Set Appliance State:
Isolate Mains Power to appliance as per TOPs P4
Remove the two wires from the low water pressure switch noting their locations
Ensure system pressure is correctly set
Remove the two wires from the low water pressure switch noting their locations
Ensure system pressure is correctly set
Measurement:
Measure the resistance between the two exposed terminal of the low water pressure switch where the wires were previously connected.
Expect continuity / zero resistance.
Is the resistance measured as expected?
Note:
Low pressure switch is shown removed for clarity but test is carried out with it in situ.
Expect continuity / zero resistance.
Is the resistance measured as expected?
Note:
Low pressure switch is shown removed for clarity but test is carried out with it in situ.

Isolate as per TOPs P4
and refit as necessary