECT CONDENSATE LEAD
DISCONNECT THE LEAD FROM THE CONDENSATE TRAP TO THE RECTIFICATION LEAD
OBSERVATION LINK EXTERNAL CONTROLS
{GAINPCBACS}
DISC
RESISTANCE HARNESS X1 TO EXTERNAL CONTROLS BLOCK
DISCONNECT CONNECTOR J1 FROM THE CONTROL PCB
OBSERVATION IS INTERNAL CLOCK FITTED
IS AN INTEGRAL CLOCK FITTED TO THE BOILER?
OBSERVATION DISCONNECT CLOCK
DISCONNECT CONNECTOR J4 FROM THE CONTROL PCB
INSPECTION HARNESS CLOCK
REMOVE CLOCK HARNESS FROM PCB
VOLTAGE RECTIFICATION CIRCUIT WITHOUT LEAD
{GAINPCBACS}
DISCONNECT THE FLAME SENSE LEAD FROM THE IGNITION PCB
INSPECTION RECTIFICATION ELECTRODE (SHORT)
GAIN ACCESS TO BURNER
RESISTANCE AIR PRESSURE SWITCH WITH KIT
DISCONNECT WIRES AND
OBSERVATION SPARKING WITH APS PROVEN
APS TEST KIT STILL C
INSPECTION HEAT EXCHANGER
GAIN ACCESS TO PRIMARY HEAT EXCHANGER
INSPECTION VENTURI AND FAN SEALS
REMOVE FAN FROM APPL
INSPECTION RECUPERATOR
REMOVE FAN FROM APPLIANCE
OBSERVATION PUMP RUNS WITH FLOW SWITCH MADE
UNCLIP THE FLOW SWITCH FROM ITS HOUSING AND
WEDGE IT ABOVE THE PRESSURE GAUGE AS SHOWN
PRESSURE BURNER MAXIMUM (CONSTANT)
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE OUTLET TEST POINT
DHW TEMPERATURE SELECTOR SET TO MAX
RESISTANCE SENSOR DHW
DISCONNECT CONNECTOR FROM THE DHW THERMISTOR
PRESSURE GAS INLET
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
ENSURE APPLIANCE IS COOL
ADJUSTMENT PRESSURE MAX AND MIN
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE OUTLET TEST POINT
INFORMATION FAULTY LED
TESTS CARRIED OUT HA
OBSERVATION PUMP RUNS (BOTH DEMANDS)
DHW TEMPERATURE SELECTOR SET TO MAX
CH TEMPERATURE SELECTOR SET TO MAX
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR AT TOP OF PUMP
OBSERVATION SPARKING AT PCB
REMOVE THE LOWER SPA
RESISTANCE GAS VALVE AT PCB
DISCONNECT CONNECTOR J3 FROM THE IGNITION PCB
INSPECTION HEAT EXCHANGER
GAIN ACCESS TO PRIMARY HEAT EXCHANGER
RESISTANCE OVERHEAT THERMOSTAT
GAIN ACCESS TO INNER
RESISTANCE FLUE OVERHEAT STAT
DISCONNECT WIRES FROM FLUE STAT (NOTE POSITION OF CONNECTORS)
RESISTANCE IGNITION PCB
DISCONNECT CONNECTOR J2 FROM THE CONTROL PCB
RESISTANCE SENSOR PRIMARY
DISCONNECT CONNECTOR FROM THE PRIMARY THERMISTOR
TEMPERATURE DIFFERENTIAL DHW
ATTACH TEMPERATURE P
RESISTANCE FUSE (CONTROL PCB)
REMOVE INTERNAL FUSE FROM CONTROL PCB (LEFT OF TRANSFORMER)
INSPECTION HEAT EXCHANGER
GAIN ACCESS TO PRIMARY HEAT EXCHANGER
INSPECTION RECUPERATOR
REMOVE FAN FROM APPLIANCE
INSPECTION HEAT EXCHANGER
GAIN ACCESS TO PRIMARY HEAT EXCHANGER
INSPECTION RECUPERATOR
REMOVE FAN FROM APPLIANCE
INSPECTION DHW FILTER
