XSol Diagnostic System

Interactive Test Sequence Navigator

Welcome to the XSol Diagnostic System

This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.

Start Diagnostic Sequence

or choose a specific test below:

DHW FLOW RATE

TURN HOT WATER TAP ON

Next: &2881, f3124

DHW OPERATION

Next: &148, ?96, ?98, ?100, ?102, ?671, ?2501

CH OPERATION

CH TEMPERATURE CONTROL SET TO MAX

Next: &183, ?149, ?151, ?715

PUMP OVERRUN

CH TEMPERATURE CONTROL SET TO MAX

Next: &185, !f184

SYPHON OPERATION

Next: &nff, !f186

DHW BURNER IGNITION & ESTABLISH

ENSURE PRIMARY HEAT EXCHANGER IS COOL

Next: &1826, ?318, ?986, ?1509, ?3793

MAXIMUM OUTPUT MODE

INSTRUCTIONS TO S

Next: &nff, !f701

FURTHER INVESTIGATION OVERHEAT

NOT USED

Next: &nff, f911

FURTHER INVESTIGATION FUSE BLOWN

NOT USED

Next: &nff, f1075

FAN PRESSURE TEST

ATTACH PRESSURE GAUG

Next: &1833, f3453

INLET PRESSURE MAX OUTPUT

ATTACH PRESSURE GAU

Next: &1835, !f1834

COMBUSTION ANALYSIS MAX AND MIN

UNCLIP DIVERTER VALVE HEAD FROM THE BODY AND LEAVE IN A SAFE POSITION

Next: &2790, ?1836, ?1838

CH OPERATION PERFORMANCE TEST FAIL

OUTSIDE OF MODEL

Next: &nff, f1880

INFORMATION CASE REMOVAL


CASE REMOVAL<

Next: &3041, !f1956

POWER UP SELF TEST

NO DEMANDS

Next: &1990, ?1958, ?1960

TYPE OF DIAGNOSTIC PROCEDURE

PLEASE SELECT FROM O

Next: &1992, !f1991

OPERATIONAL SEQUENCE

NO LONGER USED

Next: &5, !f1993

FAN RUNS

SET FLOW RATE TO APPROX. 3 LITRES PER MINUTE

Next: &317, f2895

VOLATILE LOCK OUT

NOT USED

Next: &nff, f3754

CH DEMAND

CH TEMPERATURE CONTROL SET TO MAX
ENSURE BOILER IS NOT UP TO TEMPERATURE

Next: &95, f2797

INTERNAL FAULT

NOT USED

Next: &nff, f2828

PUMP RUNS PREHEAT

ENSURE PRIMARY HEAT EXCHANGER IS BELOW 40°C (TO ENSURE A DEMAND FOR PREHEAT)

Next: &2362, f3634

PRE-HEAT FUNCTION

1. THIS AP

Next: &1957, !f3042

BURNER SEAL CHECK FOR OVERHEAT

OUTSIDE MODEL

Next: &nff, f3172

INFORMATION FAN PCB REMOVAL

Next: &nff, !f3904

INFORMATION FAN DEMAND VOLTAGE

THE PWM OR (DEMAND/S

Next: &nff, !f4001

BURNER BAFFLES OUT

FLUE

Next: End

FURTHER INVESTIGATION FUSE F1

PUMP ASSEMBLY - 3 SPEED

Next: End

DHW SENSOR

SENSOR - TEMPERATURE - DHW

Next: End

PRIMARY TEST

INLET PRESSURE

Next: End

PUMP OVERRUN

PCB (FROM FD988)

Next: End

SYPHON

SYPHON ASSEMBLY

Next: End

CASE REMOVAL

DIRECTION CHOICE OR CONTINUE

Next: End

FOR TYPE DIAG PROCEDURE

DIRECTION CHOICE OR CONTINUE

Next: End

OPERATIONAL SEQUENCE

DIRECTION CHOICE OR CONTINUE

Next: End

BLOWN STAND BY MODE AT POWER UP

FUSE (FUSED SPUR)

Next: End

LED AT POWER UP

PCB (FROM FD988)

Next: End

FAULT CODES

Z REDIRECTION

Next: End

NO BLUE LED

FUSE F1 (APPLIANCE PCB)

Next: End

BURNER BAFFLES OUT 1

FLUE

Next: End

DHW COOL

PUMP ASSEMBLY - 3 SPEED

Next: End

HEAT EXCHANGER NOISY

PUMP ASSEMBLY - 3 SPEED

Next: End

OVERHEAT

LIMITER - TEMPERATURE

Next: End

OVERHEAT

HEAT EXCHANGER ASSEMBLY

Next: End

FURTHER INVESTIGATION

HARNESS - MK3 NO ON/OFF

Next: End

PUMP PULSES

SYSTEM PRESSURE

Next: End

BAFFLES OUT

TUBE GAS SUPPLY

Next: End

BURNER BAFFLES OUT

BURNER

Next: End

BURNER BAFFLES OUT 2

BURNER

Next: End

PUMP PULSES 2

SENSOR - CONTROL

Next: End

PUMP PULSES 2

SENSOR - TEMPERATURE - DHW

Next: End

PUMP PULSING

PUMP ASSEMBLY - 3 SPEED

Next: End

PUMP PULSING

HEAT EXCHANGER ASSEMBLY

Next: End

HEAT EXCHANGER NOISY

HEAT EXCHANGER ASSEMBLY

Next: End

INTERNAL CLOCK2DHW NOISY

PCB (FROM FD988)

Next: End

INTERNAL FAULT

Z REDIRECTION

Next: End

NO BLUE LED 2

Z REDIRECTION

Next: End

FAN DOES NOT RUN

CODE PLUG

Next: End

TURBINE

HARNESS - MK3 NO ON/OFF

Next: End

FAN DOES NOT RUN

SENSOR - CONTROL

Next: End

FAN DOES NOT RUN

SENSOR - TEMPERATURE - DHW

Next: End

BAFFLES OUT 2

TUBE GAS SUPPLY

Next: End

COMBUSTION INCORRECT

TUBE GAS SUPPLY

Next: End

DROP OUT MIN MODE

TUBE GAS SUPPLY

Next: End

CH PERFORMANCE FAIL

TUBE GAS SUPPLY

Next: End

PREHEAT FUNCTION

DIRECTION CHOICE OR CONTINUE

Next: End

BURNER IGNITES

SYPHON ASSEMBLY

Next: End

BURNER IGNITES

INLET PRESSURE

Next: End

DHW FLOW RATE

MAINS WATER SUPPLY

Next: End

BURNER DOES NOT ESTABLISH

SYPHON ASSEMBLY

Next: End

INTERNAL CLOCKDHW NOISY

PCB (FROM FD988)

Next: End

BURNER SEAL FOR OVERHEAT

FLUE / BURNER SEALS

Next: End

DHW COOL RADS HOT DIVERTER MOTOR SWITCHING

PCB (FROM FD988)

Next: End

DOES NOT ESTABLISH - FLAME SENSE SHORTING TO EARTH

HARNESS - MK3 NO ON/OFF

Next: End

DHW COOL RADS HOT DIVERTER MOTOR SUPPLY

PCB (FROM FD988)

