Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
IDEAL ISAR / EVO HE - GREY DIVERTER VALVE HEAD
GLOBALLY REPLACED
IDEAL ISAR / EVO HE - GREY DIVERTER VALVE HEAD
BOILER FRONT
PREHEAT SATISFACTORY
ENSURE SECONDARY HEA
CH DEMAND
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
CH DEMAND
DHW OPERATION
BOILER ON OFF SWITCH ON
BOILER DHW THERMOSTAT SET TO MAX
DHW BURNER MODULATION
SET THE DHW FLOW RATE AT THE TAP TO APPROXIMATELY 3.0 L/MIN
CH OPERATION
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
CENTRAL HEATING DEMAND
CH BURNER MODULATION
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
CH DEMAND
CHOICE FULL DIAG OR FAULT CODE
THIS MODEL CONTAI
WATER IN IMPULSE TUBE
HEADER FOR IMPULSE TUBE INVESTIGATION
HEADER FOR FUSE INVESTIGATION
INTENTIONALLY BLANK HEADER FOR FUSE INVESTIGATION
ELECTRICAL SAFETY CHECKS
ELECTRICAL SAFETY CHECKS
PREHEAT INPUT CHECK
INPUT LINK
LINK FAULT
INPUT LINK
DHW BURNER MODULATION
USER CONTROL (DISPLAY UNIT)
DHW MODULATION
DHW THERMISTOR
PUMP RUNS PREHEAT
HARNESS - BOILER WIRING
PRE HEAT
LEAD - DETECTION
L E FAULT CODE DIAGNOSIS
ELECTRODE - FLAME DETECTION
LF FAULT99PRE HEATFCDIAG
LEAD - DETECTION
LF LE FAULT CODE DIAGNOSIS
ELECTRODE - FLAME DETECTION
LF FAULT CODE
ELECTRODE - FLAME DETECTION
PREHEAT FLAME SENSEFCDIAG
BURNER
HF FAULTPRE HEATFCDIAG
LEAD - DETECTION
HF FAULTFAULT L E FAULT CODE DIAGNOSIS
ELECTRODE - FLAME DETECTION
RADS COOL CH OP
THERMISTOR - BOILER CONTROL (FLOW)
RADS COOL CH OPPREHEAT
DHW THERMISTOR
OPEN CIRCUIT FAULT L_E FC DIAG
THERMOSTAT - OVERHEAT
PRE HEAT 2
LEAD - DETECTION
FAULT L E FAULT CODE DIAGNOSIS
ELECTRODE - FLAME DETECTION
PASSING CH OPPREHEAT
TAPS
OVERHEAT 1
DHW THERMISTOR
OVERHEAT
THERMISTOR - BOILER CONTROL (RETURN)
OVERHEAT
THERMISTOR - BOILER CONTROL (FLOW)
OVERHEAT 3
DHW THERMISTOR
OVERHEAT 3
THERMISTOR - BOILER CONTROL (RETURN)
OVERHEAT 3
THERMISTOR - BOILER CONTROL (FLOW)
FAULTYLARESET
PUMP
FAULTYLARESETHA
PUMP
OVERHEAT 9
DHW THERMISTOR
OVERHEAT 9
THERMISTOR - BOILER CONTROL (RETURN)
OVERHEAT 9
THERMISTOR - BOILER CONTROL (FLOW)
POTSOHLARESET
USER CONTROL (DISPLAY UNIT)
OVERHEAT PROBLEMOHLARESETH9OH
PLATE - HEAT EXCHANGER
O/H SECTION LINK IN SUPPLY CH DEMAND
INPUT LINK
OVERHEAT OPERATIONOHLARESETHA
DHW THERMISTOR
OVERHEAT 10
THERMISTOR - BOILER CONTROL (RETURN)
OVERHEAT 10
THERMISTOR - BOILER CONTROL (FLOW)
POTSOHLARESETHA
USER CONTROL (DISPLAY UNIT)
OVERHEAT PROBLEMOHLARESETH9OHHA
PLATE - HEAT EXCHANGER
O/H SECTION LINK IN SUPPLY CH DEMAND 2
INPUT LINK
PUMP VOLTAGE
PCB - PRIMARY CONTROLS
PUMP VOLTAGE 2
PCB - PRIMARY CONTROLS
NO PREHEAT
TRAP AND SEAL
DRIED ALL WORKING
IMPULSE TUBE WATER INGRES
CH BURNER MODULATION
USER CONTROL (DISPLAY UNIT)
WATER
GAS VALVE
OVERHEAT 4
DHW THERMISTOR
OVERHEAT 4
THERMISTOR - BOILER CONTROL (RETURN)
OVERHEAT 4
THERMISTOR - BOILER CONTROL (FLOW)
OVERHEAT
SYSTEM FILL AND VENT
FAULT CODE DIAG
FAN
FAULT HE
HARNESS FAN
L9
SYSTEM FILL AND VENT
H_3 FC DIAG PUMP NOT RUNNING STARTUP
DHW THERMISTOR
PUMP RUNS (PREHEAT)
THERMISTOR - DRY FIRE
PUMP RUNS (PREHEAT)
DHW THERMISTOR
FC DIAG H_N
POLARITY REVERSAL
DHW QUIET OPERATION RADIATORS WARM
CARTRIDGE - DIVERTER VALVE
BLOCKED DHW OP
PLATE - HEAT EXCHANGER
FLASHES LA OR HA
THERMISTOR - DRY FIRE
FLASHES LA OR HA RESETS SHOWS 3 DASHES
THERMISTOR - DRY FIRE
3 DASHES IN DISPLAY
THERMISTOR - DRY FIRE
RESETS SHOWS 3 DASHES 1
THERMISTOR - DRY FIRE
FLASHES H9 OR L9
THERMISTOR - DRY FIRE
FALT CODE LF2
INSULATION - COMBUSTION CHAMBER
FAULT CODE LF
HEAT ENGINE
PREHEAT SATISFACTORY
CARTRIDGE - DIVERTER VALVE
BLOCKED PREHEAT SAT
PLATE - HEAT EXCHANGER
CH OPERATION
CARTRIDGE - DIVERTER VALVE
CH OPERATION
PUMP
NO INVESTIGATIONLA
BOILER OVERHEAT
NOT RESETLA
THERMOSTAT - OVERHEAT
FLASHES LA OR HA WILL NOT RESET
THERMISTOR - DRY FIRE
OVERHEAT 5
DHW THERMISTOR
OVERHEAT 5
THERMISTOR - BOILER CONTROL (RETURN)
OVERHEAT 5
THERMISTOR - BOILER CONTROL (FLOW)
NO INVESTIGATIONLAH9
BOILER OVERHEAT
NOT RESETLAH9
THERMOSTAT - OVERHEAT
FLASHES LA OR HA WILL NOT RESET 1
THERMISTOR - DRY FIRE
OVERHEAT 8
DHW THERMISTOR
OVERHEAT 8
THERMISTOR - BOILER CONTROL (RETURN)
OVERHEAT 8
THERMISTOR - BOILER CONTROL (FLOW)
OVERHEATLAH9
REDIRECTS
FLASHES LA OR HA RESETS SHOWS 3 DASHES 1
THERMISTOR - DRY FIRE
OVERHEAT 7
DHW THERMISTOR
OVERHEAT 7
THERMISTOR - BOILER CONTROL (RETURN)
OVERHEAT 7
THERMISTOR - BOILER CONTROL (FLOW)
OVERHEATLAH93 DASHES
REDIRECTS
SHOWS 3 DASHES
THERMISTOR - DRY FIRE
OVERHEAT 6
DHW THERMISTOR
OVERHEAT 6
THERMISTOR - BOILER CONTROL (RETURN)
OVERHEAT 6
THERMISTOR - BOILER CONTROL (FLOW)
OVERHEATLA
REDIRECTS
RESETS SHOWS 3 DASHES
THERMISTOR - DRY FIRE
OVERHEAT 2
DHW THERMISTOR
OVERHEAT 2
THERMISTOR - BOILER CONTROL (RETURN)
OVERHEAT 2
THERMISTOR - BOILER CONTROL (FLOW)
RADS TOO COOL BOILER TO TEMP
