Set Appliance State:
Mains Power Off
CH Demand
On/Off Switch in ON position
Mode selector switch to Constant
Delay Time delay set to min (2mins)
Mode selector switch to Constant
Delay Time delay set to min (2mins)
| WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure |
Measurement:
Measure Mains Voltage across connections 26 L (Red/Black) and N (Blue) after a period of two minutes.
NOTE:
Remember the C/H Delay Timer - the boiler will not fire immediately. There will be approximately a two minute wait.
NOTE:
Remember the C/H Delay Timer - the boiler will not fire immediately. There will be approximately a two minute wait.

Isolate as per TOPs P4
and refit as necessary