Next: End

DHW COOL RADS HOT

HARNESS - STEPPER MOTOR

Next: End

BOILER REACHES TEMP RADS DO NOT HEAT

HARNESS - STEPPER MOTOR

Next: End

DHW COOL RADS COOL

EXTERNAL MIXING

Next: End

FAN DOES NOT RUN

EXTERNAL MIXING

Next: End

OVERHEAT

SENSOR - CONTROL

Next: End

OVERHEAT

SENSOR - TEMPERATURE - DHW

Next: End

DOES NOT ESTABLISH

TUBE GAS SUPPLY

Next: End

FLAME SENSE BURNER IGNITES

HARNESS - MK3 NO ON/OFF

Next: End

BURNER IGNITES

ELECTRODES

Next: End

DOES NOT ESTABLISH 2

BURNER

Next: End

FAN PRESSURE TEST

TUBE GAS SUPPLY

Next: End

FAN PRESSURE TEST

SYPHON ASSEMBLY

Next: End

TIMER - MECHANICAL - MT10

TIMER - MECHANICAL - MT10

Next: End

BURNER DOES NOT IGNITEFAN RUNS OVERHEAT 1

LIMITER 120°C - TEMPERATURE

Next: End

BURNER DOES NOT IGNITEBURNER IGNITION OVERHEAT 1

LIMITER - TEMPERATURE

Next: End

BURNER DOES NOT IGNITE 2

GAS VALVE

Next: End

BURNER DOES NOT IGNITE

FLUE

Next: End

DOES NOT IGNITE 2

TUBE GAS SUPPLY

Next: End

BURNER DOES NOT IGNITE

BURNER

Next: End

DOES NOT IGNITE

TUBE GAS SUPPLY

Next: End

NO VOLTAGE

PCB AND GAS VALVE

Next: End

BURNER DOES NOT IGNITE

PCB-HARNESS (MAIN)

Next: End

FAN RUNS

LIMITER 120°C - TEMPERATURE

Next: End

BURNER IGNITION

LIMITER - TEMPERATURE

Next: End

FAN RUNS OVERHEAT 1

LIMITER 120°C - TEMPERATURE

Next: End

BURNER IGNITION OVERHEAT 1

LIMITER - TEMPERATURE

Next: End

DHW TOO COOL

HEAT EXCHANGER ASSEMBLY

Next: End

DHW TO COOL 2

SENSOR - TEMPERATURE - DHW

Next: End

DHW TO COOL

SENSOR - CONTROL

Next: End

BURNER IGNITES

LEAD - IGNITION

Next: End

BURNER DOES NOT IGNITE

TUBE GAS SUPPLY

Next: End

BURNER IGNITES

ELECTRODES

Next: End

DOES NOT IGNITE

HEAT EXCHANGER ASSEMBLY

Next: End

DOES NOT IGNITE

SENSOR - TEMPERATURE - DHW

Next: End

DHW FLOW RATE

ISOLATION VALVES

Next: End

STUCK IN DHW

DIVERTER VALVE ASSEMBLY

Next: End

PREVENTING PREHEAT

DT20 / DT20RF

Next: End

PUMP DOES NOT RUN DT20

SENSOR - CONTROL

Next: End

PUMP DOES NOT RUN DT20

SENSOR - TEMPERATURE - DHW

Next: End

PREHEAT DT20

CABLE - PUMP

Next: End

PUMP DOES NOT RUN

SENSOR - CONTROL

Next: End

PUMP DOES NOT RUN

SENSOR - TEMPERATURE - DHW

Next: End

PREHEAT

CABLE - PUMP

Next: End

DOES NOT ESTABLISH

BURNER

Next: End

FAN PRESSURE PRIMARY TEST

FLUE

Next: End

CH PERFORMANCE FAIL 2

TUBE GAS SUPPLY

Next: End

FAN DOES NOT RUNFAULT CODE

CODE PLUG

Next: End

FAN DOES NOT RUN 1FAULT CODE

SENSOR - CONTROL

Next: End

VOLATILE LOCKOUTFAULT CODE

SENSOR - TEMPERATURE - DHW

Next: End

DHW BURNER IGNITION ESTABLISH - INTERMITTENT- HIGH RESIST

LIMITER - TEMPERATURE (CORROSION)

Next: End

DHW BURNER IGNITION ESTABLISH - INTERMITTENT

HARNESS - MK3 NO ON/OFF

Next: End

FAN DOES NOT RUN - NEW STYLE

CABLE CONNECTING FAN ASSEMBLY

Next: End

FAN VOLTAGE PCB - NEW STYLE FAN

PCB (FROM FD988)

Next: End

FAN RUNS - NEW STYLE

CABLE CONNECTING FAN ASSEMBLY

Next: End

FAN RUNS

CABLE CONNECTING FAN ASSEMBLY

Next: End

DOES NOT RUN

FAN ASSEMBLY

Next: End

FAN VOLTAGE PCB

PCB (FROM FD988)

Next: End

FAN DOES NOT RUN

CABLE CONNECTING FAN ASSEMBLY

Next: End

FAN RUNS

FAN ASSEMBLY

Next: End

BETWEEN 125 VAC AND 135 VAC - NEW STYLE

CABLE CONNECTING FAN ASSEMBLY

Next: End

ABOVE 135 VAC - NEW STYLE

CABLE CONNECTING FAN ASSEMBLY

Next: End

STSLOW THEN TO TO HIGH SPEED - NEW STYLE

CABLE CONNECTING FAN ASSEMBLY

Next: End

BETWEEN 125 VAC AND 135 VAC

CABLE CONNECTING FAN ASSEMBLY

Next: End

ABOVE 135 VAC

CABLE CONNECTING FAN ASSEMBLY

Next: End

SLOW THEN TO HIGH SPEED

FAN ASSEMBLY

Next: End

STSLOW THEN TO TO HIGH SPEED

CABLE CONNECTING FAN ASSEMBLY

Next: End

BELOW 124 VAC

FAN ASSEMBLY

Next: End

INFORMATION FAN PCB REMOVAL

Z DIRECTION

Next: End

FUSE INVESTIGATION - INCOMPATIBLE

FAN ASSEMBLY

Next: End

FURTHER INVESTIGATION FUSE F1

FAN ASSEMBLY

Next: End

VOLATILE LOCKOUT BETWEEN 125 VAC AND 135 VAC - NEW STYLE

CABLE CONNECTING FAN ASSEMBLY

Next: End

VOLATILE LOCKOUT ABOVE 135 VAC - NEW STYLE

CABLE CONNECTING FAN ASSEMBLY

Next: End

VOLATILE LOCKOUT STSLOW THEN TO TO HIGH SPEED - NEW STYLE

CABLE CONNECTING FAN ASSEMBLY

Next: End

DOES NOT ESTABLISH

INLET PRESSURE

Next: End

VOLATILE LOCKOUT BETWEEN 125 VAC AND 135 VAC

CABLE CONNECTING FAN ASSEMBLY

Next: End

VOLATILE LOCKOUT ABOVE 135 VAC

CABLE CONNECTING FAN ASSEMBLY

Next: End

VOLATILE LOCKOUT STSLOW THEN TO TO HIGH SPEED

CABLE CONNECTING FAN ASSEMBLY

Next: End

VOLATILE LOCKOUT BELOW 124 VAC

FAN ASSEMBLY

Next: End

VOLATILE LOCKOUT FAN RUNS 1 - NEW STYLE

CABLE CONNECTING FAN ASSEMBLY

Next: End

VOLATILE LOCKOUT FAN RUNS 1 - NEW STYLE FAN

PCB (FROM FD988)

Next: End

VOLATILE LOCKOUT FAN RUNS - NEW STYLE

CABLE CONNECTING FAN ASSEMBLY

Next: End

FAN RUNS1 FAULT CODE

CABLE CONNECTING FAN ASSEMBLY

Next: End

FAN VOLTAGE PCB1 FAULT CODE

PCB (FROM FD988)

Next: End

FAN DOES NOT RUN1 FAULT CODE

CABLE CONNECTING FAN ASSEMBLY

Next: End

FAN RUNS1 FAULT CODE

FAN ASSEMBLY

Next: End

DOES NOT RUN1 FAULT CODE

FAN ASSEMBLY

Next: End

240V ON ALL FAN CONNECTIONS 2

PCB (FROM FD988)