CARTRIDGE - DIVERTER VALVE
RADS COOL CH OP
PCB - PRIMARY CONTROLS
DIVERTER VOLTAGE CH OP
PCB - PRIMARY CONTROLS
RADS COOL CH OP
DHW THERMISTOR
PASSING CH OP
TAPS
H THEN F FAULT CODE
LEAD - DETECTION
H THEN F FAULT CODE
ELECTRODE - FLAME DETECTION
ON WITH NO DEMAND
THERMISTOR - BOILER CONTROL (RETURN)
PUMP RUNS (PREHEAT)
THERMISTOR - BOILER CONTROL (RETURN)
DOES NOT RECOGNISE DEMAND
DHW THERMISTOR
PUMP RUNS FOR 5 SECONDS THEN STOPS
THERMISTOR - BOILER CONTROL (FLOW)
BOILER FIRING AFTER PREHEAT WITH NO DEMAND
THERMISTOR - BOILER CONTROL (FLOW)
DHW BURNER MODULATION
THERMISTOR - BOILER CONTROL (FLOW)
DHW MODULATION
THERMISTOR - BOILER CONTROL (RETURN)
RED DASH FC DIAG
PCB/USER CONTROLS HARNESS
DOT DASH FAULT CODE
USER CONTROL (DISPLAY UNIT)
BURNER IGNITES BUT DOES NOT ESTABLISH
GAS INLET PRESSURE
BURNER ESTABLISHES PRE HEAT
LEAD - DETECTION
BURNER ESTABLISHES (PREHEAT)
ELECTRODE - FLAME DETECTION
GAP
ELECTRODE - FLAME DETECTION (GAP)
BURNER ESTABLISHES (PREHEAT)
TRAP AND SEAL
BURNER ESTABLISHES (PREHEAT)
BURNER
BURNER IGNITES BUT DOES NOT ESTABLISH
INSULATION - COMBUSTION CHAMBER
BURNER IGNITES BUT DOES NOT ESTABLISH
HEAT ENGINE
BURNER ESTABLISHES (PREHEAT)
TURRET GASKET
SPARKING PRESENT
ELECTRODE - IGNITION (GAP)
BURNER DOES NOT IGNITE
IMPULSE TUBE
BURNER DOES NOT IGNITE
INJECTOR & HOUSING
BURNER DOES NOT IGNITE
TRAP AND SEAL
BURNER DOES NOT IGNITE
BURNER
LF CODE
FLUE WAYS
FALT CODE LF
INSULATION - COMBUSTION CHAMBER
BURNER DOES NOT IGNITE
FLUE WAYS
BURNER DOES NOT IGNITE
INSULATION - COMBUSTION CHAMBER
LF FAULT CODE
ELECTRODE - IGNITION (GAP)
DOES NOT RECOGNISE DEMAND
HARNESS FAN
DAMAGED L8
HARNESS FAN
FAN DOES NOT RUN 3 L8
PCB - PRIMARY CONTROLS AND FAN
FAN DOES NOT RUN 4 L8
PCB - PRIMARY CONTROLS AND FAN
POWER FROM PCB L8
HARNESS FAN
NO FAN L8
HARNESS FAN
FAN DOES NOT RUN L8
PCB - PRIMARY CONTROLS AND FAN
FAN DOES NOT RUN 2 L8
PCB - PRIMARY CONTROLS AND FAN
FAN DOES NOT RUN L8
HARNESS FAN
DAMAGED
HARNESS FAN
FAN DOES NOT RUN 3
PCB - PRIMARY CONTROLS AND FAN
FAN DOES NOT RUN 4
PCB - PRIMARY CONTROLS AND FAN
POWER FROM PCB
HARNESS FAN
NO FAN
HARNESS FAN
FAN DOES NOT RUN
PCB - PRIMARY CONTROLS AND FAN
FAN DOES NOT RUN 2
PCB - PRIMARY CONTROLS AND FAN
FAN DOES NOT RUN
HARNESS FAN
PREHEAT SATISFACTORY
PCB - PRIMARY CONTROLS
PREHEAT SAT RADS WARM NO CH DEMAND
HARNESS - BOILER WIRING
STUCK
CARTRIDGE - DIVERTER VALVE
DHW QUIET OPERATION RADIATORS WARM
PCB - PRIMARY CONTROLS
DHW RADS WARM
HARNESS - BOILER WIRING
STUCK 2
CARTRIDGE - DIVERTER VALVE
KETTLING
SYSTEM FILL AND VENT
NOISY CH
SYSTEM FILL AND VENT
DHW OPERATION
THERMOSTAT - OVERHEAT
DHW OPERATION
THERMISTOR - BOILER CONTROL (FLOW)
DHW OPERATION
THERMISTOR - BOILER CONTROL (RETURN)
DHW OPERATION
THERMISTOR - DRY FIRE
OUT OF CALIBRATION 2
DHW THERMISTOR
RESTRICTED OR BLOCKED
TRAP AND SEAL
RUNNING SLOW / WEAK
PUMP
FAULT LF BURNER DOES NOT IGNITE
IMPULSE TUBE
FAULT FURTHER INVESTIGATION LF BURNER DOES NOT IGNITE
THERMOSTAT - OVERHEAT
FAULT LF BURNER DOES NOT IGNITE
GAS VALVE
OVERHEAT NOT GONE BURNER DOES NOT IGNITE
PCB - PRIMARY CONTROLS
RESTRICTED OR BLOCKED BURNER DOES NOT IGNITE
TRAP AND SEAL
BURNER DOES NOT IGNITE 2
INJECTOR & HOUSING
FAULT LF
IMPULSE TUBE
FAULT FURTHER INVESTIGATION LF
THERMOSTAT - OVERHEAT
FAULT LF
GAS VALVE
OVERHEAT NOT GONE
PCB - PRIMARY CONTROLS
RESTRICTED OR BLOCKED 3
TRAP AND SEAL
NO GAS DROP
INJECTOR & HOUSING
RESTRICTED OR BLOCKED 2
TRAP AND SEAL
LOW 2
GAS INLET PRESSURE
RESTRICTED OR BLOCKED
IMPULSE TUBE
LEAKING CAUSING BAFFLING ETC
TURRET GASKET
DAMAGED OR BLOCKED
BURNER
COLLAPSED IN AFFECTING COMBUSTION
INSULATION - COMBUSTION CHAMBER
RESTRICTED OR BLOCKED
FLUE WAYS
RESTRICTED OR BLOCKED 2
INJECTOR & HOUSING
RADS COOL CH OP 2
THERMISTOR - BOILER CONTROL (FLOW)
SHUTS DOWN PREMATURELY 2
CARTRIDGE - DIVERTER VALVE
CH OPERATION 2
PUMP
PREMATURE SHUTDOWN
USER CONTROL (DISPLAY UNIT)
CH OPERATION
TURRET GASKET
RESTRICTED OR BLOCKED 8
TRAP AND SEAL
RADS TOO COOL BOILER TO TEMP SHUTS DOWN PREMATURELY
CARTRIDGE - DIVERTER VALVE
RADS COOL CH OP SHUTS DOWN PREMATURELY
PCB - PRIMARY CONTROLS
DIVERTER VOLTAGE CH OP SHUTS DOWN PREMATURELY
PCB - PRIMARY CONTROLS
RADS COOL CH OP SHUTS DOWN PREMATURELY
DHW THERMISTOR
MAINS FUSE INVESTIGATION
REDIRECTS
CONNECTOR FAULT POWER UP
MAINS CONNECTOR
POWER UP
FUSE MAIN PCB F1
POWER UP
MAINS SWITCH C/W HARNESS
BLANK DISPLAY
PCB - PRIMARY CONTROLS AND FAN
NO DISPLAY
PCB - PRIMARY CONTROLS AND FAN
BLANK DISPLAY
PCB/USER CONTROLS HARNESS
FUSE BLOWN 3
HARNESS - BOILER WIRING
FUSE BLOW
GAS VALVE
ELECTRICAL SHORT
DIVERTER VALVE HEAD
FUSE BLOWN 4
HARNESS - BOILER WIRING
DASH DOT
HOUSING - USER CONTROL
NOISY
SYSTEM FILL AND VENT
H_4 FC DIAG 2
THERMISTOR - DRY FIRE
FAULT H4
PCB - PRIMARY CONTROLS
