XSol Diagnostic System

Interactive Test Sequence Navigator

Welcome to the XSol Diagnostic System

This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.

Start Diagnostic Sequence

or choose a specific test below:

BG RD628

GLOBALLY REPLACED

Next: &6, *

DHW FAN RUNS

DHW TEMPERATURE CONTROL SET TO MAXIMUM
ENSURE NO DEMAND FOR CH

Next: &11, ?40, ?651, ?653

DHW FLOW RATE

Next: &3, f1052

BG RD628

{ISOLATEMAINSPOWER}<

Next: &1350, !f15

CH OPERATION

CH TEMPERATURE CONTROL SET TO MAXIMUM

Next: &13, ?254, ?256, ?258

DHW OPERATION

DHW TEMPERATURE CONTROL SET TO MAXIMUM

Next: &1399, ?248, ?250, ?252, ?420, ?1419

BURNER FULL RATE

{ISOLATEMAINSPOWER}<

Next: &1407, f23

DHW BURNER IGNITES

DHW TEMPERATURE CONTROL SET TO MAXIMUM

Next: &9, ?129, ?131, ?1138, ?1155

OVERRUNS

Next: &nff, f27

SYSTEM PRESSURE RISE

Next: &12, !f26

CH DEMAND

CH TEMPERATURE CONTR

Next: &7, ?1000, ?1009

FAULT CODE SLOW FLASH

OUTSIDE MODEL

Next: &nff, f1167

FAULT CODE FAST FLASH

OUTSIDE MODEL

Next: &nff, f1281

FURTHER INVESTIGATION MELTED APS

OUTSIDE MODEL

Next: &nff, f1333

OBSERVATION BOILER STANDBY

ENSURE NO DEMANDS

Next: &5, ?1351, ?1353, ?1355

OBSERVATION DHW MODULATION

{ISOLATEMAINSPOWER}<

Next: &448, f1400

PRESSURE BURNER MINIMUM RATE

{ISOLATEMAINSPOWER}<

Next: &8, !f1408

CH DEMAND PROGRAMMER FITTED

CONTROL BOARD

Next: End

PUMP DOES NOT RUN

CONTROL BOARD

Next: End

PUMP DOES NOT RUN

HARNESS PUMP

Next: End

CH OPERATION CH NOISY OPERATION

PIPE - BYPASS

Next: End

CH OPERATION CH NOISY OPERATION

NTC / THERMISTOR CH

Next: End

CH OPERATION CH NOISY OPERATION

CONTROL BOARD

Next: End

FAN DOES NOT RUN

KIT THERMISTOR SENSOR - PRIMARY / DOMESTIC

Next: End

DHW FLOW RATE

VALVE - DCW IN

Next: End

DHW FLOW RATE

FLOW REGULATOR C/W FILTER

Next: End

DHW FLOW RATE

FLOW REGULATOR

Next: End

DHW FLOW RATE

WATER SUPPLY

Next: End

DHW FLOW SWITCH DHW FAN RUNS

HARNESS - MAIN

Next: End

DHW FLOW SWITCH GREEN WIRE

HARNESS - MAIN

Next: End

NO SPARKING

HEAT EXCHANGER FLUE WAYS

Next: End

BURNER ESTABLISHES

SET - ELECTRODES - FLAME AND IGNITION

Next: End

BURNER ESTABLISHES

HARNESS - END FLAME SENSE

Next: End

BURNER ESTABLISHES

NTC / THERMISTOR CH

Next: End

BURNER ESTABLISH

KIT THERMISTOR SENSOR - PRIMARY / DOMESTIC

Next: End

BURNER ESTABLISHES

GAS INLET PRESSURE

Next: End

BURNER ESTABLISHES

HEAT EXCHANGER FLUE WAYS

Next: End

BURNER ESTABLISHES

FLUE

Next: End

BURNER ESTABLISHESIGNITES BUT BAFFLES

GAS INLET PRESSURE

Next: End

BURNER ESTABLISHESIGNITES BUT BAFFLES

HEAT EXCHANGER FLUE WAYS

Next: End

BURNER IGNITES BUT BAFFLES

BURNER

Next: End

SLOW FLASH NOT RESETTING

THERMOSTAT OVERHEAT

Next: End

SLOW FLASH FAN DOES NOT RUN

PROBE - AIR PRESSURE SENSING

Next: End

SLOW FLASH

CODE PLUG

Next: End

SLOW FLASH NO SPARKING

SET - ELECTRODES - FLAME AND IGNITION

Next: End

SLOW FLASH NO SPARKING

WIRE - IGNITION

Next: End

SLOW FLASH CUTTING OUT ON RAMP UP

GAS INLET PRESSURE

Next: End

SLOW FLASH POOR CONDITION OR GAP

SET - ELECTRODES - FLAME AND IGNITION

Next: End

SLOW FLASH OPEN CCT

SET - ELECTRODES - FLAME AND IGNITION

Next: End

SLOW FLASH NOT ESTABLISHING

BURNER MANIFOLD

Next: End

SLOW FLASH NOT ESTABLISHING

GAS INLET PRESSURE

Next: End

SLOW FLASH NOT IGNITING

GAS INLET PRESSURE

Next: End

SLOW FLASH NOT IGNITING

SET - ELECTRODES - FLAME AND IGNITION

Next: End

SLOW FLASH OVERHEAT INVESTIGATION

SYSTEM PRESSURE

Next: End

SLOW FLASH NO POWER TO EXT CONTROLS

CONTROL BOARD

Next: End

SLOW FLASH NO POWER TO PUMP

CONTROL BOARD

Next: End

SLOW FLASH PUMP DOES NOT RUN

HARNESS PUMP

Next: End

SLOW FLASH RUNNING SLOW

PUMP

Next: End

SLOW FLASH BOTH PRESSURES OUT

GAS INLET PRESSURE

Next: End

SLOW FLASH MAXIMUM OUT

GAS INLET PRESSURE

Next: End

SLOW FLASH NO POWER TO MODUREG

CONTROL BOARD