Next: End

240V ON ALL FAN CONNECTIONS 3

PCB (FROM FD988)

Next: End

240 ON ALL FAN CONNECTIONS 4

PCB (FROM FD988)

Next: End

240V ON ALL FAN CONNECTIONS

PCB (FROM FD988)

Next: End

DHW TOO COOL

SENSOR - TEMPERATURE - DHW

Next: End

HOT THEN COLD

HEAT EXCHANGER - PLATE

Next: End

DHW HOT THEN COLD

SENSOR - CONTROL

Next: End

DHW HOT THEN COLD

PUMP ASSEMBLY - 3 SPEED

Next: End

MAXIMUM OUTPUT INSTRUCTIONS

MAXIMUM OUTPUT INSTRUCTIONS

Next: End

EXPANSION VESSEL

EXPANSION VESSEL

Next: End

DHW COOL

SYSTEM PRESSURE

Next: End

DHW NOISY

SYSTEM PRESSURE

Next: End

DHW HOT THEN COLD

SYSTEM PRESSURE

Next: End

CH NOISY

PUMP ASSEMBLY - 3 SPEED

Next: End

CH NOISY

SENSOR - CONTROL

Next: End

CH NOISY

SYSTEM PRESSURE

Next: End

RADS DO NOT HEAT

SYSTEM PRESSURE

Next: End

RADS DO NOT HEAT

PUMP ASSEMBLY - 3 SPEED

Next: End

RADS DO NOT HEAT

ISOLATION VALVES

Next: End

OVERHEAT

SYSTEM PRESSURE

Next: End

OVERHEAT

PUMP ASSEMBLY - 3 SPEED

Next: End

RADS COLD

VALVE - BY-PASS

Next: End

BURNER BAFFLES OUT

SYPHON ASSEMBLY

Next: End

BURNER BAFFLES OUT

INLET PRESSURE

Next: End

DHW COOL RADIATORS HOT

DIVERTER VALVE ASSEMBLY

Next: End

FURTHER INVESTIGATION FUSE F1

CABLE - PUMP

Next: End

FURTHER INVESTIGATION FUSE F1

CABLE CONNECTING FAN ASSEMBLY

Next: End

OVERHEAT

PCB (FROM FD988)

Next: End

DHW TOO HOT

PCB (FROM FD988)

Next: End

DHW TOO HOT

HARNESS - MK3 NO ON/OFF

Next: End

CH NOISY

PCB (FROM FD988)

Next: End

CH NOISY

HEAT EXCHANGER ASSEMBLY

Next: End

CH NOISY

Next: End

FURTHER INVESTIGATION FUSED SPUR

Z REDIRECTION

Next: End

FAULT CODES

DIRECTION CHOICE OR CONTINUE

Next: End

NO BLUE LED

Z REDIRECTION

Next: End

BOILER GOES TO OVERHEAT

LIMITER 120°C - TEMPERATURE

Next: End

DHW COOL RADIATORS COOLPUMP RUNNING PRE TEST 2

PUMP ASSEMBLY - 3 SPEED

Next: End

OVERHEAT

HEAT EXCHANGER - PLATE

Next: End

FURTHER INVESTIGATION

GAS VALVE

Next: End

BURNER BAFFLES OUT

HEAT EXCHANGER ASSEMBLY

Next: End

BURNER BAFFLES OUT

GAS VALVE

Next: End

PUMP PULSES

HEAT EXCHANGER - PLATE

Next: End

CH OPERATION DHWDHW NOISY

HEATING CONTROLS

Next: End

CH OPERATION (DHW)DHW NOISY

HEATING CONTROLS

Next: End

INTERNAL FAULT

DIRECTION CHOICE OR CONTINUE

Next: End

FAN SIGNAL

PCB (FROM FD988)

Next: End

FLOW SENSOR FAN RUNS 2

HARNESS - MK3 NO ON/OFF

Next: End

DHW SENSOR FAN DOES NOT RUN

HARNESS - MK3 NO ON/OFF

Next: End

CO2 SETTINGS INCORRECT

GAS VALVE SETTING RETEST

Next: End

DROPS OUT ON MINIMUM

GAS VALVE SETTING

Next: End

CH OP PT FAIL

GAS VALVE SETTING RETEST

Next: End

FLOW RATE

HEAT EXCHANGER - PLATE

Next: End

FLOW RATE

FLOW SENSOR ASSEMBLY

Next: End

FLOW RATE

FILTER - INSERT - DHW

Next: End

FLOW RATE

FLOW REGULATOR

Next: End

FLOW RATE

NOZZLES

Next: End

FLAME SENSE

PCB (FROM FD988)

Next: End

DOES NOT REACT TO DH DEMAND CH DEMAND 1

INTERNAL CLOCK

Next: End

OVERHEAT OCCURED

NORMAL OPERATION

Next: End

SHORTING TO EARTH

ELECTRODES

Next: End

DHW COOL RADS HOT ELECTRICAL FAULT

MOTOR - DIVERTER VALVE

Next: End

BAFFLES OUT

MEMBRANE

Next: End

BAFFLES OUT

FAN ASSEMBLY

Next: End

ELECTRICAL

FLOW SENSOR ASSEMBLY

Next: End

BURNER DOES NOT ESTABLISH

GAS VALVE

Next: End

FAN PRESSURE TEST

MEMBRANE

Next: End

FAN PRESSURE TEST

FAN ASSEMBLY

Next: End

FURTHER INVESTIGATION

PCB (FROM FD988) FUSE INVESTIGATION

Next: End

DOES NOT IGNITE - HIGH RESIST

LIMITER - TEMPERATURE (CORROSION)

Next: End

BURNER DOES NOT IGNITEAPS/FLUE/OH OVERHEAT 1

HARNESS - MK3 NO ON/OFF

Next: End

BURNER IGNITES 2

HARNESS - MK3 NO ON/OFF

Next: End

NOT IGNITING NO DROP

MEMBRANE

Next: End

NOT IGNITING NO DROP

FAN ASSEMBLY

Next: End

BURNER DOES NOT IGNITE2

HEAT EXCHANGER ASSEMBLY

Next: End

BURNER IGNITES

GAS VALVE

Next: End

VOLTAGE GAS VALVE

PCB (FROM FD988)

Next: End

DOES NOT IGNITE - OPEN CIRCUIT

LIMITER - TEMPERATURE (CORROSION)

Next: End

FLUE/OH

HARNESS - MK3 NO ON/OFF

Next: End

GAS VALVE OVERHEAT 1

PCB (FROM FD988)

Next: End

OVERHEAT INVESTIGATION

LIMITER - TEMPERATURE (CORROSION)

Next: End

APS/FLUE/OH OVERHEAT 1

HARNESS - MK3 NO ON/OFF

Next: End

DHW COOL RADIATORS COOL

HEAT EXCHANGER - PLATE

Next: End

DHW SENSOR - TOO COOL RADS COOL

HARNESS - MK3 NO ON/OFF

Next: End

DHW TOO COOL 2

PCB (FROM FD988)

Next: End

NOT IGNITING WITH DROP

MEMBRANE

Next: End

NOT IGNITING WITH DROP

FAN ASSEMBLY

Next: End

BURNER DOES NOT IGNITE

GAS VALVE

Next: End

PUMP DOES NOT RUN DT20

HARNESS - MK3 NO ON/OFF

Next: End

PREHEAT DT20

PCB (FROM FD988)