FC DIAG H_4 NOT FILLED AND VENTED
SYSTEM FILL AND VENT
IGNITION BURNER IGNITES PREHEAT NO SPARKING 2
ELECTRODE - IGNITION
IGNITION BURNER IGNITES PREHEAT NO SPARK
ELECTRODE - IGNITION
SPARK GEN BURNER IGNITES PREHEAT 2
PCB - PRIMARY CONTROLS & HARNESS BOILER
SPARK GEN BURNER IGNITES PREHEAT 3
PCB - PRIMARY CONTROLS & HARNESS BOILER
IGNITION BURNER IGNITES PREHEAT NO SPARKING 4
ELECTRODE - IGNITION
IGNITION BURNER IGNITES PREHEAT NO SPARK 3
ELECTRODE - IGNITION
BURNER IGNITES PREHEAT NO SPARK2
HARNESS - BOILER WIRING
BURNER IGNITES PREHEAT NO SPARK2
GAS VALVE
BURNER IGNITES PREHEAT NO SPARK
GAS VALVE
BURNER IGNITES PREHEAT NO SPARK
HARNESS - BOILER WIRING
DHW OPERATION POOR TEMP RISE
THERMISTOR - BOILER CONTROL (FLOW)
DHW OPERATION POOR TEMP RISE
THERMISTOR - BOILER CONTROL (RETURN)
DHW OPERATION POOR TEMP RISE
THERMISTOR - DRY FIRE
OUT OF CALIBRATION 3
DHW THERMISTOR
POOR DHW
USER CONTROL (DISPLAY UNIT)
LOW
GAS INLET PRESSURE
PASSING MIXER TAP
PLUMBING ISSUE
RESTRICTED OR BLOCKED
INJECTOR & HOUSING
RESTRICTED OR BLOCKED - POOR DHW
TRAP AND SEAL
RESTRICTED POOR DHW
BURNER
FAN DOES NOT RUN
THERMISTOR - BOILER CONTROL (FLOW)
FAN DOES NOT RUN
THERMISTOR - BOILER CONTROL (RETURN)
FAN DOES NOT RUN 2
THERMISTOR - BOILER CONTROL (FLOW)
FAN DOES NOT RUN 2
THERMISTOR - BOILER CONTROL (RETURN)
DHW NOISY
HEAT ENGINE
DHW OPERATION
PUMP
PREHEAT SATISFACTORY
TRAP AND SEAL
DHW FLOW RATE
FLOW RESTRICTOR
H_3 FC DIAG
DHW THERMISTOR
H_2 FC DIAG
THERMISTOR - BOILER CONTROL (RETURN)
H_1 FC DIAG
THERMISTOR - BOILER CONTROL (FLOW)
PRE HEAT IGNITES BUT DOES NOT ESTABLISH
GAS INLET PRESSURE
FAULT CODE L-F
IMPULSE TUBE
FAULT CODE L_F
INJECTOR & HOUSING
FAULT CODE L_F
TRAP AND SEAL
FAULT CODE LF
BURNER
INCORRECT POSITION
JUMPER SETTINGS
FROM PCB
HARNESS - BOILER WIRING
PREHEAT SATISFACTORY
HEAT ENGINE
CH INPUT
MULTI FAULT PCB
EXTERNAL CONTROL
HARNESS - BOILER WIRING
EXTERNAL CONTROL
MULTI FAULT HARNESS EXTERNAL CONTROL PCB
DHW BURNER MODULATION
PCB - PRIMARY CONTROLS
PUMP RUNS THEN STOPS
PCB - PRIMARY CONTROLS
PRE HEAT STUCK CH OPPREHEAT
PCB - PRIMARY CONTROLS
DHW OVERHEAT
HARNESS - BOILER WIRING
OVERHEAT SECTION RETURN
HARNESS - BOILER WIRING
OVERHEAT SECTION FLOW 1
HARNESS - BOILER WIRING
DHW OVERHEAT 3
HARNESS - BOILER WIRING
OVERHEAT SECTION RETURN 3
HARNESS - BOILER WIRING
OVERHEAT SECTION FLOW 3
HARNESS - BOILER WIRING
DHW OVERHEAT SECTION OH LA RESET
HARNESS - BOILER WIRING
OVERHEAT SECTION RETURN 9
HARNESS - BOILER WIRING
OVERHEAT SECTION FLOW 9
HARNESS - BOILER WIRING
RUN OKOH
BOILER OVERHEAT
OH SECTIONOHLARESETH9OH
MULTI FAULT PCB
FAULTYOHLARESETH9OH
MULTI FAULT HARNESS EXTERNAL CONTROL PCB
DHW OVERHEAT SECTION OH LA RESET HA
HARNESS - BOILER WIRING
OVERHEAT SECTION RETURN 10
HARNESS - BOILER WIRING
OVERHEAT SECTION FLOW 10
HARNESS - BOILER WIRING
RUN OKOHHA
BOILER OVERHEAT
OH SECTIONOHLARESETH9OHHA
MULTI FAULT PCB
FAULTYOHLARESETH9OHHA
MULTI FAULT HARNESS EXTERNAL CONTROL PCB
OVERHEAT TEMP
PCB - PRIMARY CONTROLS
OVERHEAT TEMP 2
PCB - PRIMARY CONTROLS
FAN HUNTS
PCB - PRIMARY CONTROLS
FAULT H1
PCB - PRIMARY CONTROLS
FAULT H2
PCB - PRIMARY CONTROLS
FAULT HF
PCB - PRIMARY CONTROLS
FAULT LE
PCB - PRIMARY CONTROLS
CH BURNER MODULATION
PCB - PRIMARY CONTROLS
IMPULSE TUBE
WATER LEAK
IMPULSE TUBE
WATER LEAK AND GAS VALVE
OVERHEAT TEMP 23 DASHES
PCB - PRIMARY CONTROLS
DHW OVERHEAT 4
HARNESS - BOILER WIRING
OVERHEAT SECTION RETURN 4
HARNESS - BOILER WIRING
OVERHEAT SECTION FLOW 4
HARNESS - BOILER WIRING
CH DEMAND
PCB - PRIMARY CONTROLS
NOISY 2
HEAT ENGINE
NOISY
HEAT ENGINE
FAULT HE
PCB - PRIMARY CONTROLS
PUMP RUNS (PREHEAT)
PUMP
PUMP NOT RUNNING ON PREHEAT
PCB - PRIMARY CONTROLS
DHW FC DIAG PUMP NOT RUNNING STARTUP
HARNESS - BOILER WIRING
FAULT CODE H THEN N
PCB - PRIMARY CONTROLS
LETBY DHW OPERATION
CARTRIDGE - DIVERTER VALVE
DHW QUIET OPERTAION RADIATORS WARM
DIVERTER VALVE HEAD
FLASHES LA OR HA
HARNESS - BOILER WIRING
FLASHES LA OR HA RESETS SHOWS 3 DASHES
HARNESS - BOILER WIRING
3 DASHES 1
HARNESS - BOILER WIRING
RESETS SHOWS 3 DASHES 1
HARNESS - BOILER WIRING
FLASHES H9 OR L9
HARNESS - BOILER WIRING
HB OR LB FAULT CODE
USER CONTROLS
FAULT LF
PCB - PRIMARY CONTROLS
LETBY PREHEAT
CARTRIDGE - DIVERTER VALVE
STICKING RADS WARM NO CH DEMAND
DIVERTER VALVE HEAD
STICKING DHW QUIET RADS WARM
DIVERTER VALVE HEAD
RADS WARM NO DEMAND
DIVERTER VALVE HEAD
INVESTIGATIONLA
REDIRECTS
OVERHEATLA
HARNESS - BOILER WIRING
OVERHEAT TEMPOVERHEAT 2
PCB - PRIMARY CONTROLS
FLASHES LA OR HA WILL NOT RESET
HARNESS - BOILER WIRING
DHW OVERHEAT 5
HARNESS - BOILER WIRING
OVERHEAT SECTION RETURN 5
HARNESS - BOILER WIRING
OVERHEAT SECTION FLOW 5
HARNESS - BOILER WIRING
INVESTIGATIONLAH9
REDIRECTS
OVERHEATLAH9
HARNESS - BOILER WIRING
OVERHEAT TEMPOVERHEAT 4
PCB - PRIMARY CONTROLS