Next: End

SLOW FLASH GAS VALVE MODUREG

HARNESS - MAIN

Next: End

SLOW FLASH MINIMUM OUT

GAS INLET PRESSURE

Next: End

SLOW FLASH NOT MODULATING DHW

KIT THERMISTOR SENSOR - PRIMARY / DOMESTIC

Next: End

SLOW FLASH NOT MODULATING

NTC / THERMISTOR CH

Next: End

SLOW FLASH OVERHEAT INVESTIGATION

PIPE - BYPASS

Next: End

FAST FLASH FIRES WITH NO DEMAND

CONTROL BOARD SERVICE POTENTIOMETER

Next: End

FAST FLASH

CODE PLUG

Next: End

FAST FLASH

KIT THERMISTOR SENSOR - PRIMARY / DOMESTIC

Next: End

FAST FLASH

NTC / THERMISTOR CH

Next: End

FAST FLASH POSITIONING

HARNESS - MAIN

Next: End

FAST FLASH SHORT CCT

PROBE - AIR PRESSURE SENSING

Next: End

FAST FLASH SHORT CCT

AIR PRESSURE SWITCH

Next: End

FAST FLASH RESISTANCE

HARNESS FAN

Next: End

FAST FLASH OPEN CCT

AIR PRESSURE SWITCH

Next: End

FAST FLASH OPEN CCT

PROBE - AIR PRESSURE SENSING

Next: End

FAST FLASH OPEN CCT

FLUE

Next: End

MELTED FAN MOTOR FAULTY

FAN + AIR PRESSURE SWITCH

Next: End

FURTHER INF MELTED APS

HARNESS FAN + APS

Next: End

MELTED APS STIFF

FAN + AIR PRESSURE SWITCH

Next: End

FAN RUNS 35 SECONDS SHORT TIME

HEAT EXCHANGER FLUE WAYS

Next: End

OBSERVATION BOILER STANDBY

FROST PROTECTION

Next: End

OBSERVATION BOILER STANDBY

TAP OPEN OR LEAK

Next: End

OBSERVATION BOILER STANDBY - FIRES WITH NO DEMAND

CONTROL BOARD SERVICE POTENTIOMETER

Next: End

OBSERVATION BOILER STANDBY - FIRES NO DEMAND

NTC / THERMISTOR CH

Next: End

OBSERVATION BOILER STANDBY

KIT THERMISTOR SENSOR - PRIMARY / DOMESTIC

Next: End

OBSERVATION BOILER STANDBY - FAN RUNS CONTINUALLY

CONTROL BOARD SERVICE POTENTIOMETER

Next: End

GAS VALVE NO IGNITION

HARNESS - MAIN

Next: End

DHW BURNER IGNITES (SPARKING)

CONTROL BOARD

Next: End

BURNER FULL RATE

HARNESS - MAIN

Next: End

BURNER FULL RATE

NTC / THERMISTOR CH

Next: End

BURNER FULL RATE

KIT THERMISTOR SENSOR - PRIMARY / DOMESTIC

Next: End

OBSERVATION DHW MODULATION

NTC / THERMISTOR CH

Next: End

OBSERVATION DHW MODULATION

KIT THERMISTOR SENSOR - PRIMARY / DOMESTIC

Next: End

PRESSURE BURNER MINIMUM RATE

GAS VALVE ADJUSTMENT

Next: End

SLOW FLASH NOT IGNITING

HARNESS - MAIN

Next: End

SLOW FLASH NOT IGNITING

CONTROL BOARD

Next: End

FAN RUNS FOR 2 SECONDS

HARNESS FAN

Next: End

DHW COOL RADS WARM

Next: End

DHW COOL RADS HEAT

NTC / THERMISTOR CH

Next: End

DHW COOL RADS HEAT

KIT THERMISTOR SENSOR - PRIMARY / DOMESTIC

Next: End

ELECTRICAL SAFETY CHECKS

ELECTRICAL SAFETY CHECKS

Next: End

SYSTEM PRESSURE RISE

EXPANSION VESSEL

Next: End

OVERRUNS

NTC / THERMISTOR CH

Next: End

BURNER FULL RATE

GAS INLET PRESSURE

Next: End

DHW OPERATION

NTC / THERMISTOR CH

Next: End

DHW OPERATION

KIT THERMISTOR SENSOR - PRIMARY / DOMESTIC

Next: End

DHW OPERATION

BURNER MANIFOLD

Next: End

DHW OPERATION DHW TOO HOT

NTC / THERMISTOR CH

Next: End

DHW OPERATION DHW TOO HOT

KIT THERMISTOR SENSOR - PRIMARY / DOMESTIC

Next: End

DHW OPERATION DHW RUNS HOT THEN COLD

NTC / THERMISTOR CH

Next: End

DHW OPERATION DHW RUNS HOT THEN COLD

THERMOSTAT OVERHEAT

Next: End

DHW OPERATION DHW RUNS HOT THEN COLD

KIT THERMISTOR SENSOR - PRIMARY / DOMESTIC

Next: End

CH OPERATION BOILER COOL RADIATORS COOL

NTC / THERMISTOR CH

Next: End

OPERATIONAL SEQUENCE

SYSTEM CHECKS

Next: End

DHW FAN RUNS (FAN DOES NOT RUN)

TRANSFORMER

Next: End

FAN2

HARNESS FAN

Next: End

DHW FAN RUNS (FAN RUNS)

AIR PRESSURE SWITCH

Next: End

DHW FAN RUNS (FAN RUNS)

PROBE - AIR PRESSURE SENSING

Next: End

DHW FAN RUNS (FAN RUNS)

FLUE

Next: End

DHW BURNER IGNITES (NO SPARKING)

SET - ELECTRODES - FLAME AND IGNITION

Next: End

DHW BURNER IGNITES (NO SPARKING)

WIRE - IGNITION

Next: End

DHW FAN RUNS (NO SPARKING)

PROBE - AIR PRESSURE SENSING

Next: End

DHW FAN RUNS (NO SPARKING)

AIR PRESSURE SWITCH

Next: End

DHW FAN RUNS (FAN DOES NOT RUN)