Next: End

PUMP DOES NOT RUN 2 DT20

HARNESS - MK3 NO ON/OFF

Next: End

PREHEAT DT20

PUMP ASSEMBLY - 3 SPEED

Next: End

PUMP DOES NOT RUN

HARNESS - MK3 NO ON/OFF

Next: End

PREHEAT

PCB (FROM FD988)

Next: End

PUMP DOES NOT RUN 2

HARNESS - MK3 NO ON/OFF

Next: End

PREHEAT

PUMP ASSEMBLY - 3 SPEED

Next: End

BURNER DOES NOT IGNITE

MEMBRANE

Next: End

BURNER DOES NOT IGNITE

FAN ASSEMBLY

Next: End

BURNER DOES NOT EST

HEAT EXCHANGER ASSEMBLY

Next: End

PRIMARY PRE TEST FAN PRESSURE

HEAT EXCHANGER ASSEMBLY

Next: End

CH OP PT FAIL FAN PRESSURE FAIL

HEAT EXCHANGER ASSEMBLY

Next: End

FAN DOES NOT RUNFAULT CODE

HARNESS - MK3 NO ON/OFF

Next: End

FAN DOES NOT RUN 1FAULT CODE

PCB (FROM FD988)

Next: End

VOLATILE LOCKOUTFAULT CODE

HARNESS - MK3 NO ON/OFF

Next: End

DHW BURNER IGNITION ESTABLISH - INTERMITTENT 2

HEAT EXCHANGER ASSEMBLY

Next: End

DHW BURNER IGNITION ESTABLISH - INTERMITTENT

GAS VALVE SETTING RETEST

Next: End

DHW BURNER IGNITION ESTABLISH - INTERMITTENT

GAS VALVE SETTING

Next: End

DHW BURNER IGNITION ESTABLISH - INTERMITTENT

NO FAULT INTERMITTENT IGNITION

Next: End

FAN DOES NOT RUN - NEW STYLE FAN

PCB (FROM FD988)

Next: End

DOES NOT RUN - NEW STYLE

FAN ASSEMBLY

Next: End

FAN RUNS - NEW STYLE

FAN ASSEMBLY

Next: End

FAN DOES NOT RUN

PCB (FROM FD988)

Next: End

DOES NOT RUN

FAN PCB

Next: End

FAN RUNS

FAN PCB

Next: End

FAN REDUCES AND STOPS - NEW STYLE

PCB (FROM FD988)

Next: End

SLOW THEN TO HIGH SPEED - NEW STYLE

FAN ASSEMBLY

Next: End

BELOW 124 VAC - NEW STYLE

FAN ASSEMBLY

Next: End

FAN REDUCES AND STOPS

PCB (FROM FD988)

Next: End

SLOW THEN TO HIGH SPEED

FAN PCB

Next: End

BELOW 124 VAC

FAN PCB

Next: End

FUSE INVESTIGATION

FAN PCB

Next: End

VOLATILE LOCKOUT FAN REDUCES AND STOPS

PCB (FROM FD988)

Next: End

VOLATILE LOCKOUT BELOW 124 VAC

FAN PCB

Next: End

VOLATILE LOCKOUT FAN RUNS - NEW STYLE FAN

PCB (FROM FD988)

Next: End

VOLATILE LOCKOUT FAN RUNS - NEW STYLE

FAN ASSEMBLY

Next: End

FAN DOES NOT RUN1 FAULT CODE

PCB (FROM FD988)

Next: End

FAN RUNS1 FAULT CODE

FAN PCB

Next: End

DOES NOT RUN1 FAULT CODE

FAN PCB

Next: End

DHW HOT THEN COLD

PCB (FROM FD988)

Next: End

HEAT EXCHANGER NOISY

HEAT EXCHANGER - PLATE

Next: End

EXCESSIVE SYSTEM PRESSURE

HOSE - FLEXIBLE

Next: End

RADS DO NOT HEAT

Next: End

DHW COOL, RADIATORS HEAT WITH NO CH DEMAND

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p101

DHW TOO HOT

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p1810

BOILER NOISY

CHARACTERISTIC TEST FROM CH OPERATION

Next: p779

BURNER DOES NOT IGNITE

CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH

Next: p3060

BOILER REACHES TEMPERATURE, RADIATORS DO NOT HEAT

CHARACTERISTIC TEST FROM CH OPERATION

Next: p796

CO2 SETTINGS INCORRECT

CHARACTERISTIC TEST FROM COMBUSTION ANALYSIS MAX AND MIN

Next: p3007

BURNER DROPS OUT IN MINIMUM MODE

CHARACTERISTIC TEST FROM COMBUSTION ANALYSIS MAX AND MIN

Next: p3010

TEMPERATURE DIFFERENTIAL INCORRECT LOCAL NOISE

CHARACTERISTIC TEST FROM DIFFERENTIAL FLOW RETURN

Next: !p1871

DIFFERENTIAL OK SYSTEM NOISE

CHARACTERISTIC TEST FROM DIFFERENTIAL FLOW RETURN

Next: !p1873

BLUE LED NOT ILLUMINATED

CHARACTERISTIC TEST FROM POWER UP SELF TEST

Next: p1994

BLUE LED FLASHING (FAULT CODE)

CHARACTERISTIC TEST FROM POWER UP SELF TEST

Next: p2007

BOILER FIRES FOR DHW THEN SHUTS DOWN WITH PUMP PULSING ON/OFF

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p2536

FLOW SENSOR BLOCKED AND/OR IN POOR CONDITION

CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS

Next: !p3130

INLET FILTER BLOCKED AND/OR IN POOR CONDITION

CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS

Next: !p3132

FLOW REGULATOR BLOCKED AND/OR IN POOR CONDITION

CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS

Next: !p3134

NOZZLES BLOCKED AND/OR IN POOR CONDITION

CHARACTERISTIC TEST FROM CHECK FLOW COMPONENTS

Next: !p3136

VOLTAGE PRESENT ON TEST 1 BUT DOES NOT DROP OR FLUCTUATES

CHARACTERISTIC TEST FROM RECTIFICATION VOLTAGE

Next: p3446

VOLTAGE ABSENT ON TEST 1

CHARACTERISTIC TEST FROM RECTIFICATION VOLTAGE

Next: p3153

BURNER IGNITES SMOOTHLY, BUT DOES NOT ESTABLISH

CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH

Next: p319

FAN MEMBRANE DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION FAN MEMBRANE

Next: !p3293

FAN STIFF TO TURN OR SEIZED

CHARACTERISTIC TEST FROM INSPECTION FAN MEMBRANE

Next: !p3295

FAN MEMBRANE DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION FAN MEMBRANE

Next: !p3460

FAN STIFF TO TURN OR SEIZED

CHARACTERISTIC TEST FROM INSPECTION FAN MEMBRANE

Next: !p3462

FLUE STAT CORRODED, DAMAGED, OR MOISTURE PRESENT

CHARACTERISTIC TEST FROM RESISTANCE SAFETY CIRCUIT

Next: !p3494

RESISTANCE NOT AS EXPECTED

CHARACTERISTIC TEST FROM RESISTANCE SAFETY CIRCUIT

Next: p3508

FAN MEMBRANE DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION FAN MEMBRANE

Next: !p3528

FAN STIFF TO TURN OR SEIZED

CHARACTERISTIC TEST FROM INSPECTION FAN MEMBRANE

Next: !p3530

FLUE STAT CORRODED, DAMAGED, OR MOISTURE PRESENT

CHARACTERISTIC TEST FROM RESISTANCE SAFETY CIRCUIT

Next: !p3542

RESISTANCE NOT AS EXPECTED

CHARACTERISTIC TEST FROM RESISTANCE SAFETY CIRCUIT

Next: p3545

FLUE STAT CORRODED, DAMAGED, OR MOISTURE PRESENT

CHARACTERISTIC TEST FROM RESISTANCE SAFETY CIRCUIT

Next: !p3565

RESISTANCE NOT AS EXPECTED

CHARACTERISTIC TEST FROM RESISTANCE SAFETY CIRCUIT

Next: p3568

FAN MEMBRANE DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION FAN MEMBRANE