FLASHES LA OR HA WILL NOT RESET 1
HARNESS - BOILER WIRING
DHW OVERHEAT 8
HARNESS - BOILER WIRING
OVERHEAT SECTION RETURN 8
HARNESS - BOILER WIRING
OVERHEAT SECTION FLOW 8
HARNESS - BOILER WIRING
OVERHEATLAH9
BOILER OVERHEAT
OVERHEAT TEMPOVERHEAT 3
PCB - PRIMARY CONTROLS
RESETS SHOWS 3 DASHES
HARNESS - BOILER WIRING
DHW OVERHEAT 7
HARNESS - BOILER WIRING
OVERHEAT SECTION RETURN 7
HARNESS - BOILER WIRING
OVERHEAT SECTION FLOW 7
HARNESS - BOILER WIRING
OVERHEATLAH93 DASHES
BOILER OVERHEAT
OVERHEAT TEMPOVERHEAT 2 OVERHEAT 4
PCB - PRIMARY CONTROLS
3 DASHES
HARNESS - BOILER WIRING
DHW OVERHEAT 6
HARNESS - BOILER WIRING
OVERHEAT SECTION RETURN 6
HARNESS - BOILER WIRING
OVERHEAT SECTION FLOW 6
HARNESS - BOILER WIRING
OVERHEATLA
BOILER OVERHEAT
OVERHEAT TEMP OVERHEAT
PCB - PRIMARY CONTROLS
FLASHES LA OR HA RESETS SHOWS 3 DASHES 1
HARNESS - BOILER WIRING
DHW OVERHEAT 2
HARNESS - BOILER WIRING
OVERHEAT SECTION RETURN 2
HARNESS - BOILER WIRING
OVERHEAT SECTION FLOW 2
HARNESS - BOILER WIRING
DOES NOT RECOGNISE DEMAND
HARNESS - BOILER WIRING
CH OPERATION
DIVERTER VALVE HEAD
PRE HEAT STUCK CH OP
PCB - PRIMARY CONTROLS
H THEN F FAULT CODE
PCB - PRIMARY CONTROLS
ON WITH NO DEMAND
PCB - PRIMARY CONTROLS
RED DASH
PCB - PRIMARY CONTROLS
BURNER IGNITES BUT DOES NOT ESTABLISH
PCB - PRIMARY CONTROLS
PRESSURE DROPS AWAY
GAS INLET PRESSURE
INCORRECT MIX 1
GAS VALVE
WRONG MIX 1
GAS VALVE
FAN DOESNT RUN L8
PCB - PRIMARY CONTROLS
FAN NOT RUN L8
PCB - PRIMARY CONTROLS
FAN DOES NOT RUN BLUE PCB L8
PCB - PRIMARY CONTROLS
FAN DOES NOT RUN BLUE PCB FITTED L8
PCB - PRIMARY CONTROLS
FAN DOESNT RUN
PCB - PRIMARY CONTROLS
FAN DOES NOT RUN BLUE PCB
PCB - PRIMARY CONTROLS
PREHEAT SATISFACTORY
DIVERTER VALVE HEAD
DHW OPERATION
DIVERTER VALVE HEAD
BOILER CYCLING
PCB - PRIMARY CONTROLS
RESTRICTED OR BLOCKED
PLATE - HEAT EXCHANGER
RESTRICTED OR BLOCKED
HEAT ENGINE
FAULT CODE L-F BURNER DOES NOT IGNITE
THERMOSTAT - OVERHEAT
FAULT CODE LF BURNER DOES NOT IGNITE
HARNESS - BOILER WIRING
MECHANICAL BURNER DOES NOT IGNITE
GAS VALVE
FAULT CODE L-F
THERMOSTAT - OVERHEAT
FAULT CODE LF
HARNESS - BOILER WIRING
MECHANICAL
GAS VALVE
WRONG MIX 2
GAS VALVE
PREMATURE SHUTDOWN OR BOILER DOESNT FIRE
PCB - PRIMARY CONTROLS
CH OPERATION SHUTS DOWN PREMATURELY
DIVERTER VALVE HEAD
PRE HEAT STUCK CH OP SHUTS DOWN PREMATURELY
PCB - PRIMARY CONTROLS
POWER UP
FUSE MAINS
MAINS CONNECTOR PCB POWER UP
HARNESS - BOILER WIRING
PCB FUSE INVESTIGATION
REDIRECTS
BLANK DISPLAY
HARNESS - BOILER WIRING
NO DISPLAY
USER CONTROL (DISPLAY UNIT)
NO DISPLAY
PCB - PRIMARY CONTROLS
BLANK DISPLAY BLUE PCB FITTED
USER CONTROL (DISPLAY UNIT)
BLANK DISPLAY
PCB - PRIMARY CONTROLS
BLOWING FUSES
PUMP
FUSE BLOWN
HARNESS FAN
FUSE BLOWN 2
HARNESS - BOILER WIRING
FUSE BLOWN
HARNESS - BOILER WIRING
PCB - FUSE BLOWN
PCB - PRIMARY CONTROLS (FUSE)
FUSE BLOWN
SPARK GENERATOR
BLANK DISPLAY
HOUSING - USER CONTROL
FLUE FC DIAG 2
HARNESS - BOILER WIRING
FAULT CODE H4
FAULT CODE RESET - RETEST APPLIANCE
BLANK DISPLAY
PCB AND FAN HARNESS
BLANK DISPLAY 2
PCB AND FAN HARNESS
NO SPARKING 2
PCB - PRIMARY CONTROLS & SPARK GENERATOR
BURNER IGNITES PREHEAT NO SPARK 2
SPARK GENERATOR
BURNER IGNITES PREHEAT NO SPARK 2
LEAD - IGNITION
BURNER IGNITES PREHEAT NO SPARK
SPARK GENERATOR
BURNER IGNITES PREHEAT NO SPARK
LEAD - IGNITION
NO SPARKING 3
PCB - PRIMARY CONTROLS & SPARK GENERATOR
BURNER IGNITES PREHEAT NO SPARK 3
SPARK GENERATOR
BURNER IGNITES PREHEAT NO SPARK 3
LEAD - IGNITION
BURNER IGNITES PREHEAT NO SPARK4
SPARK GENERATOR
BURNER IGNITES PREHEAT NO SPARK 4
LEAD - IGNITION
NO SPARKING 4
PCB - PRIMARY CONTROLS & SPARK GENERATOR
FAN RUNS NO SPARK
HARNESS - BOILER WIRING
NO SPARKING
PCB - PRIMARY CONTROLS & SPARK GENERATOR
FAN RUNS NO SPARK 2
HARNESS - BOILER WIRING
FAULT H3
DHW SENSOR - PCB
DHW NOT RECOGNISED
DHW SENSOR - PCB
RESTRICTED OR BLOCKED POOR TEMP RISE
PLATE - HEAT EXCHANGER
RESTRICTED OR BLOCKED POOR TEMP RISE
HEAT ENGINE
BOILER CYCLING POOR TEMP RISE
PCB - PRIMARY CONTROLS
FAN NOT RUN
PCB - PRIMARY CONTROLS
FAN DOES NOT RUN BLUE PCB FITTED
PCB - PRIMARY CONTROLS
DHW NOISY
PLATE - HEAT EXCHANGER
CH OPERATION
EXPANSION VESSEL
PREHEAT SATISFACTORY
PLATE - HEAT EXCHANGER
DHW FLOW RATE
PLATE - HEAT EXCHANGER
DHW FC DIAG
HARNESS - BOILER WIRING
RETURN FC DIAG
HARNESS - BOILER WIRING
FLOW FC DIAG
HARNESS - BOILER WIRING
PREHEATFCDIAG
GAS INLET PRESSURE
FLASHES H THEN 5
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
BOILER DOES NOT REACT TO CH DEMAND
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
BOILER KETTLES
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
FLASHES H9 OR L9
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
1 DASH AND/OR DOT
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
