Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
CH potentiometer set to MAX
Attach temperature clamps to flow and return pipes
Attach temperature clamps to flow and return pipes
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Allow boiler operate until noise begins.
Measure the temperature of the flow and return pipes as close to the boiler as possible and ascertain temperature difference between flow and return.
Expected differential 20°c or lower.
Notes:
To reduce the time for the test the heating load can be reduced
by turning off some radiators.
Differential may be higher at initial system startup.
Measure the temperature of the flow and return pipes as close to the boiler as possible and ascertain temperature difference between flow and return.
Expected differential 20°c or lower.
Notes:
To reduce the time for the test the heating load can be reduced
by turning off some radiators.
Differential may be higher at initial system startup.