Set Appliance State:
Mains Power Off
Gas Off
Turn Hot Water Tap On
Selector switch to DHW position
CH temperature selector to minimum
DHW Preheat selector to OFF position
CH temperature selector to minimum
DHW Preheat selector to OFF position
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Allow fan to run. After approximately five seconds measure voltage across connection 3 (blue lead) and connection 5 (brown lead) on connector A1 on the PCB.
Voltage will only be present for approximately 10 seconds during ignition sequence.
If boiler goes to lockout it will require resetting.
Voltage will only be present for approximately 10 seconds during ignition sequence.
If boiler goes to lockout it will require resetting.

Isolate as per TOPs P4
and refit as necessary