PREHEAT DOES NOT SWITCH OFF OR COMES ON TOO FREQUENTLY, RADS REMAIN COOL
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
WILL NOT RESET
CHARACTERISTIC TEST FROM CAN BOILER BE RESET
RESETS _SHOWS THREE DASHES
CHARACTERISTIC TEST FROM CAN BOILER BE RESET
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
WILL NOT RESET
CHARACTERISTIC TEST FROM CAN BOILER BE RESET
RESETS _SHOWS THREE DASHES
CHARACTERISTIC TEST FROM CAN BOILER BE RESET
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
SYSTEM KETTLES (O/H)
CHARACTERISTIC TEST FROM CH OPERATION (HEX PROVING)
SYSTEM DOES NOT REACT TO CH DEMAND
CHARACTERISTIC TEST FROM CH OPERATION (HEX PROVING)
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
SYSTEM KETTLES (O/H)
CHARACTERISTIC TEST FROM CH OPERATION (HEX PROVING)
SYSTEM DOES NOT REACT TO CH DEMAND
CHARACTERISTIC TEST FROM CH OPERATION (HEX PROVING)
3 DASHES
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
PUMP DOES NOT RUN
CHARACTERISTIC TEST FROM PUMP RUNS (PREHEAT)
PUMP RUNS FOR APPROXIMATELY 5 SECONDS THEN STOPS
CHARACTERISTIC TEST FROM PUMP RUNS (PREHEAT)
LEVER CYCLES IN AND OUT CONTINUOUSLY
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
DIVERTER VALVE NOT IN CORRECT POSITION
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
HB OR LB (B WILL BE IN LOWER CASE)
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
PREHEAT SATISFACTORY - BOILER FIRES WITH NO DEMAND DISPLAY SHOWS C
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
DIVERTER VALVE NOT IN CORRECT POSITION
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
DIVERTER VALVE STICKING
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
DIVERTER VALVE STICKING
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
LEVER CYCLES IN AND OUT CONTINUOUSLY
CHARACTERISTIC TEST FROM DIVERTER VALVE DHW POSITION
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLOW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
RETURN THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DHW THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
DRY FIRE THERMISTOR RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE CONTROL THERMISTORS AND HARNESS
FLASHES H THEN F
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
BURNER IGNITES BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM BURNER IGNITES (PREHEAT)
RADIATORS HEAT UP DURING PREHEAT FUNCTION WITH NO CH DEMAND
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM BURNER IGNITES (PREHEAT)
BOILER KETTLING
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
GAS FLOW PRESSURE DROPS AWAY
CHARACTERISTIC TEST FROM CH OPERATION (HEX PROVING)
GAS FLOW DIPS BUT STILL NO IGNITION
CHARACTERISTIC TEST FROM CH OPERATION (HEX PROVING)
DHW NOISY
CHARACTERISTIC TEST FROM DHW OPERATION
DHW TEMPERATURE RISE INSUFFICIENT, RADS BEGIN TO HEAT
CHARACTERISTIC TEST FROM DHW OPERATION
BOILER CYCLING
CHARACTERISTIC TEST FROM DHW OPERATION
DHW TEMPERATURE RISE INSUFFICIENT, RADS REMAIN COLD
CHARACTERISTIC TEST FROM DHW OPERATION
CH NOISY OPERATION
CHARACTERISTIC TEST FROM CH OPERATION
BOILER FIRES FOR CH AND REACHES TEMPERATURE BUT RADIATORS REMAIN COOL
CHARACTERISTIC TEST FROM CH OPERATION
BOILER SHUTS DOWN PREMATURELY OR DOES NOT FIRE FOR CH
CHARACTERISTIC TEST FROM CH OPERATION
EXCESSIVE SYSTEM PRESSURE
CHARACTERISTIC TEST FROM CH OPERATION
FLASHES L THEN E
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES LA OR HA
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES L THEN 8
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN 1
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN 2
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN 3
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN 4
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES L THEN F. OR H THEN F. (NOTE THE DOT AFTER THE F)
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
FLASHES H THEN N
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
NOISE WHEN MODULATING DOWN OR COMBUSTION NOISE DURING OPERATION
CHARACTERISTIC TEST FROM PREHEAT SATISFACTORY
FLASHES H THEN E
CHARACTERISTIC TEST FROM WHAT FAULT CODE IS SHOWN (PASS=L/F)
GAS FLOW PRESSURE DROPS AWAY
CHARACTERISTIC TEST FROM GAS FLOW
GAS FLOW DIPS BUT STILL NO IGNITION
CHARACTERISTIC TEST FROM GAS FLOW
FAN DOES NOT RUN
CHARACTERISTIC TEST FROM FAN RUNS (PREHEAT)
FAN HUNTS RUNS SLOWS RUNS SLOWS
CHARACTERISTIC TEST FROM FAN RUNS (PREHEAT)
29/07/2019 14:40:09 1907_0_50_1 08/08/2019 10:53:08
05/08/2019 14:16:57
PUMP VOLTAGE AT PCB
BOILER MAINS SWITCH
EXTERNAL CONTROLS CALLING
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
PUMP VOLTAGE
BOILER MAINS SWITCH ON
ENSURE SECONDARY HEAT EXCHANGER IS COOL AND THERE IS A DEMAND FOR PREHEAT
PUMP VOLTAGE