PROBE - AIR PRESSURE SENSING

Next: End

DHW FAN RUNS (FAN DOES NOT RUN)

NTC / THERMISTOR CH

Next: End

DHW FAN RUNS (FAN DOES NOT RUN)

CODE PLUG

Next: End

DHW FAN RUNS (FAN RUNS)

KIT THERMISTOR SENSOR - PRIMARY / DOMESTIC

Next: End

DHW FAN RUNS (FAN RUNS)

THERMOSTAT OVERHEAT

Next: End

FAN RUNS SHORT TIME

NTC / THERMISTOR CH

Next: End

DHW BURNER IGNITES SPARKING PRESENT

THERMOSTAT OVERHEAT

Next: End

DHW BURNER IGNITES (SPARKING)

GAS INLET PRESSURE

Next: End

DHW BURNER IGNITES (SPARKING)

SET - ELECTRODES - FLAME AND IGNITION

Next: End

CH DEMAND

Next: End

CH DEMAND PROGRAMMER FITTED

INTEGRAL PROGRAMMER

Next: End

PUMP DOES NOT RUN

PUMP

Next: End

CH OPERATION CH NOISY OPERATION

HEAT EXCHANGER

Next: End

DHW FAN RUNS

CONTROL BOARD

Next: End

DHW SENSOR FAN DOES NOT RUN

HARNESS - MAIN

Next: End

DHW FAN RUNS (FAN DOES NOT RUN)

SENSOR - FLOW

Next: End

DHW FAN RUNS FLOW SWITCH VOLTAGE IN

CONTROL BOARD

Next: End

BURNER ESTABLISHES

CONTROL BOARD

Next: End

IGNITES BUT BAFFLES

GAS VALVE

Next: End

SLOW FLASH SAFETY CIRCUIT

HARNESS - MAIN

Next: End

SLOW FLASH FAN DOES NOT RUN

CONTROL BOARD

Next: End

SLOW FLASH FAN DOES NOT RUN

HARNESS - MAIN

Next: End

SLOW FLASH FAN DOES NOT RUN

AIR PRESSURE SWITCH

Next: End

SLOW FLASH STUCK IN FAULT

CONTROL BOARD

Next: End

SLOW FLASH NO SPARKING

CONTROL BOARD

Next: End

SLOW FLASH INCORRECT PRESSURE

GAS VALVE

Next: End

SLOW FLASH NOT RECOGNISING FLAME

CONTROL BOARD

Next: End

SLOW FLASH CUTTING OUT

GAS VALVE

Next: End

SLOW FLASH NOT IGNITING

BURNER MANIFOLD

Next: End

SLOW FLASH BOTH PRESSURES OUT

GAS VALVE

Next: End

SLOW FLASH MAXIMUM OUT

GAS VALVE

Next: End

SLOW FLASH WRONG VOLTAGE TO MODUREG

CONTROL BOARD

Next: End

SLOW FLASH MINIMUM OUT

GAS VALVE

Next: End

SLOW FLASH NOT MODULATING ON DHW

CONTROL BOARD

Next: End

SLOW FLASH NOT MODULATING ON CH

CONTROL BOARD

Next: End

SLOW FLASH OVERHEAT INVESTIGATION

HEAT EXCHANGER

Next: End

SLOW FLASH NO FAULT

NORMAL OPERATION

Next: End

SLOW FLASH STUCK ON

CONTROL BOARD

Next: End

SLOW FLASH CUTTING OUT EARLY

THERMOSTAT OVERHEAT

Next: End

FAST FLASH FIRING WITH NO DEMAND

CONTROL BOARD

Next: End

FAST FLASH DHW THERMISTOR

HARNESS - MAIN

Next: End

FAST FLASH CH THERMISTOR

HARNESS - MAIN

Next: End

FAST FLASH STUCK IN FAULT

CONTROL BOARD

Next: End

FAST FLASH NEUTRAL FAULT FAN

CONTROL BOARD

Next: End

FAST FLASH NO POWER TO FAN

CONTROL BOARD

Next: End

FAST FLASH APS SHORT CCT

HARNESS - MAIN

Next: End

FAST FLASH APS SHORTED

Z REDIRECTION

Next: End

FAST FLASH INCORRECT RESISTANCE

FAN ASSEMBLY

Next: End

FAST FLASH APS OPEN CCT

Z REDIRECTION

Next: End

FAST FLASH RUNNING SLOW

FAN ASSEMBLY

Next: End

MELTED APS

CONTROL BOARD + AIR PRESSURE SWITCH

Next: End

DHW FLOW RATE

HEAT EXCHANGER (DHW FLOW RATE)

Next: End

OBSERVATION BOILER STANDBY

CONTROL BOARD

Next: End

OBSERVATION BOILER STANDBY DHW SENSOR

HARNESS - MAIN

Next: End

BURNER FULL RATE

GAS VALVE

Next: End

BURNER FULL RATE

GAS VALVE ADJUSTMENT

Next: End

BURNER FULL RATE

CONTROL BOARD

Next: End

OBSERVATION DHW MODULATION

GAS VALVE

Next: End

OBSERVATION DHW MODULATION

CONTROL BOARD

Next: End

DHW COOL RADS HEAT PRIMARY SENSOR

HARNESS - MAIN

Next: End

DHW COOL RADS HEAT

CONTROL BOARD

Next: End

DHW COOL RADS HEAT DHW SENSOR

HARNESS - MAIN

Next: End

DHW FAN RUNS (FAN DOES NOT RUN)

TUBING 5M LONG SILICONE

Next: End

FAULTY

TEE PIECE

Next: End

FAN RUNS CH (FAN RUNS)

TUBING 5M LONG SILICONE

Next: End

FAULTY 2

TEE PIECE

Next: End

FAN RUNS CH (NO SPARKING)

