Set Appliance State:
Mains Power Off
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
NOV2018
Isolate Mains Power to appliance as per TOPs P4
CH or HW Demand
WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure
Mains Power ON
Check the operation of the pump, ensure the wiring to the pump is secure and that the impeller and shaft are free to rotate.
If it is available to you, you can perform a limpet test on the pump. Note however that the Limpet probe is not compatible with the FZ-G1 tablet and, due to functional differences, Limpet may not work reliably on ERP pumps.
Click here for a Quick Guide to Checking Pumps
Click here for a Quick Guide to Checking Pumps
Isolate as per TOPs P4
and refit as necessary