Next: !p3592

FAN STIFF TO TURN OR SEIZED

CHARACTERISTIC TEST FROM INSPECTION FAN MEMBRANE

Next: !p3594

FAN MEMBRANE DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION FAN MEMBRANE

Next: !p3667

FAN STIFF TO TURN OR SEIZED

CHARACTERISTIC TEST FROM INSPECTION FAN MEMBRANE

Next: !p3669

VOLATILE LOCKOUT DISPLAYED WITHIN 10 SECONDS

CHARACTERISTIC TEST FROM OBSERVATION BLUE LED - FAULT CODE

Next: p3757

VOLATILE LOCKOUT DISPLAYED AFTER MORE THAN 20 SECONDS AND FAN DOES NOT RUN

CHARACTERISTIC TEST FROM OBSERVATION BLUE LED - FAULT CODE

Next: p3941

BURNER DOES NOT IGNITE SMOOTHLY / INTERMITTENT IGNITION

CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH

Next: p3794

FAN MEMBRANE DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION FAN MEMBRANE

Next: !p3806

FAN STIFF TO TURN OR SEIZED

CHARACTERISTIC TEST FROM INSPECTION FAN MEMBRANE

Next: !p3808

BURNER DROPS OUT IN MINIMUM MODE

CHARACTERISTIC TEST FROM COMBUSTION ANALYSIS MAX AND MIN

Next: p3816

CO2 SETTINGS INCORRECT

CHARACTERISTIC TEST FROM COMBUSTION ANALYSIS MAX AND MIN

Next: p3818

FAN MEMBRANE DAMAGED OR WORN

CHARACTERISTIC TEST FROM INSPECTION FAN MEMBRANE

Next: !p3840

FAN STIFF TO TURN OR SEIZED

CHARACTERISTIC TEST FROM INSPECTION FAN MEMBRANE

Next: !p3842

240 VOLTS ABSENT BETWEEN PURPLE/BROWN

CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)

Next: !p3848

240 VOLTS PRESENT BETWEEN PURPLE/BROWN BUT OTHERS NOT AS ABOVE

CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)

Next: p3976

240 VOLTS ABSENT BETWEEN PURPLE/BROWN

CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)

Next: !p3860

240 VOLTS PRESENT BETWEEN PURPLE/BROWN BUT OTHERS NOT AS ABOVE

CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)

Next: p3980

VOLTAGE ABOVE 120 VAC

CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB) - NEW STYLE

Next: p3878

VOLTAGE BETWEEN 110 VAC AND 120 VAC

CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB) - NEW STYLE

Next: p3880

VOLTAGE ABOVE 140 VAC

CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB)

Next: p3890

VOLTAGE BETWEEN 129 VAC AND 140 VAC

CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB)

Next: p3892

VOLTAGE ABOVE 120 VAC

CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB) - NEW STYLE

Next: p3916

VOLTAGE BETWEEN 110 VAC AND 120 VAC

CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB) - NEW STYLE

Next: p3918

VOLTAGE ABOVE 140 VAC

CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB)

Next: p3928

VOLTAGE BETWEEN 129 VAC AND 140 VAC

CHARACTERISTIC TEST FROM FAN VOLTAGE CONTROL (PCB)

Next: p3930

240 VOLTS ABSENT BETWEEN PURPLE/BROWN

CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)

Next: !p3946

240 VOLTS PRESENT BETWEEN PURPLE/BROWN BUT OTHERS NOT AS ABOVE

CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)

Next: p3994

240 VOLTS ABSENT BETWEEN PURPLE/BROWN

CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)

Next: !p3958

240 VOLTS PRESENT BETWEEN PURPLE/BROWN BUT OTHERS NOT AS ABOVE

CHARACTERISTIC TEST FROM VOLTAGE FAN (AT PCB)

Next: p3988

DHW RUNS HOT THEN COLD

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p761

EXCESSIVE SYSTEM PRESSURE RISE

CHARACTERISTIC TEST FROM CH OPERATION

Next: p716

HEAT EXCHANGER NOISY

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p720

DHW TOO COOL, RADIATORS COLD

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p733

BURNER IGNITES BUT BAFFLES OR IS NOISY

CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH

Next: p987

RESISTANCE GAS VALVE MAIN AND HARNESS FURTHER INVESTIGATION

DISCONNECT ST9 CONNE

Next: p1076, f1077

RESISTANCE GAS VALVE HARNESS

REMOVE THE CONNECTOR

Next: !p2343, !f2344

RESISTANCE PUMP

DISCONNECT THE PUMP CONNECTOR
ENSURE PUMP SPEED SELECTOR IS SET TO POSITION 3

Next: !p1082, !f1083

RESISTANCE FAN

DISCONNECT FAN CONNECTOR AT FAN

Next: !p1086, f3905

DHW SENSOR

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: !p1813, !f1814

FAN PRESSURE TEST

ATTACH PRESSURE GAUG

Next: p3031, f3696

RESISTANCE FUSE (FUSED SPUR)

REMOVE FUSE FROM FUSED SPUR

Next: !p1997, f1998

FUSE FURTHER INVESTIGATION

Next: !p1999, !f2000

FUSE FURTHER INVESTIGATION F1

Next: !p2013, !f2014

INSPECTION FLUE

Next: p2990, !f2044

RESISTANCE FLUE OH STAT

DISCONNECT ONE OF THE ORANGE LEADS FROM THE OVERHEAT STAT

Next: !p2301, !f2302

PUMP VOLTAGE

{GAINPCBACS}

Next: p2320, !f2321

DIFFERENTIAL PRIMARY HEAT EXCHANGER

CH TEMPERATURE CONTR

Next: !p2337, !f2338

INTERNAL OR EXTERNAL CONTROLS

Next: p2798, f2799

EXTERNAL CONTROLS VOLTAGE (RETURN)

{GAINPCBACS}
EXTERNAL CONTROLS CALLING FOR HEAT

Next: p3166, f2801

EXTERNAL CONTROL VOLTAGE (SEND)

Next: !p2802, !f2803

EXTERNAL CONTROL VOLTAGE (SEND)

Next: !p2808, !f2809

INTERNAL FAULT RESET

Next: !p2829, !f2830

INSPECTION CODE PLUG

LOWER THE FACIA PANEL

Next: p2896, !f2897

VOLTS TO TURBINE

Next: p3314, f2901

HARNESS CONTINUITY (TURBINE)

BREAK THE INLINE CON

Next: !p2902, !f2903

RESISTANCE SENSOR TEMP FLOW

DISCONNECT PLUG (RE

Next: !p2906, !f2907

RESISTANCE DHW SENSOR

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: !p2910, !f2911

RESISTANCE SAFETY CIRCUIT

DISCONNECT CONNECTOR

Next: p3601, ?3541, ?3543

OBSERVATION COLD MAINS FLOW RATE

Next: p3615, !f3126

INSPECTION SEAL INTEGRITY

Next: !p3173, !f3174

VOLTAGE DIVERTER VALVE AT PCB

NO DEMAND
REMOVE CONNECTOR ST17 FROM PCB

Next: p3227, !f3177

VOLTAGE DIVERTER VALVE AT PCB

NO DEMAND
REMOVE CONNECTOR ST17 FROM PCB

Next: p3232, !f3182

INSPECTION HARNESS ELECTRODE SENSE

DISCONNECT THE CONNECTOR FROM THE FLAME SENSE
ELECTRODE AT THE TOP OF THE APPLIANCE

Next: !p3225, !f3226

CONDENSATE PIPE

Next: p3678, !f3467

RESISTANCE SAFETY CIRCUIT

DISCONNECT CONNECTOR

Next: p3513, ?3493, ?3495

RESISTANCE GAS VALVE

REMOVE THE TWO CONNECTORS FROM THE GAS VALVE

Next: !p3517, !f3518

INSPECTION FLUE

Next: p3521, !f3522

RESISTANCE GAS VALVE

REMOVE THE TWO CONNECTORS FROM THE GAS VALVE

Next: p3536, !f3537

DIFFERENTIAL PRIMARY HEAT EXCHANGER

CH TEMPERATURE CONTR

Next: !p3576, !f3577

DHW SENSOR

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: !p3580, !f3581

OBSERVATION DISCONNECT DT20 PUMP RUNS?