TUBING 5M LONG SILICONE

Next: End

FAULTY 3

TEE PIECE

Next: End

FAST FLASH OPEN CCT

TUBING 5M LONG SILICONE

Next: End

FAULTY 4

TEE PIECE

Next: End

FAST FLASH SHORT CCT

TUBING 5M LONG SILICONE

Next: End

FAULTY 5

TEE PIECE

Next: End

SLOW FLASH FAN DOES NOT RUN

TUBING 5M LONG SILICONE

Next: End

FAULTY 6

TEE PIECE

Next: End

DHW OPERATION DHW NOISY OPERATION

HEAT EXCHANGER

Next: End

OVERRUNS

CONTROL BOARD

Next: End

DHW OPERATION DHW TOO COLD

HEAT EXCHANGER

Next: End

DHW OPERATION DHW RUNS HOT THEN COLD

CONTROL BOARD

Next: End

DHW OPERATION DHW TOO HOT

CONTROL BOARD

Next: End

CH OPERATION BOILER COOL RADIATORS COOL

CONTROL BOARD

Next: End

NO NEUTRAL

CONTROL BOARD

Next: End

DHW FAN RUNS 2

CONTROL BOARD

Next: End

DHW FAN RUNS (FAN DOES NOT RUN)

CONTROL BOARD

Next: End

DHW FAN RUNS (FAN DOES NOT RUN)

FAN ASSEMBLY

Next: End

DHW FAN RUNS (FAN RUNS)

FAN ASSEMBLY

Next: End

DHW BURNER IGNITES (NO SPARKING)

CONTROL BOARD

Next: End

DHW FAN RUNS (NO SPARKING)

FAN ASSEMBLY

Next: End

DHW FAN RUNS (FAN DOES NOT RUN)

AIR PRESSURE SWITCH

Next: End

PRIMARY SENSOR DHW FAN RUNS

HARNESS - MAIN

Next: End

APS DHW FAN RUNS

HARNESS - MAIN

Next: End

DHW FAN RUNS (FAN RUNS)

CONTROL BOARD

Next: End

FAN RUNS SHORT TIME OVERHEAT

HARNESS - MAIN

Next: End

DHW BURNER IGNITES (SPARKING)

BURNER MANIFOLD

Next: End

OVERHEAT SPARKING

HARNESS - MAIN

Next: End

PUMP DOES NOT RUN AND BURNER DOES NOT IGNITE

CHARACTERISTIC TEST FROM CH DEMAND

Next: p1002

PUMP DOES NOT RUN BUT BURNER IGNITES

CHARACTERISTIC TEST FROM CH DEMAND

Next: p1010

BURNER IGNITES BUT SPARKING CONTINUES UNTIL LOCKOUT

CHARACTERISTIC TEST FROM DHW BURNER IGNITES

Next: p1140

BURNER IGNITES AND ESTABLISHES BUT BAFFLES

CHARACTERISTIC TEST FROM DHW BURNER IGNITES

Next: p1157

APPLIANCE RESETS, FAN RUNS BUT EITHER DOES NOT IGNITE OR FLAME DOES NOT ESTABLISH

CHARACTERISTIC TEST FROM OBSERVATION BOILER RESET SLOW FLASH

Next: p1175

BOILER WILL NOT RESET OR RESETS AND IMMEDIATELY RETURNS TO FAULT CODE

CHARACTERISTIC TEST FROM OBSERVATION BOILER RESET SLOW FLASH

Next: p1177

FAN DOES NOT RUN, FAULT CODE REOCCURS IN APPROX 30 SECONDS

CHARACTERISTIC TEST FROM OBSERVATION BOILER RESET SLOW FLASH

Next: p1179

BURNER IGNITES, SPARK STOPS, FLAME DIES AWAY, SPARK RESTARTS

CHARACTERISTIC TEST FROM DHW BURNER IGNITES (FAULT CODE)

Next: p1201

BURNER FULLY CROSSLIGHTS, SPARK DOESN T STOP, BOILER LOCKS OUT

CHARACTERISTIC TEST FROM DHW BURNER IGNITES (FAULT CODE)

