Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Gas On; Pilot On
Measurement:
With the pilot alight (keep Gas Control Valve Knob pressed in) measure the voltage on the Thermocouple between the interrupter and a suitable earth.
Voltage measured should be greater than 8mV DC.
Voltage measured should be greater than 8mV DC.

Isolate as per TOPs P4
and refit as necessary