BOILER MAINS SWITCH ON
ENSURE SECONDARY HEAT EXCHANGER IS COOL AND THERE IS A DEMAND FOR PREHEAT
EXTERNAL CONTROLS CALLING
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
EXTERNAL CONTROLS CALLING
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
POTENTIOMETER RESISTANCE (CH)
DISCONNECT AND REMOVE THE USER CONTROL (DISPLAY UNIT)
REMOVE THE FRONT COVER
REMOVE WATER FROM IMPULSE TUBE DOES BOILER NOW LIGHT
REMOVE WATER INGRESS FROM IMPULSE TUBE
FIT IMPULSE TUBE BACK TO GAS VALVE AND COMBUSTION CHAMBER
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
EXTERNAL CONTROLS VOLTAGE OUT PCB
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
EXTERNAL CONTROLS CALLING
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
RESISTANCE CONTROL THERMISTOR DHW AND HARNESS
REMOVE PLUG FROM PCB
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE OVERHEAT AT PCB
REMOVE THE DIVERTER VALVE CONNECTOR FROM THE PCB
(SITUATED ON THE TOP OF THE PCB)
RESISTANCE OVERHEAT
REMOVE ONE OR BOTH
RESISTANCE OVERHEAT AT PCB
REMOVE THE DIVERTER VALVE CONNECTOR FROM THE PCB
(SITUATED ON THE TOP OF THE PCB)
RESISTANCE OVERHEAT
REMOVE ONE OR BOTH
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
RESISTANCE CONTROL THERMISTOR DHW AND HARNESS
REMOVE PLUG FROM PCB
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER
DIVERTER VALVE VOLTAGE (DHW CH OP)
BOILER MAINS SWITCH ON
CH DEMAND
FAN VOLTAGE PERMANENT HALL SENSOR
NO DEMANDS FOR CH OR
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
FAN VOLTAGE PERMANENT HALL SENSOR
NO DEMANDS FOR CH OR
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
TEMPERATURE DIFFERENTIAL CH
ATTACH TEMPERATURE C
GAS VALVE RESISTANCE
DISCONNECT LEADS FROM GAS VALVE
GAS VALVE RESISTANCE
DISCONNECT LEADS FROM GAS VALVE
DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER
DIVERTER VALVE VOLTAGE (DHW CH OP)
BOILER MAINS SWITCH ON
CH DEMAND
FUSE RESISTANCE FUSED SPUR
REMOVE FUSE FROM FUSED SPUR
RESISTANCE ON/OFF SWITCH
DISCONNECT THE ON/OFF SWITCH AT THE INLINE CONNECTOR
(AS HIGHLIGHTED OPPOSITE)
VOLTAGE AT MAIN PCB
LOWER MAIN PCB
DISCONNECT DISPLAY HARNESS FROM THE MAIN PCB
RESISTANCE FAN AND HARNESS
REMOVE FAN CONNECTOR FROM THE PCB
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE FAN AND HARNESS
REMOVE FAN CONNECTOR FROM THE PCB
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE PUMP AND HARNESS
REMOVE THE PUMP CONNECTOR FROM THE PCB
RESISTANCE HARNESS PUMP
REMOVE THE CONNECTOR FROM THE PUMP ASSEMBLY
REMOVE THE PUMP CONNECTOR FROM THE PCB
FAN RESISTANCE
DISCONNECT THE HARNESS FROM FAN
GAS VALVE RESISTANCE
DISCONNECT LEADS FROM GAS VALVE
DIVERTER VALVE RESISTANCE
DISCONNECT THE HARNE
HARNESS CONTINUITY PCB TO SPARK GEN
UNPLUG THE CONNECTOR FROM THE PCB
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
VOLTAGE AT SPARK GENERATOR
USE INSULATION MAT AS REQUIRED
HARNESS CONTINUITY PCB TO SPARK GEN
UNPLUG THE CONNECTOR FROM THE PCB
ELECTRODE CONTINUITY AND CONDITION
UNPLUG ELECTRODE FROM HT LEAD
ELECTRODE CONTINUITY AND CONDITION
UNPLUG ELECTRODE FROM HT LEAD
RESISTANCE GAS VALVE AND HARNESS - BLUE
REMOVE THE 12 WAY CONNECTOR FROM THE FRONT OF THE PCB
GAS VALVE RESISTANCE - BLUE
DISCONNECT LEADS FROM GAS VALVE
VOLTAGE AT SPARK GENERATOR
USE INSULATION MAT AS REQUIRED
HARNESS CONTINUITY PCB TO SPARK GEN
UNPLUG THE CONNECTOR FROM THE PCB
ELECTRODE CONTINUITY AND CONDITION
UNPLUG ELECTRODE FROM HT LEAD
RESISTANCE GAS VALVE AND HARNESS - BLUE
REMOVE THE 12 WAY CONNECTOR FROM THE FRONT OF THE PCB
GAS VALVE RESISTANCE - BLUE
DISCONNECT LEADS FROM GAS VALVE
ELECTRODE CONTINUITY AND CONDITION
UNPLUG ELECTRODE FROM HT LEAD
TEMPERATURE DIFFERENTIAL CH
ATTACH TEMPERATURE C
FLOW REGULATOR/FILTER
WATER OFF
DRAIN OFF EXCESS WATER THROUGH HOT TAP
WHAT FAULT CODE IS SHOWN
THE FAULT CODES ARE
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
INSULATION PADS
REMOVE FAN AND BURNER
EXTERNAL CONTROLS VOLTAGE OUT PCB
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
POTENTIOMETER RESISTANCE (DHW)
DISCONNECT AND REMOVE THE USER CONTROL (DISPLAY UNIT)
REMOVE THE FRONT COVER
FLAME SENSE LEAD CONTINUITY
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
UNPLUG CONNECTION FROM PCB
FLAME SENSE ELECTRODE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
FLAME SENSE LEAD CONTINUITY
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
UNPLUG CONNECTION FROM PCB
FLAME SENSE ELECTRODE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
FLAME DETECTION ELECTRODE GAP
REMOVE FAN AND BURNER FROM TOP OF HEAT EXCHANGER
BURNER CONDITION
REMOVE FAN
REMOVE THE BURNER
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
INSULATION PADS
REMOVE FAN AND BURNER
FLAME SENSE LEAD CONTINUITY