Next: p1203

MINIMUM BURNER PRESSURE INCORRECT

CHARACTERISTIC TEST FROM PRESSURE BURNER MAX AND MIN

Next: p1245

MAXIMUM BURNER PRESSURE INCORRECT

CHARACTERISTIC TEST FROM PRESSURE BURNER MAX AND MIN

Next: p1247

BOTH MAXIMUM AND MINIMUM INCORRECT

CHARACTERISTIC TEST FROM PRESSURE BURNER MAX AND MIN

Next: p1249

BOILER TEMP ABOVE 85 DEGREES, BOILER STILL FIRING

CHARACTERISTIC TEST FROM INSPECTION LOCKOUT TEMPERATURE

Next: !p1277

BOILER GOES TO LOCKOUT UNDER 85 DEGREES

CHARACTERISTIC TEST FROM INSPECTION LOCKOUT TEMPERATURE

Next: !p1279

BOILER DOES NOT FIRE BUT REMAINS IN FAULT CODE

CHARACTERISTIC TEST FROM OBSERVATION BOILER RESET FAST FLASH

Next: p1284

BOILER FIRES WITH NO DEMAND

CHARACTERISTIC TEST FROM OBSERVATION BOILER RESET FAST FLASH

Next: p1286

Sparking present BUT BURNER DOES NOT IGNITE

CHARACTERISTIC TEST FROM DHW BURNER IGNITES

Next: p929

MAINS VOLTAGE ABSENT BOTH TESTS

CHARACTERISTIC TEST FROM VOLTAGE TO FAN HIGH SPEED

Next: p1305

MAINS VOLTAGE PRESENT BOTH TESTS

CHARACTERISTIC TEST FROM VOLTAGE TO FAN HIGH SPEED

Next: !p1307

No sparking

CHARACTERISTIC TEST FROM DHW BURNER IGNITES

Next: p776

FAN RUNS CONTINUALLY AS SOON AS POWER IS TURNED ON

CHARACTERISTIC TEST FROM OBSERVATION BOILER STANDBY

Next: p1352

PUMP RUNS OR BOILER FIRES WITH NO DEMAND

CHARACTERISTIC TEST FROM OBSERVATION BOILER STANDBY

Next: p1354

FAULT INDICATOR LIGHT FLASHING

CHARACTERISTIC TEST FROM OBSERVATION BOILER STANDBY

Next: p1356

DHW TOO COLD, RADIATORS BEGIN TO HEAT

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p1420

TUBES UNSATISFACTORY

CHARACTERISTIC TEST FROM AIR PRESSURE SWITCH TUBES

Next: !p1433

TEE UNSATISFACTORY

CHARACTERISTIC TEST FROM AIR PRESSURE SWITCH TUBES

Next: !p1435

TUBES UNSATISFACTORY

CHARACTERISTIC TEST FROM AIR PRESSURE SWITCH TUBES

Next: !p1438

TEE UNSATISFACTORY

CHARACTERISTIC TEST FROM AIR PRESSURE SWITCH TUBES

Next: !p1440

TUBES UNSATISFACTORY

CHARACTERISTIC TEST FROM AIR PRESSURE SWITCH TUBES

Next: !p1443

TEE UNSATISFACTORY

CHARACTERISTIC TEST FROM AIR PRESSURE SWITCH TUBES

Next: !p1445

TUBES UNSATISFACTORY

CHARACTERISTIC TEST FROM AIR PRESSURE SWITCH TUBES

Next: !p1448

TEE UNSATISFACTORY

CHARACTERISTIC TEST FROM AIR PRESSURE SWITCH TUBES

Next: !p1450

TUBES UNSATISFACTORY

CHARACTERISTIC TEST FROM AIR PRESSURE SWITCH TUBES

Next: !p1453

TEE UNSATISFACTORY

CHARACTERISTIC TEST FROM AIR PRESSURE SWITCH TUBES

Next: !p1455

TUBES UNSATISFACTORY

CHARACTERISTIC TEST FROM AIR PRESSURE SWITCH TUBES

Next: !p1458

TEE UNSATISFACTORY

CHARACTERISTIC TEST FROM AIR PRESSURE SWITCH TUBES

Next: !p1460

DHW noisy operation

CHARACTERISTIC TEST FROM DHW OPERATION

Next: !p249

DHW TOO COLD, RADIATORS COLD

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p251

DHW too hot

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p253

CH noisy operation

CHARACTERISTIC TEST FROM CH OPERATION

Next: p1018

Boiler to temperature, radiators cool

CHARACTERISTIC TEST FROM CH OPERATION

Next: p1015

Boiler and radiators cool

CHARACTERISTIC TEST FROM CH OPERATION

Next: p259

Fan does not run

CHARACTERISTIC TEST FROM DHW FAN RUNS

Next: p703

DHW runs hot then cold

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p424

Fan runs for approximately 2 seconds then stops

CHARACTERISTIC TEST FROM DHW FAN RUNS

Next: p652

Fan runs for approximately 35 seconds then stops

CHARACTERISTIC TEST FROM DHW FAN RUNS

Next: p740

MAINS VOLTAGE ABSENT BOTH TESTS

CHARACTERISTIC TEST FROM VOLTAGE TO FAN HIGH SPEED

Next: p706

MAINS VOLTAGE PRESENT BOTH TESTS

CHARACTERISTIC TEST FROM VOLTAGE TO FAN HIGH SPEED

Next: !p708

EXTERNAL CONTROLS VOLTAGE INPUT

Next: !p1005, !f1006

RESISTANCE DHW SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE DHW SENSOR

Next: !p1050, !f1051

OBSERVATION COLD MAINS SUPPLY

TURN COLD WATER TAP ON

Next: p1053, !f1060

VOLTAGE DHW FLOW SWITCH IN

Next: !p1122, f1123

RESISTANCE HARNESS DHW FLOW SWITCH

{ISOLATEMAINSPOWER}
DISCONNECT INLINE CONNECTOR FROM FLOW SENSOR
DISCONNECT ST16 PLUG FROM PCB

Next: !p1124, !f1125

RESISTANCE OVERHEAT THERMOSTAT AT PCB

{ISOLATEMAINSPOWER}
REMOVE CONNECTOR ST16 FROM THE PCB

Next: p1168, f1169

OVERHEAT THERMOSTAT

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE OVERHEAT THERMOSTAT

Next: !p1170, !f1171

AIR PRESSURE SWITCH N/O

{ISOLATEMAINSPOWER}
REMOVE THE BLUE WIRE FROM THE AIR PRESSURE SWITCH

Next: !p1182, f1183

AIR PRESSURE SWITCH TUBES

{ISOLATEMAINSPOWER}

Next: p1184, ?1457, ?1459

IGNITION ELECTRODE

{ISOLATEMAINSPOWER}

Next: p1194, !f1195

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}
ATTACH PRESSURE GAUGE TO GAS VALVE INLET PRESSURE TEST POINT

Next: !p1206, !f1207

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}
ATTACH PRESSURE GAUGE TO GAS VALVE INLET PRESSURE TEST POINT

Next: p1409, !f1221

EXTERNAL CONTROLS VOLTAGE OUTPUT

{ISOLATEMAINSPOWER}

Next: p1232, f1233

EXTERNAL CONTROLS VOLTAGE INPUT

Next: !p1234, !f1235

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}
ATTACH PRESSURE GAUGE TO GAS VALVE INLET PRESSURE TEST POINT

Next: !p1260, !f1261

DHW THERMISTOR SENSOR (MODULATION)

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE DHW SENSOR

Next: !p1264, !f1265

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: !p1268, !f1269

INTEGRAL BYPASS

{ISOLATEMAINSPOWER}
DRAIN AND DISCHARGE APPLIANCE

Next: !p1272, !f1273

OBSERVATION BOILER RESET FAST FLASH

ENSURE NO DEMANDS
CH TEMPERATURE SELECTOR SET TO MIN

Next: p1282, ?1283, ?1285

RESISTANCE DHW SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE DHW SENSOR

Next: !p1293, !f1294

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: !p1297, !f1298

VOLTAGE TO FAN (HIGH SPEED)

