Set Appliance State:

Gas Off
Isolate Mains Power to appliance as per TOPs P4
Turn Hot Water Tap On
Remove electrode lead from spark generator & make safe
Do not touch any part of the appliance during this test
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Reset the boiler / cancel pump purge as necessary.
Allow ignition sequence to commence.
Sparking should occur 5 times as the appliance attempts to ignite (sparking for 8 seconds at a time with 3 second intervals).
Does sparking occur as described?