Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Turn Hot Water Tap On
Attach a tube from the + port on the telegan to the fan pressure test point
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Allow the fan to run and the ignition sequence to commence.
During the ignition phase a positive pressure should be recorded.
During the ignition phase a positive pressure should be recorded.