{ISOLATEMAINSPOWER}
GAIN ACCESS TO PCB, USE ISOLATION MAT AS REQUIRED

Next: p1303, ?1304, ?1306

AIR PRESSURE SWITCH N/O

{ISOLATEMAINSPOWER}
REMOVE THE BLUE WIRE FROM THE AIR PRESSURE SWITCH

Next: !p1310, f1311

AIR PRESSURE SWITCH TUBES

{ISOLATEMAINSPOWER}

Next: p1312, ?1452, ?1454

RESISTANCE FAN

{ISOLATEMAINSPOWER}
DISCONNECT LEADS FROM FAN ASSEMBLY (NOTE CONNECTIONS FOR REINSTATEMENT)

Next: p1334, !f1335

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: !p1369, !f1370

RESISTANCE DHW SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE DHW SENSOR

Next: !p1373, !f1374

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: !p1379, !f1380

RESISTANCE HARNESS GAS VALVE (MAIN SOLENOID)

{ISOLATEMAINSPOWER}<

Next: !p1384, !f1385

RESISTANCE HARNESS GAS VALVE (MODULATION SOLENOID)

{ISOLATEMAINSPOWER}<

Next: !p1391, !f1392

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: p1395, !f1396

VOLTAGE MODULATING SOLENOID AT PCB (MODULATION)

{ISOLATEMAINSPOWER}<

Next: !p1401, f1402

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: p1403, !f1404

RESISTANCE HARNESS GAS VALVE (MAIN SOLENOID)

{ISOLATEMAINSPOWER}<

Next: !p1412, !f1413

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: !p1425, !f1426

RESISTANCE DHW SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE DHW SENSOR

Next: !p1429, !f1430

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}
ATTACH PRESSURE GAUGE TO GAS VALVE INLET PRESSURE TEST POINT

Next: p1388, !f383

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: !p28, !f29

MAINS POWER SUPPLY

{ISOLATEMAINSPOWER}

Next: p713, !f714

IGNITION ELECTRODE

{ISOLATEMAINSPOWER}

Next: p795, !f796

AIR PRESSURE SWITCH N/O

{ISOLATEMAINSPOWER}
REMOVE THE BLUE WIRE FROM THE AIR PRESSURE SWITCH

Next: !p874, f825

AIR PRESSURE SWITCH TUBES

{ISOLATEMAINSPOWER}

Next: p826, ?1432, ?1434

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: !p873, !f855

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: p921, !f928

OVERHEAT THERMOSTAT

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE OVERHEAT THERMOSTAT

Next: !p926, !f927

OVERHEAT THERMOSTAT

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE OVERHEAT THERMOSTAT

Next: !p978, !f945

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}
ATTACH PRESSURE GAUGE TO GAS VALVE INLET PRESSURE TEST POINT

Next: p1381, !f971

EXTERNAL CONTROLS VOLTAGE OUTPUT

{ISOLATEMAINSPOWER}

Next: p1003, f1004

INTEGRAL PROGRAMMER

{ISOLATEMAINSPOWER}<

Next: !p1007, !f1008

PUMP VOLTAGE

{ISOLATEMAINSPOWER}<

Next: p1012, !f1011

RESISTANCE PUMP HARNESS

{ISOLATEMAINSPOWER}

Next: !p1013, !f1014

PUMP LIMPET TEST

Next: !p1016, !f1017

PUMP LIMPET TEST

Next: p1019, !f1020

INTEGRAL BYPASS

{ISOLATEMAINSPOWER}
DRAIN AND DISCHARGE APPLIANCE

Next: p1021, !f1022

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: p1023, !f1024

CH MODULATION

{ISOLATEMAINSPOWER}<

Next: !p1025, !f1026

RESISTANCE DHW SENSOR AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: p867, f1049

DHW STOP COCK

SET THE DHW STOP COCK TO FULLY OPEN

Next: p1054, !f1055

DHW INLET FILTER

{ISOLATEMAINSPOWER}<

Next: p1056, !f1057

DHW FLOW REGULATOR

{ISOLATEMAINSPOWER}
TURN OFF DHW STOP COCK
ENSURE APPLIANCE IS DRAINED AND DISCHARGED

Next: !p1340, !f1059

VOLTAGE DHW FLOW SWITCH OUT

{ISOLATEMAINSPOWER}
GAIN ACCESS TO DHW FLOW SWITCH MOLEX CONNECTOR

Next: p1091, f1121

RESISTANCE HARNESS DHW FLOW SWITCH GREEN WIRE

{ISOLATEMAINSPOWER}
DISCONNECT INLINE CONNECT FROM FLOW SENSOR
DISCONNECT ST16 PLUG FROM PCB

Next: p807, !f1127

HEAT EXCHANGER (FLUE WAYS)

{ISOLATEMAINSPOWER}

Next: p793, !f1137

FLAME SENSE ELECTRODE

{ISOLATEMAINSPOWER}

Next: p1141, !f1142

FLAME SENSE ELECTRODE LEAD

{ISOLATEMAINSPOWER}<

Next: p1143, !f1144

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: p1145, !f1146

RESISTANCE DHW SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE DHW SENSOR

Next: p1147, !f1148

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}
ATTACH PRESSURE GAUGE TO GAS VALVE INLET PRESSURE TEST POINT

Next: p1149, !f1150

HEAT EXCHANGER (FLUE WAYS)

{ISOLATEMAINSPOWER}

Next: p1151, !f1152

FLUE

Next: !p1153, !f1154

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}
ATTACH PRESSURE GAUGE TO GAS VALVE INLET PRESSURE TEST POINT

Next: p1158, !f1159

HEAT EXCHANGER (FLUE WAYS)

{ISOLATEMAINSPOWER}

Next: p1160, !f1161

FLUE

Next: p1162, !f1163

INSPECTION BURNER

{ISOLATEMAINSPOWER}
REMOVE BURNER ASSEMBLY

Next: !p1164, !f1165

OBSERVATION BOILER RESET SLOW FLASH

Next: p1172, ?1174, ?1176, ?1178

INSPECTION SYSTEM PRESSURE

{ISOLATEMAINSPOWER}

Next: p1228, !f1229

DHW SPARKING

{ISOLATEMAINSPOWER}
REMOVE INNER CASING COVER
CH POTENTIOMETER SET TO MINIMUM

Next: p1192, f1193

CODE PLUG

{ISOLATEMAINSPOWER}

Next: !p1190, !f1191

RESISTANCE APS AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: !p1180, f1181

