Set Appliance State:
Mains Power Off
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Reset the boiler by pressing the       / R button for approximately 1 second, you may need to press this twice as if held too long it will put the boiler into standby.
If the fault code remains try a hard reset of the appliance by removing the flap with the spanner symbol and pressing the button behind it for approximately 1 second.
Does the appliance reset?
(either with a normal reset or hard reset)
Boiler resets - Retest appliance
Boiler will not reset, Fault code remains
If the fault code remains try a hard reset of the appliance by removing the flap with the spanner symbol and pressing the button behind it for approximately 1 second.
Does the appliance reset?
(either with a normal reset or hard reset)
Boiler resets - Retest appliance
Boiler will not reset, Fault code remains