ISOLATE AND DRAIN DHW CIRCUIT
REMOVE GAS VALVE
REMOVE FLOW SWITCH FROM ITS HOUSING
INSPECTION PUMP PROVING DIAPHRAGM
DRAIN BOILER PRIMARY CIRCUIT
UNCLIP PUMP PROVING SWITCH
INSPECTION PUMP PROVING DIAPHRAGM
DRAIN BOILER PRIMARY CIRCUIT
UNCLIP PUMP PROVING SWITCH
INSPECTION SPARK ELECTRODES
GAIN ACCESS TO BURNER
PRESSURE BURNER MAX AND MIN
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE OUTLET TEST POINT
DHW TEMPERATURE SELECTOR SET TO MAX
INSPECTION HEAT EXCHANGER
GAIN ACCESS TO PRIMARY HEAT EXCHANGER
ADJUSTMENT PRESSURE MAX AND MIN
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE OUTLET TEST POINT
INSPECTION RECUPERATOR
REMOVE FAN FROM APPLIANCE
INSPECTION VENTURI AND FAN SEALS
REMOVE FAN FROM APPL
INSPECTION BURNER
GAIN ACCESS TO BURNER
PRESSURE IGNITION (FAULT)
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE OUTLET TEST POINT
VOLTAGE RECTIFICATION CIRCUIT
{GAINPCBACS}
RESISTANCE SENSOR DHW
DISCONNECT CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE SENSOR PRIMARY
DISCONNECT CONNECTOR FROM THE PRIMARY THERMISTOR
TEMPERATURE DIFFERENTIAL DHW
ATTACH TEMPERATURE P
INSPECTION RECTIFICATION ELECTRODE
GAIN ACCESS TO BURNER
DISCONNECT INLINE CONNECTOR TO THE RECTIFICATION ELECTRODE
RESISTANCE SENSOR DHW
DISCONNECT CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE SENSOR PRIMARY
DISCONNECT CONNECTOR FROM THE PRIMARY THERMISTOR
TEMPERATURE DIFFERENTIAL DHW
ATTACH TEMPERATURE P
RESISTANCE RECTIFICATION LEAD
DISCONNECT FLAME SEN
INSPECTION HEAT EXCHANGER
GAIN ACCESS TO PRIMARY HEAT EXCHANGER
INSPECTION VENTURI AND FAN SEALS
REMOVE FAN FROM APPL
INSPECTION RECUPERATOR
REMOVE FAN FROM APPLIANCE
INSPECTION BURNER
GAIN ACCESS TO BURNER
INSPECTION DHW POTENTIOMETER
{GAINPCBACS}
PRESSURE GAS INLET
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
ENSURE APPLIANCE IS COOL
ADJUSTMENT PRESSURE MAX AND MIN
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE OUTLET TEST POINT
OBSERVATION DISCONNECT EXTERNAL CONTROLS
{GAINPCBACS}
DISC
INSPECTION HARNESS CONTROL PCB TO IGNITION PCB
{GAINPCBACS}
VOLTAGE PUMP PROVING SWITCH AT PCB
{GAINPCBACS}
HOT WATER TAP OFF
ADJUSTMENT PRESSURE MIN FOR BURNER ESTABLISH
ATTACH PRESSURE GAUG
INSPECTION PUMP PROVING DIAPHRAGM
DRAIN BOILER PRIMARY CIRCUIT
UNCLIP PUMP PROVING SWITCH
INSPECTION PUMP PROVING DIAPHRAGM
DRAIN BOILER PRIMARY CIRCUIT
UNCLIP PUMP PROVING SWITCH
RESISTANCE SENSOR PRIMARY
DISCONNECT CONNECTOR FROM THE PRIMARY THERMISTOR
RESISTANCE PUMP PROVING MICROSWITCH AT MICROSWITCH
REMOVE THE MICROSWITCH FROM ITS HOUSING AND DISCONNECT WIRES FROM PUMP PROVING MICROSWITCH
