Set Appliance State:
Isolate Mains Power to appliance as per TOPs P4
Ease connector J1 slightly off PCB to expose the silver strip to
allow for testing with probes
Ease connector J1 slightly off PCB to expose the silver strip to
allow for testing with probes
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Measure the voltage between the Grey (2) and the White (3) on connector J1
on the main PCB Connector.
The voltage will vary according to system pressure.
Approx voltage should be between 1.7 -1.9 volts DC
on the main PCB Connector.
The voltage will vary according to system pressure.
Approx voltage should be between 1.7 -1.9 volts DC
| System pressure | Voltage DC | 0 bar | 1.2 |
| 1 bar | 1.7 |
| 2 bar | 2.2 |
| 3 bar | 2.8 |

Isolate as per TOPs P4
and refit as necessary