Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Selector switch in OFF position
CH temperature selector to maximum
DHW Preheat selector to OFF position
Remove CH micro switch head
CH temperature selector to maximum
DHW Preheat selector to OFF position
Remove CH micro switch head
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
With no CH demand the spindle should be retracted.
Test 1:
Apply a CH demand and allow pump to run.
Approximately 2 - 3 seconds after the pump has started the spindle should extend & be smooth in operation.
Test 1:
Apply a CH demand and allow pump to run.
Approximately 2 - 3 seconds after the pump has started the spindle should extend & be smooth in operation.
Isolate as per TOPs P4
and refit as necessary