Set Appliance State:

Set Multimeter to Resistance Set meter to measure resistance
Isolate Mains Power to appliance as per TOPs P4
On/Off Switch in ON position
Mode Selector Switch to Constant
IMPORTANT: Once the boiler is up to temperature,
turn mode selector switch to summer

Measurement:

Measure Mains Voltage across connections 32 L (Brown) and Neutral (Blue)
NOTE 1: The boiler must have reached its operating temperature before this test can be carried out.
NOTE 2: It may be necessary to turn off some radiators for this test.
This will assist the boiler to reach operating temperature and speed up the test.