REMOVE THE PROGRAMMER FROM THE FACIA OF THE APPLIANCE
REMOVE THE CONNECTOR FROM THE PCB

Next: p3637, !f3638

RESISTANCE SENSOR TEMP FLOW AND HARNESS

DISCONNECT CONNECTOR

Next: p3641, f3642

RESISTANCE SENSOR TEMP FLOW

DISCONNECT PLUG (RE

Next: !p3643, !f3644

RESISTANCE DHW SENSOR

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: !p3647, !f3648

RESISTANCE SENSOR TEMP FLOW AND HARNESS

DISCONNECT CONNECTOR

Next: p3653, f3654

RESISTANCE SENSOR TEMP FLOW

DISCONNECT PLUG (RE

Next: !p3655, !f3656

RESISTANCE DHW SENSOR

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: !p3659, !f3660

INSPECTION FLUE

Next: p3664, !f3674

INSPECTION FLUE

Next: p3699, !f3706

OBSERVATION BLUE LED - FAULT CODE

Next: p3911, ?3756, ?3758

RESISTANCE SENSOR TEMP FLOW

DISCONNECT PLUG (RE

Next: !p3775, !f3776

RESISTANCE DHW SENSOR

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: !p3779, !f3780

CONDENSATE PIPE

Next: p3797, !f3798

VOLTAGE FAN (AT PCB) - NEW STYLE

MOVE CONNECTOR ST5 U

Next: p3846, ?3847, ?3849

FAN VOLTAGE CONTROL (PCB) - NEW STYLE

{GAINPCBACS}
MOVE CONNECTOR ST5 TO EXPOSE TERMINALS ON PCB

Next: p3876, ?3877, ?3879

OBSERVATION FAN TYPE

Next: p3906, !f3907

FAN VOLTAGE CONTROL (PCB) - NEW STYLE

{GAINPCBACS}
MOVE CONNECTOR ST5 TO EXPOSE TERMINALS ON PCB

Next: p3914, ?3915, ?3917

VOLTAGE FAN (AT PCB) - NEW STYLE

MOVE CONNECTOR ST5 U

Next: p3944, ?3945, ?3947

BOILER RESET

ENSURE BOILER HAS COOLED

Next: p923, f912

RESISTANCE SAFETY CIRCUIT

DISCONNECT CONNECTOR

Next: !p3563, ?3564, ?3566

DIVERTER VALVE ACTUATOR OPERATION

REMOVE THE DIVERTER

Next: !p106, f3175

RESISTANCE PUMP AND HARNESS

REMOVE THE PUMP CONNECTOR ST4 FROM THE PCB
ENSURE PUMP SPEED SELECTOR IS SET TO POSITION 3

Next: p1080, f1081

RESISTANCE FAN AND HARNESS

DISCONNECT FAN CONNECTOR ST5 FROM THE PCB

Next: p3468, f1085

RUN BOILER TO MAX TEMP-DOES OVERHEAT OCCUR

ATTACH TEMPERATURE CLAMP TO FLOW PIPE
CH TEMPERATURE CONTROL TO MAX

Next: !p1789, f2300

RESISTANCE DHW SENSOR AND HARNESS

DISCONNECT CONNECTOR

Next: !p1811, f1812

DIFFERENTIAL FLOW RETURN

TEMPERATURE CONTROL SET TO MAXIMUM
ATTACH TEMPERATURE CLAMPS TO FLOW AND RETURN PIPES

Next: !p1869, ?1870, ?1872

VOLTAGE MAINS POWER INPUT TO APPLIANCE

{GAINPCBACS}

Next: p1995, f1996

FUSE F1

REMOVE CONTROL BOX COVER IF NECESSARY

Next: p2848, f2012

FURTHER INVESTIGATION LED PROBLEM

Next: !p2003, !f2004

FAULT CODES


SELECT APPROPRIATE FAULT CODE

Next: !p2008, !f2009

PUMP LIMPET TEST

Next: p3573, !f2155

PUMP LIMPET TEST

Next: p703, !f2207

PUMP RUNNING

Next: p924, f2319

PUMP HARNESS CONTINUITY

REMOVE THE ELECTRICAL CONNECTOR FROM THE PUMP AND
THE PUMP CONNECTOR ST4 FROM THE PCB

Next: !p2322, !f2323

DIFFERENTIAL PLATE HEAT EX

ATTACH TEMPERATURE C

Next: p1788, f2334

INSPECTION PRESSURE SYSTEM

Next: p2763, !f2537

INSPECTION GAS SUPPLY TUBE

Next: p992, !f2571

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: !p2616, !f2617

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: !p2739, !f2740

DIFFERENTIAL PRIMARY HEAT EXCHANGER

CH TEMPERATURE CONTR

Next: p2742, !f2794

RESISTANCE SENSOR TEMP FLOW

DISCONNECT PLUG (RE

Next: p2759, !f2760

DHW SENSOR

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: !p2761, !f2762

PUMP LIMPET TEST

Next: p2741, !f2786

EXTERNAL CONTROLS VOLTAGE (RETURN)

{GAINPCBACS}
EXTERNAL CONTROLS CALLING FOR HEAT

Next: !p2806, f2807

VOLTS FROM TURBINE

SET FLOW RATE TO APPROX. 3 LITRES PER MINUTE

Next: p2898, f2899

RESISTANCE SENSOR TEMP FLOW AND HARNESS

DISCONNECT CONNECTOR

Next: p2904, f2905

RESISTANCE DHW SENSOR AND HARNESS

DISCONNECT CONNECTOR

Next: p3843, f2909

INSPECTION GAS SUPPLY TUBE

Next: p3260, !f2994

INSPECTION GAS SUPPLY TUBE

Next: !p3009, !f3008

INSPECTION GAS SUPPLY TUBE

Next: !p3011, !f3012

INSPECTION GAS SUPPLY TUBE

Next: !p3032, !f3033

SPARKING PRESENT TEST

REMOVE SPARK LEADS F

Next: p3061, f3062

CONDENSATE PIPE

Next: p3080, !f3081

INLET PRESSURE

ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT ON GAS VALVE

Next: p3082, !f3083

PRESSURE GAS INLET DROP

ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT ON GAS VALVE

Next: p3584, f3481

CHECK FLOW COMPONENTS

ISOLATE AND DRAIN TH

Next: !p3127, ?3129, ?3131, ?3133, ?3135

CONDENSATE PIPE

Next: p3400, !f3139

FAN PRESSURE TEST (IGNITION)

ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT

Next: p3140, f3663

RECTIFICATION VOLTAGE

{GAINPCBACS}

Next: !p3148, ?3150, ?3152

RESISTANCE HARNESS ELECTRODE SENSE TO EARTH

DISCONNECT CONNECTER

Next: !p3154, f3224

INTERNAL CLOCK

ANY EXTERNAL CH CONT

Next: !p3167, !f3168

INLET PRESSURE

ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT ON GAS VALVE

Next: p3137, !f393

VOLTAGE DIVERTER MOTOR SUPPLY PCB

NO DEMAND
REMOVE

Next: p3228, !f3229

DIVERTER VALVE HARNESS CONTINUITY

DISCONNECT ST17 CONN

Next: !p3230, !f3231

VOLTAGE DIVERTER MOTOR SUPPLY PCB

NO DEMAND
REMOVE

Next: p3233, !f3234

DIVERTER VALVE HARNESS CONTINUITY

DISCONNECT ST17 CONN

Next: !p3235, !f3236

INSPECTION FAN MEMBRANE

REMOVE FAN ASSEMBLY FROM APPLIANCE

Next: p2615, ?3292, ?3294

OBSERVATION ISOLATE DHW

TURN HOT WATER TAP ON

Next: !p3315, !f3341

TEMPERATURE DHW AT BOILER

Next: p2153, !f3340

PRIMARY SENSOR (HIGH FLAME)

DISCONNECT PLUG (RE

Next: p3389, !f3386

RESISTANCE DHW SENSOR

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: p2324, !f3399

INSPECTION GAS SUPPLY TUBE

Next: p3138, !f3434

ELECTRODE SENSE HARNESS

DISCONNECT FLAME SEN

Next: p3447, !f3448

ELECTRODE SENSE

REMOVE THE ELECTRODE ASSEMBLY

Next: p3449, !f3450

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: !p3451, !f3452

INSPECTION GAS SUPPLY TUBE

Next: p3455, !f3456

INSPECTION FAN MEMBRANE

REMOVE FAN ASSEMBLY FROM APPLIANCE

Next: p3457, ?3459, ?3461

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: !p3695, !f3464

RESISTANCE MECHANICAL TIMER (MT10)

Next: !p3469, !f3480

RESISTANCE OH STAT

DISCONNECT ONE OF THE ORANGE LEADS FROM THE OVERHEAT STAT

Next: p3509, !f3510

RESISTANCE FLUE OH STAT

DISCONNECT ONE OF THE ORANGE LEADS FROM THE OVERHEAT STAT

Next: !p3511, !f3512

VOLTAGE GAS VALVE AT PCB

{GAINPCBACS}
REMOVE THE GAS VALVE CONNECTORS FROM THE GAS VALVE AND MAKE SAFE

Next: p3514, f3535

RESISTANCE GAS VALVE SOLENOID MAIN AND HARNESS

DISCONNECT ST9 CONNE

Next: p3515, f3516

FAN PRESSURE TEST (IGNITION)

ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT

Next: p3519, f3520

INSPECTION GAS SUPPLY TUBE

Next: !p3533, !f3534

INSPECTION GAS SUPPLY TUBE

Next: p3523, !f3524

INSPECTION FAN MEMBRANE

REMOVE FAN ASSEMBLY FROM APPLIANCE

Next: p3525, ?3527, ?3529

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: !p3531, !f3532

RESISTANCE GAS VALVE HARNESS

REMOVE THE CONNECTOR

Next: !p3538, !f3539

RESISTANCE OH STAT

DISCONNECT ONE OF THE ORANGE LEADS FROM THE OVERHEAT STAT

Next: p3546, !f3547

RESISTANCE FLUE OH STAT

DISCONNECT ONE OF THE ORANGE LEADS FROM THE OVERHEAT STAT

Next: !p3548, !f3549

RESISTANCE OH STAT

DISCONNECT ONE OF THE ORANGE LEADS FROM THE OVERHEAT STAT

Next: p3569, !f3570

RESISTANCE FLUE OH STAT

DISCONNECT ONE OF THE ORANGE LEADS FROM THE OVERHEAT STAT

Next: !p3571, !f3572

DIFFERENTIAL PLATE HEAT EX

ATTACH TEMPERATURE C

Next: p3574, f3575

RESISTANCE DHW SENSOR AND HARNESS

DISCONNECT CONNECTOR

Next: p3578, f3579

RESISTANCE SENSOR TEMP FLOW

DISCONNECT PLUG (RE

Next: !p3582, !f3583

ELECTRODE SPARK HARNESS

REMOVE THE IGNITION HARNESS CONNECTION FROM THE
ELECTRODES TOP OF THE BURNER AND FROM THE PCB

Next: p3585, !f3586

INSPECTION GAS SUPPLY TUBE

Next: p3587, !f3588

INSPECTION FAN MEMBRANE

REMOVE FAN ASSEMBLY FROM APPLIANCE

Next: p3589, ?3591, ?3593

INSPECTION SPARK ELECTRODE

REMOVE THE ELECTRODE ASSEMBLY

Next: p3595, !f3596

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: p3597, !f3598

INSPECTION HEAT EXCHANGER

REMOVE FAN/MANIFOLD

Next: !p3599, !f3600

RESISTANCE DHW SENSOR

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: p3873, !f3614

INSPECTION DHW ISOLATION VALVE

Next: p3125, !f3626

INSPECTION DIVERTER VALVE PADDLE

REMOVE THE DIVERTER VALVE ACTUATOR FROM THE DIVERTER VALVE BODY

Next: p805, !f3633

VOLTS TO PUMP (PREHEAT)

{GAINPCBACS}
ENSURE PRIMARY HEAT EXCHANGER IS BELOW 40°C (TO ENSURE A DEMAND FOR PREHEAT)

Next: p3651, f3652

VOLTS TO PUMP (PREHEAT)

{GAINPCBACS}
ENSURE PRIMARY HEAT EXCHANGER IS BELOW 40°C (TO ENSURE A DEMAND FOR PREHEAT)