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
UNPLUG CONNECTION FROM PCB
FLAME SENSE ELECTRODE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
RESISTANCE HARNESS USER CONTROL
REMOVE HARNESS FROM PCB AND USER CONTROL
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
DIVERTER VALVE POSITION (CH)
BOILER MAINS SWITCH
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE OVERHEAT
REMOVE ONE OR BOTH
FLAME SENSE LEAD CONTINUITY
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
UNPLUG CONNECTION FROM PCB
FLAME SENSE ELECTRODE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
DHW INLET VALVE
TURN OFF DHW INLET ISOLATION VALVE
CAN BOILER BE RESET
PRESS THE RESET BUTTON IN THE MIDDLE OF THE USER DISPLAY
COOL DOWN HEAT EXCHANGER AND RESET APPLIANCE
ALLOW FAN OVERRUN TO COMMENCE
COOL HEAT EXCHANGER AND RESET APPLIANCE
ALLOW FAN OVERRUN TO COMMENCE
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
PUMP RUNS
BOILER MAINS SWITCH
CAN BOILER BE RESET
PRESS THE RESET BUTTON IN THE MIDDLE OF THE USER DISPLAY
COOL DOWN HEAT EXCHANGER AND RESET APPLIANCE
ALLOW FAN OVERRUN TO COMMENCE
COOL HEAT EXCHANGER AND RESET APPLIANCE
ALLOW FAN OVERRUN TO COMMENCE
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
PUMP RUNS
BOILER MAINS SWITCH
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
POTENTIOMETER RESISTANCE (DHW)
DISCONNECT AND REMOVE THE USER CONTROL (DISPLAY UNIT)
REMOVE THE FRONT COVER
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
DHW HEAT EXCHANGER TEMPERATURE
LOWER PCB
TURN HW STAT TO MAX
CH OPERATION (HEX PROVING)
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
CH DEMAND
EXTERNAL CONTROLS VOLTAGE OUT PCB
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
POTENTIOMETER RESISTANCE (DHW)
DISCONNECT AND REMOVE THE USER CONTROL (DISPLAY UNIT)
REMOVE THE FRONT COVER
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
DHW HEAT EXCHANGER TEMPERATURE
LOWER PCB
TURN HW STAT TO MAX
CH OPERATION (HEX PROVING)
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
CH DEMAND
EXTERNAL CONTROLS VOLTAGE OUT PCB
BOILER SWITCH ON
EXTERNAL CONTROLS CALLING
COOL HEAT EXCHANGER AND RESET APPLIANCE
ALLOW FAN OVERRUN TO COMMENCE
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
PUMP VOLTAGE
BOILER MAINS SWITCH ON
ENSURE SECONDARY HEAT EXCHANGER IS COOL AND THERE IS A DEMAND FOR PREHEAT
FAN RESISTANCE
DISCONNECT THE HARNESS FROM FAN
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
VOLTAGE POLARITY
GAIN ACCESS TO MAINS TERMINAL (USE INSULATION MAT AS REQUIRED)
DIVERTER VALVE POSITION (DHW)
BOILER MAINS SWITCH ON
DIVERTER VALVE LOCATED AT THE LOWER LH SIDE OF THE APPLIANCE
DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER
SECONDARY HEAT EXCHANGER
ENSURE SECONDARY HEA
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
DISCONNECT EXTERNAL CONTROLS
DISCONNECT EXTERNAL CONTROLS AND MAKE SAFE
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER
OBSERVATION DOES PREHEAT COMPLETE
ENSURE SECONDARY HEA
DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE CONTROL THERMISTORS AND HARNESS
REMOVE THERMISTOR CONNECTOR FROM PCB
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
DIVERTER VALVE VOLTAGE (CH)
BOILER MAINS SWITCH ON
CH DEMAND
DISPLAY SHOWS CORRECT DEMAND
IF PREHEAT ACTIVATES THEN ALLOW TO SATISFY
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
TAPS
ALLOW PRE HEAT TO SATISFY
FLAME SENSE LEAD CONTINUITY
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
UNPLUG CONNECTION FROM PCB
FLAME SENSE ELECTRODE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
INSPECTION DISPLAY PCB CONNECTIONS
REMOVE THE DISPLAY PCB
GAS INLET PRESSURE
ENSURE SECONDARY HEA
FLAME SENSE LEAD CONTINUITY
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
UNPLUG CONNECTION FROM PCB
FLAME SENSE ELECTRODE
REMOVE FLAME DETECTION ELECTRODE FROM ITS HOUSING
FLAME DETECTION ELECTRODE GAP
REMOVE FAN AND BURNER FROM TOP OF HEAT EXCHANGER
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
DIVERTER VALVE POSITION (DHW)
BOILER MAINS SWITCH ON
DIVERTER VALVE LOCATED AT THE LOWER LH SIDE OF THE APPLIANCE
BURNER CONDITION
REMOVE FAN
REMOVE THE BURNER
INSULATION PADS
REMOVE FAN AND BURNER
IGNITION ELECTRODE GAP
REMOVE IGNITION ELECTRODE FROM ITS HOUSING
GAS VALVE OPENS
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
BURNER INJECTOR
REMOVE THE BURNER INJECTOR FROM ITS HOUSING
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
BURNER CONDITION
REMOVE FAN
REMOVE THE BURNER
INSULATION PADS
REMOVE FAN AND BURNER
IGNITION ELECTRODE GAP
REMOVE IGNITION ELECTRODE FROM ITS HOUSING
OBSERVATION DISCONNECT FAN - DEMAND RECOGNISED?
REMOVE CONNECTOR FROM FAN ASSEMBLY AND MAKE SAFE
OBSERVATION DISCONNECT FAN HARNESS - DEMAND RECOGNISED?