VENTURI

{ISOLATEMAINSPOWER}

Next: p1186, !f1187

FLUE

Next: !p1188, !f1189

DHW BURNER IGNITES (FAULT CODE)

CH POTENTIOMETER SET TO MINIMUM

Next: p1198, ?1200, ?1202

IGNITION ELECTRODE LEADS

{ISOLATEMAINSPOWER}
REMOVE THE IGNITION ELECTRODE LEADS

Next: !p1196, !f1197

BURNER PRESSURE

{ISOLATEMAINSPOWER}<

Next: p1218, f1219

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}
ATTACH PRESSURE GAUGE TO GAS VALVE INLET PRESSURE TEST POINT

Next: !p1216, !f1217

BURNER PRESSURE

{ISOLATEMAINSPOWER}<

Next: p1204, f1205

FLAME SENSE ELECTRODE

{ISOLATEMAINSPOWER}

Next: p1208, !f1209

FLAME SENSE ELECTRODE LEAD

{ISOLATEMAINSPOWER}<

Next: p1210, !f1211

INSPECTION BURNER

{ISOLATEMAINSPOWER}
REMOVE BURNER ASSEMBLY

Next: p1212, !f1213

INSPECTION INJECTORS

{ISOLATEMAINSPOWER}
REMOVE BURNER ASSEMBLY

Next: !p1214, !f1215

IGNITION ELECTRODE

{ISOLATEMAINSPOWER}

Next: !p1226, !f1227

CH DEMAND PUMP RUNS

CH TEMPERATURE CONTR

Next: p1230, f1231

PUMP LIMPET TEST

Next: p1240, !f1241

PUMP VOLTAGE

{ISOLATEMAINSPOWER}<

Next: p1236, !f1237

RESISTANCE PUMP HARNESS

{ISOLATEMAINSPOWER}

Next: !p1238, !f1239

PRESSURE BURNER MAX AND MIN

{ISOLATEMAINSPOWER}<

Next: p1242, ?1244, ?1246, ?1248

DHW MODULATION

{ISOLATEMAINSPOWER}
ATTACH A U-GAUGE TO THE GAS VALVE BURNER PRESSURE TEST POINT

Next: p1262, f1263

PRESSURE MIN SOLENOID DISCONNECTED

{ISOLATEMAINSPOWER}<

Next: !p1258, f1259

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}
ATTACH PRESSURE GAUGE TO GAS VALVE INLET PRESSURE TEST POINT

Next: p1252, !f1253

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}
ATTACH PRESSURE GAUGE TO GAS VALVE INLET PRESSURE TEST POINT

Next: !p1250, !f1251

VOLTAGE MODUREG (FULL) AT PCB

{ISOLATEMAINSPOWER}<

Next: p1254, !f1255

VOLTAGE MODUREG (FULL) AT GAS VALVE

{ISOLATEMAINSPOWER}<

Next: !p1256, !f1257

CH MODULATION

{ISOLATEMAINSPOWER}<

Next: p1266, f1267

DIFFERENTIAL HEAT EXCHANGER

{ISOLATEMAINSPOWER}<

Next: p1270, f1271

INSPECTION LOCKOUT TEMPERATURE

{ISOLATEMAINSPOWER}<

Next: !p1274, ?1276, ?1278

DHW FAN RUNS (FAULT CODE)

CH POTENTIOMETER SET TO MINIMUM

Next: p1301, f1302

CODE PLUG

{ISOLATEMAINSPOWER}

Next: p1289, !f1290

INSPECTION SERVICE MODE POTENTIOMETER

{ISOLATEMAINSPOWER}
GAIN ACCESS TO PCB

Next: !p1287, !f1288

RESISTANCE DHW SENSOR AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: p1291, f1292

RESISTANCE PRIMARY SENSOR AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: p1295, f1296

INSPECTION ST16 PLUG

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: !p1299, !f1300

PRESSURE APS SWITCHING

{ISOLATEMAINSPOWER}
DISCONNECT LEADS FROM THE AIR PRESSURE SWITCH NOTING THE CONNECTIONS

Next: p1320, f1321

CONTINUITY FAN HARNESS

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST1 FROM THE PCB

Next: !p1318, !f1319

RESISTANCE APS AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: !p1308, f1309

VENTURI

{ISOLATEMAINSPOWER}

Next: p1314, !f1315

OBSERVATION SPARKING APS PROVEN

{ISOLATEMAINSPOWER}<

Next: p1324, !f1325

AIR PRESSURE SWITCH TUBES

{ISOLATEMAINSPOWER}

Next: p1326, ?1447, ?1449

VENTURI

{ISOLATEMAINSPOWER}

Next: p1328, !f1329

FLUE

Next: !p1330, !f1331

CONTINUITY FAN HARNESS

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST1 FROM THE PCB

Next: p1336, !f1337

INSPECTION FAN ASSEMBLY FREE

{ISOLATEMAINSPOWER}

Next: !p1338, !f1339

HEAT EXCHANGER (FLUE WAYS)

{ISOLATEMAINSPOWER}

Next: p743, !f1349

INSPECTION SERVICE MODE POTENTIOMETER

{ISOLATEMAINSPOWER}
GAIN ACCESS TO PCB

Next: p1375, !f1376

TEMPERATURE AMBIENT

{ISOLATEMAINSPOWER}

Next: p1359, !f1360

FAULT CODES

Next: !p1357, !f1358

OBSERVATION DISCONNECT FLOW SWITCH

{ISOLATEMAINSPOWER}
DISCONNECT THE DHW FLOW SWITCH INLINE CONNECTOR AND MAKE SAFE

Next: p1361, !f1362

INSPECTION SERVICE MODE POTENTIOMETER

{ISOLATEMAINSPOWER}
GAIN ACCESS TO PCB

Next: p1363, !f1364

EXTERNAL CONTROLS VOLTAGE OUTPUT (NO DEMAND)