Next: p3639, f3640

PUMP HARNESS CONTINUITY

REMOVE THE ELECTRICAL CONNECTOR FROM THE PUMP AND
THE PUMP CONNECTOR ST4 FROM THE PCB

Next: !p3649, !f3650

RESISTANCE DHW SENSOR AND HARNESS

DISCONNECT CONNECTOR

Next: !p3645, f3646

PUMP HARNESS CONTINUITY

REMOVE THE ELECTRICAL CONNECTOR FROM THE PUMP AND
THE PUMP CONNECTOR ST4 FROM THE PCB

Next: !p3661, !f3662

RESISTANCE DHW SENSOR AND HARNESS

DISCONNECT CONNECTOR

Next: !p3657, f3658

INSPECTION FAN MEMBRANE

REMOVE FAN ASSEMBLY FROM APPLIANCE

Next: p3665, ?3666, ?3668

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: !p3677, !f3671

INSPECTION FLUE

Next: p3454, !f3694

INSPECTION GAS SUPPLY TUBE

Next: p3700, !f3701

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: !p3709, !f3703

INSPECTION CODE PLUG

LOWER THE FACIA PANEL

Next: p3771, !f3772

RESISTANCE SENSOR TEMP FLOW AND HARNESS

DISCONNECT CONNECTOR

Next: p3773, f3774

RESISTANCE DHW SENSOR AND HARNESS

DISCONNECT CONNECTOR

Next: !p3777, f3778

FAN PRESSURE TEST

ATTACH PRESSURE GAUG

Next: p3795, f3796

INLET PRESSURE

ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT ON GAS VALVE

Next: p3811, !f3812

INSPECTION FLUE

Next: p3799, !f3800

INSPECTION GAS SUPPLY TUBE

Next: p3801, !f3802

INSPECTION FAN MEMBRANE

REMOVE FAN ASSEMBLY FROM APPLIANCE

Next: p3803, ?3805, ?3807

BURNER INSPECTION

REMOVE FAN/MANIFOLD ASSEMBLY
REMOVE THE BURNER/BAFFLES ASSEMBLY

Next: !p3809, !f3810

COMBUSTION ANALYSIS MAX AND MIN

UNCLIP DIVERTER VALVE HEAD FROM THE BODY AND LEAVE IN A SAFE POSITION

Next: p3813, ?3815, ?3817

SPARKING PRESENT TEST

REMOVE SPARK LEADS F

Next: p3823, !f3824

INSPECTION GAS SUPPLY TUBE

Next: !p3821, !f3822

INSPECTION GAS SUPPLY TUBE

Next: !p3819, !f3820

CONDENSATE PIPE

Next: p3825, !f3826

INSPECTION FLUE OH STAT

Next: p3827, !f3828

INSPECTION GAS SUPPLY TUBE

Next: p3829, !f3830

ELECTRODE SENSE HARNESS

DISCONNECT FLAME SEN

Next: p3831, !f3832

ELECTRODE SPARK HARNESS

REMOVE THE IGNITION HARNESS CONNECTION FROM THE
ELECTRODES TOP OF THE BURNER AND FROM THE PCB

Next: p3833, !f3834

INSPECTION ELECTRODES

REMOVE THE ELECTRODE ASSEMBLY

Next: p3835, !f3836

INSPECTION FAN MEMBRANE

REMOVE FAN ASSEMBLY FROM APPLIANCE

Next: !p3837, ?3839, ?3841

OBSERVATION FAN TYPE

Next: p3844, f3845

VOLTAGE FAN (AT PCB)

MOVE CONNECTOR ST5 U

Next: p3857, ?3859, ?3861

VOLTAGE FAN (PCB DEMAND)

DISCONNECT ELECTRICA

Next: p3853, !f3854

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p3851, !f3852

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p3855, !f3856

VOLTAGE FAN (PCB DEMAND)

DISCONNECT ELECTRICA

Next: p3867, !f3868

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: p3863, !f3864

INSPECTION FAN

REMOVE PCB FROM FAN ASSEMBLY (FOR INSTRUCTIONS CLICK HERE)

Next: !p3865, !f3866

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: p3869, !f3870

INSPECTION FAN

REMOVE PCB FROM FAN ASSEMBLY (FOR INSTRUCTIONS CLICK HERE)

Next: !p3871, !f3872

OBSERVATION FAN TYPE

Next: p3874, f3875

FAN VOLTAGE CONTROL (PCB)

{GAINPCBACS}
MOVE CONNECTOR ST5 TO EXPOSE TERMINALS ON PCB

Next: p3887, ?3889, ?3891

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p3885, !f3886

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p3883, !f3884

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p3881, !f3882

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: p3899, !f3900

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: p3895, !f3896

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p3893, !f3894

INSPECTION FAN

REMOVE PCB FROM FAN ASSEMBLY (FOR INSTRUCTIONS CLICK HERE)

Next: !p3897, !f3898

INSPECTION FAN

REMOVE PCB FROM FAN ASSEMBLY (FOR INSTRUCTIONS CLICK HERE)

Next: !p3901, !f3902

INSPECTION FAN

REMOVE PCB FROM FAN ASSEMBLY (FOR INSTRUCTIONS CLICK HERE)

Next: !p3908, !f3909

OBSERVATION FAN TYPE

Next: p3912, f3913

FAN VOLTAGE CONTROL (PCB)

{GAINPCBACS}
MOVE CONNECTOR ST5 TO EXPOSE TERMINALS ON PCB

Next: p3925, ?3927, ?3929

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p3923, !f3924

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p3921, !f3922

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p3919, !f3920

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: p3937, !f3938

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: p3933, !f3934

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p3931, !f3932

INSPECTION FAN

REMOVE PCB FROM FAN ASSEMBLY (FOR INSTRUCTIONS CLICK HERE)

Next: !p3935, !f3936

INSPECTION FAN

REMOVE PCB FROM FAN ASSEMBLY (FOR INSTRUCTIONS CLICK HERE)

Next: !p3939, !f3940

OBSERVATION FAN TYPE

Next: p3942, f3943

VOLTAGE FAN (AT PCB)

MOVE CONNECTOR ST5 U

Next: p3955, ?3957, ?3959

VOLTAGE FAN (PCB DEMAND)

DISCONNECT ELECTRICA

Next: p3951, !f3952

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p3949, !f3950

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: !p3953, !f3954

VOLTAGE FAN (PCB DEMAND)

DISCONNECT ELECTRICA

Next: p3967, !f3968

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: p3973, !f3962

RESISTANCE FAN HARNESS

DISCONNECT CONNECTOR FROM THE FAN ASSEMBLY

Next: p3969, !f3970

INSPECTION FAN

REMOVE PCB FROM FAN ASSEMBLY (FOR INSTRUCTIONS CLICK HERE)

Next: !p3971, !f3972

INSPECTION FAN

REMOVE PCB FROM FAN ASSEMBLY (FOR INSTRUCTIONS CLICK HERE)

Next: !p3974, !f3975

VOLTAGE MAINS GND PWM AND HALL

REMOVE THE CONNECTOR

Next: p3850, !f3987

VOLTAGE MAINS GND PWM AND HALL

REMOVE THE CONNECTOR

Next: p3862, !f3986

VOLTAGE MAINS GND PWM AND HALL

REMOVE THE CONNECTOR

Next: p3960, !f3998

VOLTAGE MAINS GND PWM AND HALL

REMOVE THE CONNECTOR

Next: p3948, !f3999

DHW SENSOR

REMOVE YELLOW WIRES FROM DHW SENSOR

Next: p678, !f674

DIFFERENTIAL PLATE HEAT EX

ATTACH TEMPERATURE C

Next: !p675, !f677

PRIMARY SENSOR (HIGH FLAME)

DISCONNECT PLUG (RE

Next: p673, !f682

PUMP LIMPET TEST

Next: p672, !f697

CH OPERATION

CH TEMPERATURE CONTROL SET TO MAX

Next: !p704, !f2796

INSPECTION VESSEL PRESSURE

CLOSE FLOW AND RETURN ISOLATION VALVES
DISCHARGE PRIMARY SYSTEM WATER

Next: !p718, !f719

INSPECTION PRESSURE SYSTEM

Next: p2184, !f760

INSPECTION PRESSURE SYSTEM

Next: p3320, !f759

INSPECTION PRESSURE SYSTEM

Next: p683, !f771

PUMP LIMPET TEST

Next: p775, !f776

PRIMARY SENSOR (HIGH FLAME)

DISCONNECT PLUG (RE

Next: p1868, !f778

INSPECTION PRESSURE SYSTEM

Next: p774, !f785

INSPECTION PRESSURE SYSTEM

Next: p152, !f804

PUMP LIMPET TEST

Next: p815, !f811

BYPASS (INTERNAL)

ENSURE RADS ARE OPEN AND WATER CAN CIRCULATE AROUND THE SYSTEM
USE AN FGA TEMPERATURE PROBE

Next: !p834, !f934

DIVERTER VALVE ACTUATOR OPERATION

REMOVE THE DIVERTER

Next: p3627, f3180

INSPECTION PRESSURE SYSTEM

Next: p2307, !f925

PUMP LIMPET TEST

Next: p3372, !f926

CONDENSATE PIPE

Next: p989, !f988

INLET PRESSURE

ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT ON GAS VALVE

Next: p990, !f991

FAN PRESSURE TEST (IGNITION)

ATTACH PRESSURE GAUGE TO FAN PRESSURE TEST POINT

Next: p2567, f2042

INSPECTION FLUE

Next: p2738, !f1011

System Information

  • Total Tests: 641
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control