RESISTANCE SENSOR DHW
DISCONNECT CONNECTOR FROM THE DHW THERMISTOR
VOLTAGE FAN AT FAN
REMOVE COMBUSTION CHAMBER
RESISTANCE AIR PRESSURE SWITCH AT PCB (NORMALLY CLOSED)
{GAINPCBACS}
DISCONNECT CONNECTOR J2 FROM THE IGNITION PCB
INSPECTION FAN VENTURI
REMOVE FAN FROM APPL
RESISTANCE GAS VALVE MODUREG AT PCB
DISCONNECT CONNECTOR J7 FROM THE CONTROL PCB
VOLTAGE GAS VALVE MODUREG MAXIMUM AT PCB
{GAINPCBACS}
RESISTANCE GAS VALVE MODUREG AT PCB
DISCONNECT CONNECTOR J7 FROM THE CONTROL PCB
PRESSURE IGNITION (FAULT)
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE OUTLET TEST POINT
VOLTAGE GAS VALVE MODUREG MAXIMUM AT PCB
{GAINPCBACS}
RESISTANCE GAS VALVE MODUREG AT PCB
DISCONNECT CONNECTOR J7 FROM THE CONTROL PCB
VOLTAGE GAS VALVE MODUREG MAXIMUM AT PCB
{GAINPCBACS}
INSPECTION SPARK ELECTRODES
GAIN ACCESS TO BURNER
RESISTANCE GAS VALVE MODUREG AT PCB
DISCONNECT CONNECTOR J7 FROM THE CONTROL PCB
VOLTAGE GAS VALVE MODUREG MAXIMUM AT PCB
{GAINPCBACS}
PRESSURE GAS INLET
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
ENSURE APPLIANCE IS COOL
ADJUSTMENT PRESSURE MIN
ATTACH PRESSURE GAUG
OBSERVATION ADDITIONAL FAULT MINIMUM PRESSURE
NOW THAT THE BURNER
PRESSURE GAS INLET
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
ENSURE APPLIANCE IS COOL
INSPECTION SPARK ELECTRODES
GAIN ACCESS TO BURNER
INSPECTION BURNER
GAIN ACCESS TO BURNER
PRESSURE GAS INLET
ATTACH U-GAUGE TO INLET PRESSURE TEST POINT
ENSURE APPLIANCE IS COOL
INSPECTION BURNER
GAIN ACCESS TO BURNER
ADJUSTMENT PRESSURE MIN FOR BURNER IGNITION
ATTACH PRESSURE GAUG
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
RESISTANCE HARNESS GAS VALVE
DISCONNECT CONNECTOR AT GAS VALVE
VOLTAGE FLOW SWITCH AT PCB (NO DEMAND)
{GAINPCBACS}
ENSURE NO DEMANDS
INSPECTION DHW POTENTIOMETER
{GAINPCBACS}
INSPECTION DHW POTENTIOMETER
{GAINPCBACS}
RESISTANCE SENSOR DHW
DISCONNECT CONNECTOR FROM THE DHW THERMISTOR
TEMPERATURE DIFFERENTIAL DHW
ATTACH TEMPERATURE P
OBSERVATION ISOLATE DHW
ISOLATE COLD MAINS SUPPLY TO APPLIANCE BY TURNING THE BLUE ISOLATION VALVE 90° CLOCKWISE
VOLTAGE CLOCK BATTERY
UNCLIP AND REMOVE THE BATTERY AT THE BACK OF THE TIMER
OBSERVATION DISCONNECT EXTERNAL CONTROLS LINK
{GAINPCBACS}
DISC
OBSERVATION ARE EXTERNAL CONTROLS FITTED
DOES THE SYSTEM HAVE
VOLTAGE MAINS IN AT PCB
{GAINPCBACS}
OBSERVATION DISCONNECT EXTERNAL CONTROLS
{GAINPCBACS}
DISC
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR AT TOP OF PUMP
VOLTAGE FLOW SWITCH AT PCB (NO DEMAND)
{GAINPCBACS}
ENSURE NO DEMANDS
OBSERVATION DISCONNECT EXTERNAL CONTROLS
{GAINPCBACS}
