Set Appliance State:
Mains Power Off
Gas Off
CH Demand
Keep Boiler Case Switch depressed
| WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure |
Measurement:
Measure the voltage across terminal 6 (marked AMBIENT THERMOSTAT) and the neutral terminal 1 (Blue wire, marked N) on the main terminal block.
Note:
If no room thermostat is fitted there should be a link wire connected between terminals 5 and 6 on the main terminal block.
Note:
If no room thermostat is fitted there should be a link wire connected between terminals 5 and 6 on the main terminal block.

Isolate as per TOPs P4
and refit as necessary