{ISOLATEMAINSPOWER}
GAIN ACCESS TO PCB, USE ISOLATION MAT AS REQUIRED
ENSURE NO DEMANDS

Next: p1365, !f1366

RESISTANCE PRIMARY SENSOR AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: p1367, f1368

RESISTANCE DHW SENSOR AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: !p1371, f1372

RESISTANCE PRIMARY SENSOR AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: !p1377, f1378

RESISTANCE GAS VALVE (MAIN SOLENOID) AND HARNESS

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: p1382, f1383

VOLTAGE GAS VALVE AT PCB

{ISOLATEMAINSPOWER}<

Next: !p1386, !f1387

RESISTANCE GAS VALVE (MODULATION SOLENOID) AND HARNESS

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: p1389, f1390

VOLTAGE MODULATING SOLENOID AT PCB

{ISOLATEMAINSPOWER}<

Next: !p1393, f1394

RESISTANCE DHW SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE DHW SENSOR

Next: !p1397, !f1398

RESISTANCE DHW SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE DHW SENSOR

Next: !p1405, !f1406

RESISTANCE GAS VALVE (MAIN SOLENOID) AND HARNESS

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: p1410, f1411

VOLTAGE GAS VALVE AT PCB

{ISOLATEMAINSPOWER}<

Next: !p1414, !f1415

CONTINUITY FAN HARNESS

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST1 FROM THE PCB

Next: !p1417, !f1418

EXTERNAL CONTROLS VOLTAGE OUTPUT (NO DEMAND)

{ISOLATEMAINSPOWER}
GAIN ACCESS TO PCB, USE ISOLATION MAT AS REQUIRED
ENSURE NO DEMANDS

Next: p1421, !f1422

RESISTANCE PRIMARY SENSOR AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: p1423, f1424

RESISTANCE DHW SENSOR AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: !p1427, f1428

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: p410, !f411

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: p416, !f417

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: !p444, !f445

RESISTANCE DHW SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE DHW SENSOR

Next: p412, !f413

BURNER MANIFOLD

{ISOLATEMAINSPOWER}

Next: !p414, !f415

RESISTANCE DHW SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE DHW SENSOR

Next: !p431, !f419

OVERHEAT THERMOSTAT

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE OVERHEAT THERMOSTAT

Next: p425, !f428

RESISTANCE PRIMARY SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE ONE OF THE WIRES FROM THE PRIMARY SENSOR

Next: p426, !f427

RESISTANCE DHW SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE DHW SENSOR

Next: !p429, !f430

VOLTAGE TO FAN (LOW SPEED)

{ISOLATEMAINSPOWER}
GAIN ACCESS TO PCB, USE ISOLATION MAT AS REQUIRED.

Next: p1416, !f668

VOLTAGE TO FAN (HIGH SPEED)

{ISOLATEMAINSPOWER}
GAIN ACCESS TO PCB, USE ISOLATION MAT AS REQUIRED

Next: p704, ?705, ?707

CONTINUITY FAN HARNESS

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST1 FROM THE PCB

Next: !p735, !f736

VOLTAGE AT FUSE F2 OUTPUT

Next: p1061, f710

FUSE F2

{ISOLATEMAINSPOWER}
REMOVE FUSE F2 FROM THE PCB

Next: p717, !f718

FUSE F1

{ISOLATEMAINSPOWER}
REMOVE FUSE F1 FROM THE PCB

Next: !p715, !f716

TRANSFORMER RESISTANCE

{ISOLATEMAINSPOWER}
REMOVE THE TRANSFORMER FROM THE CONTROL BOX

Next: !p719, !f720

PRESSURE APS SWITCHING

{ISOLATEMAINSPOWER}
DISCONNECT LEADS FROM THE AIR PRESSURE SWITCH NOTING THE CONNECTIONS

Next: p741, !f742

OBSERVATION SPARKING APS PROVEN

{ISOLATEMAINSPOWER}<

Next: p1341, f913

AIR PRESSURE SWITCH TUBES

{ISOLATEMAINSPOWER}

Next: p749, ?1437, ?1439

VENTURI

{ISOLATEMAINSPOWER}

Next: p751, !f752

FLUE

Next: !p753, !f754

PRESSURE APS SWITCHING

{ISOLATEMAINSPOWER}
DISCONNECT LEADS FROM THE AIR PRESSURE SWITCH NOTING THE CONNECTIONS

Next: p792, !f806

OBSERVATION SPARKING APS PROVEN

{ISOLATEMAINSPOWER}<

Next: p1129, f794

AIR PRESSURE SWITCH TUBES

{ISOLATEMAINSPOWER}

Next: p799, ?1442, ?1444

IGNITION ELECTRODE LEADS

{ISOLATEMAINSPOWER}
REMOVE THE IGNITION ELECTRODE LEADS

Next: !p797, !f798

VENTURI

{ISOLATEMAINSPOWER}

Next: p801, !f802

FLUE

Next: !p803, !f804

RESISTANCE APS AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: p845, f823

VENTURI

{ISOLATEMAINSPOWER}

Next: p828, !f829

FLUE

Next: !p830, !f831

RESISTANCE PRIMARY SENSOR AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR ST16 FROM THE PCB

Next: p1036, f853

CODE PLUG

{ISOLATEMAINSPOWER}

Next: !p1027, !f869

RESISTANCE DHW SENSOR AT SENSOR

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE DHW SENSOR

Next: p922, !f923

RESISTANCE OVERHEAT THERMOSTAT AT PCB

{ISOLATEMAINSPOWER}
REMOVE CONNECTOR ST16 FROM THE PCB

Next: !p924, f925

RESISTANCE OVERHEAT THERMOSTAT AT PCB

{ISOLATEMAINSPOWER}
REMOVE CONNECTOR ST16 FROM THE PCB

Next: p967, f943

BURNER PRESSURE

{ISOLATEMAINSPOWER}<

Next: p968, f969

IGNITION ELECTRODE

{ISOLATEMAINSPOWER}

Next: !p976, !f977

System Information

  • Total Tests: 480
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control