DISC
OBSERVATION DISCONNECT EXTERNAL CONTROLS LINK
{GAINPCBACS}
DISC
VOLTAGE CLOCK BATTERY
UNCLIP AND REMOVE THE BATTERY AT THE BACK OF THE TIMER
RESISTANCE SENSOR PRIMARY
DISCONNECT CONNECTOR FROM THE PRIMARY THERMISTOR
RESISTANCE SENSOR PRIMARY
DISCONNECT CONNECTOR FROM THE PRIMARY THERMISTOR
OBSERVATION BOILER RESET - EXCESSIVE TEMP ON DHW OPERATION
ENSURE BOILER IS COOL
OPERATION DHW (FAULT CODE)
SET FLOW RATE TO 10 LITRES A MINUTE
OBSERVATION DIVERTER VALVE MOVEMENT (DHW)
REMOVE DIVERTER VALV
RESISTANCE SENSOR DHW
DISCONNECT CONNECTOR FROM THE DHW THERMISTOR
TEMPERATURE DIFFERENTIAL DHW
ATTACH TEMPERATURE P
PRESSURE BURNER MAX AND MIN
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE OUTLET TEST POINT
DHW TEMPERATURE SELECTOR SET TO MAX
ADJUSTMENT PRESSURE MAX AND MIN
ATTACH PRESSURE GAUGE TO GAS VALVE PRESSURE OUTLET TEST POINT
OBSERVATION DHW MODULATION
ADJUST DHW FLOW RATE
OBSERVATION BOILER RESET - SENSOR FAULT
ENSURE BOILER IS COOL
FAULT CODES
PLEASE USE ALL THE T
OBSERVATION BOILER RESET - SENSOR FAULT
ENSURE BOILER IS COOL
RESISTANCE HARNESS PUMP
REMOVE CONNECTOR AT TOP OF PUMP
VOLTAGE PUMP PROVING SWITCH AT PCB
{GAINPCBACS}
HOT WATER TAP OFF
RESISTANCE PUMP PROVING MICROSWITCH AT MICROSWITCH
REMOVE THE MICROSWITCH FROM ITS HOUSING AND DISCONNECT WIRES FROM PUMP PROVING MICROSWITCH
RESISTANCE SENSOR DHW
DISCONNECT CONNECTOR FROM THE DHW THERMISTOR
OBSERVATION PUMP RUNS (NO DEMAND)
ENSURE NO DEMAND FOR CH OR DHW
SET THE CH TEMPERATURE CONTROL TO 'O' POSITION
INSPECTION DHW FILTER
ISOLATE AND DRAIN DHW CIRCUIT
REMOVE GAS VALVE
REMOVE FLOW SWITCH FROM ITS HOUSING
RESISTANCE SENSOR PRIMARY
DISCONNECT CONNECTOR FROM THE PRIMARY THERMISTOR
OBSERVATION DIVERTER VALVE MOVEMENT (DHW)
REMOVE DIVERTER VALV
OBSERVATION ADDITIONAL FAULT BURNER IGNITION
NOW THAT THE BURNER
OBSERVATION ADDITIONAL FAULT BURNER ESTABLISH
NOW THAT THE BURNER
RESISTANCE MAINS INTO BOILER
{GAINPCBACS}
REMOVE FUSE FROM CONTROL PCB
RESISTANCE PUMP AND HARNESS
DISCONNECT CONNECTOR J3 FROM THE CONTROL PCB
RESISTANCE FAN AND HARNESS
DISCONNECT CONNECTOR J2 FROM THE IGNITION PCB
RESISTANCE GAS VALVE SOLENOIDS AND HARNESS WITH EARTH CHECK
DISCONNECT CONNECTOR J3 FROM THE IGNITION PCB
INSPECTION CH POTENTIOMETER
{GAINPCBACS}
PRESSURE EXPANSION VESSEL
DISCHARGE PRIMARY SYSTEM WATER
RESISTANCE HARNESS DIVERTER VALVE
DISCONNECT CONNECTOR J3 FROM THE CONTROL PCB
RESISTANCE HARNESS DIVERTER VALVE
DISCONNECT CONNECTOR J3 FROM THE CONTROL PCB
System Information
- Total Tests: 697
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control