Set Appliance State:
CH Demand
Isolate Mains Power to appliance as per TOPs P4
Boiler ON/OFF switch ON
Room thermostat (if fitted) calling
Attach temperature clamps to flow and return pipes
Boiler ON/OFF switch ON
Room thermostat (if fitted) calling
Attach temperature clamps to flow and return pipes
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow boiler to ignite and reach a reasonable flow temperature, e.g. 55°C.
Measure the differential across the flow and return pipe?
Expect approximately 18°C or less.
Measure the differential across the flow and return pipe?
Expect approximately 18°C or less.