REMOVE FAN CONNECTOR FROM THE PCB
VOLTAGE PERMANENT FAN HALL SENSOR
NO DEMANDS FOR CH OR
VOLTAGE FAN POWER AT PCB
GAIN ACCESS TO BOTTO
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
VOLTAGE FAN AT PCB
DISCONNECT DHW THERM
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
VOLTAGE PERMANENT FAN HALL SENSOR
NO DEMANDS FOR CH OR
VOLTAGE FAN POWER AT PCB
GAIN ACCESS TO BOTTO
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
VOLTAGE FAN AT PCB
DISCONNECT DHW THERM
RESISTANCE FAN
DISCONNECT THE FAN HARNESS FROM FAN
RESISTANCE FAN HARNESS
DISCONNECT THE CONNECTOR FROM THE FAN
DISCONNECT THE FAN HARNESS CONNECTOR FROM THE PCB
DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER
DIVERTER VALVE VOLTAGE (DHW)
BOILER MAINS SWITCH ON
RESISTANCE DIVERTER HARNESS
REMOVE THE 12 WAY CO
DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER
DIVERTER VALVE VOLTAGE (DHW)
BOILER MAINS SWITCH ON
RESISTANCE DIVERTER HARNESS
REMOVE THE 12 WAY CO
RESISTANCE OVERHEAT
REMOVE ONE OR BOTH
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
TEMPERATURE DIFFERENTIAL DHW
TURN HOT WATER TAP ON
RESISTANCE OVERHEAT
REMOVE ONE OR BOTH
RESISTANCE GAS VALVE AND HARNESS
REMOVE THE 12 WAY CONNECTOR FROM THE FRONT OF THE PCB
VOLTAGE GAS VALVE AT PCB
BOILER ON/OFF SWITCH ON
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
BURNER INJECTOR
REMOVE THE BURNER INJECTOR FROM ITS HOUSING
RESISTANCE OVERHEAT
REMOVE ONE OR BOTH
RESISTANCE GAS VALVE AND HARNESS
REMOVE THE 12 WAY CONNECTOR FROM THE FRONT OF THE PCB
VOLTAGE GAS VALVE AT PCB
BOILER ON/OFF SWITCH ON
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
BURNER INJECTOR
REMOVE THE BURNER INJECTOR FROM ITS HOUSING
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
GAS INLET PRESSURE
ENSURE SECONDARY HEA
BURNER CONDITION
REMOVE FAN
REMOVE THE BURNER
INSULATION PADS
REMOVE FAN AND BURNER
BURNER INJECTOR
REMOVE THE BURNER INJECTOR FROM ITS HOUSING
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
DIVERTER VALVE POSITION (CH)
BOILER MAINS SWITCH
DIVERTER VALVE SPINDLE
REMOVE THE DIVERTER
POTENTIOMETER RESISTANCE (CH)
DISCONNECT AND REMOVE THE USER CONTROL (DISPLAY UNIT)
REMOVE THE FRONT COVER
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
DIVERTER VALVE VOLTAGE (CH)
BOILER MAINS SWITCH ON
CH DEMAND
DISPLAY SHOWS CORRECT DEMAND
IF PREHEAT ACTIVATES THEN ALLOW TO SATISFY
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
TAPS
ALLOW PRE HEAT TO SATISFY
FUSE F1 PCB
REMOVE FUSE F1 FROM THE CONTROL BOX
RESISTANCE ON/OFF SWITCH AND HARNESS
LOWER THE PCB
REM
OBSERVATION PLUG DISPLAY PCB ON TO MAIN PCB - DOES DISPLAY ILLUMINATE
DISCONNECT THE HARNE
RESISTANCE HARNESS USER CONTROL
REMOVE HARNESS FROM PCB AND USER CONTROL
VOLTAGE MAIN PCB
DISCONNECT DISPLAY HARNESS FROM THE MAIN PCB
RESISTANCE FAN AND HARNESS
REMOVE FAN CONNECTOR FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS
REMOVE THE 12 WAY CONNECTOR FROM THE FRONT OF THE PCB
RESISTANCE DIVERTER VALVE AND HARNESS
REMOVE THE DIVERTER VALVE CONNECTOR FROM THE PCB
RESISTANCE SPARK GENERATOR AND HARNESS
REMOVE SPARK GENERATOR CONNECTOR FROM THE PCB
RESISTANCE DRY FIRE THERMISTOR AND HARNESS
ENSURE BOILER IS COOL
REMOVE THERMISTOR CONNECTOR FROM PCB
VOLTAGE AT SPARK GENERATOR - BLUE
USE INSULATION MAT AS REQUIRED
ELECTRODE AND LEAD CONTINUITY
MAKE SURE HT LEAD IS CLICKED ON TO THE ELECTRODE PROPERLY
ELECTRODE AND LEAD CONTINUITY
MAKE SURE HT LEAD IS CLICKED ON TO THE ELECTRODE PROPERLY
HARNESS CONTINUITY PCB TO SPARK GEN- BLUE
UNPLUG THE CONNECTOR FROM THE PCB
VOLTAGE AT SPARK GENERATOR - BLUE
USE INSULATION MAT AS REQUIRED
ELECTRODE AND LEAD CONTINUITY
MAKE SURE HT LEAD IS CLICKED ON TO THE ELECTRODE PROPERLY
ELECTRODE AND LEAD CONTINUITY
MAKE SURE HT LEAD IS CLICKED ON TO THE ELECTRODE PROPERLY
HARNESS CONTINUITY PCB TO SPARK GEN- BLUE
UNPLUG THE CONNECTOR FROM THE PCB
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE DRY FIRE THERMISTOR
DISCONNECT THE DRY FIRE SENSOR LEADS
RESISTANCE DHW THERMISTOR
DISCONNECT THE INLINE CONNECTOR FROM THE DHW THERMISTOR
POTENTIOMETER RESISTANCE (DHW)
DISCONNECT AND REMOVE THE USER CONTROL (DISPLAY UNIT)
REMOVE THE FRONT COVER
PRESSURE GAS INLET (DHW)
ATTACH U-GAUGE TO THE GAS VALVE INLET PRESSURE TEST POINT
TURN HOT WATER TAP ON
TEMPERATURE DIFFERENTIAL DHW
TURN HOT WATER TAP ON
BURNER INJECTOR
REMOVE THE BURNER INJECTOR FROM ITS HOUSING
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
BURNER CONDITION
REMOVE FAN
REMOVE THE BURNER
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
RESISTANCE CONTROL THERMISTOR FLOW
REMOVE ONE OR BOTH OF THE RED LEADS FROM THE CONTROL THERMISTOR
RESISTANCE CONTROL THERMISTOR RETURN
REMOVE ONE OR BOTH OF THE PINK LEADS FROM THE RETURN THERMISTOR
CH OPERATION
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
CENTRAL HEATING DEMAND
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
CH OPERATION
BOILER MAINS SWITCH ON
BOILER CH THERMOSTAT TO MAX
CENTRAL HEATING DEMAND
BURNER IGNITES LF
BOILER MAINS SWITCH ON
ENSURE SECONDARY HEAT EXCHANGER IS COOL AND THERE IS A DEMAND FOR PREHEAT
RESISTANCE CONTROL THERMISTOR FLOW AND HARNESS
REMOVE PLUG FROM PCB
RESISTANCE CONTROL THERMISTOR RETURN AND HARNESS
REMOVE PLUG FROM PCB
RESISTANCE CONTROL THERMISTOR DHW AND HARNESS
REMOVE PLUG FROM PCB
GAS INLET PRESSURE
ENSURE SECONDARY HEA
GAS VALVE OPENS
ATTACH PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
BURNER INJECTOR
REMOVE THE BURNER INJECTOR FROM ITS HOUSING
CONDENSATE TRAP AND DRAIN
CONDENSATE TRAP IS LOCATED LOWER L/H SIDE OF THE APPLIANCE BEHIND THE GAS VALVE
BURNER CONDITION
REMOVE FAN
REMOVE THE BURNER