4704436 VAILLANT ECOTEC PRO 24
OUTER CASE REMOVA
FAN RUNS
TURN DHW TEMPERATURE SELECTOR TO MINIMUM AND ENSURE NO CH DEMAND
CH DEMAND
ENSURE BOILER IS NOT UP TO TEMPERATURE
PREHEAT OPERATION
ENSURE THE PLATE HEA
F10/F0 FAULT CODE/ FLOW THERMISTOR
NOT USED
F11/F1 FAULT CODE/ RETURN THERMISTOR
NOT USED
F75 FAULT CODE PUMP RUNS
INTENTIONALLY BLANK HEADER FOR F75 FAULT CODE
F72 FAULT CODE
OUTSIDE MODEL
FURTHER INVESTIGATION FUSE
NOT USED
FURTHER INVESTIGATION PCB
NOT USED
F63 FAULT CODE
BLANK PAGE OUTSIDE MODEL
INFORMATION D34 FAN SPEED
TO ACCESS PARAMETER
F25 FAULT CODE
OK TO BE BLANK
F32 FAULT CODE
OK TO BE BLANK
F61 AND F62 FAULT CODE
INTENTIONALLY BLANK HEADER FOR FAULT CODE F61 AND F62
POWER UP
NO DEMANDS
CON FAULT
INTENTIONALLY BLANK HEADER FOR CON FAULT
F22 / F73 / F74 FAULT CODE
INTENTIONALLY BLANK HEADER FOR FAULT CODE F22 / F73 AND F74
F77 FAULT CODE
NOT USED
INFORMATION D34 FAN SPEED
Z DIRECTION CHOICE OR CONTINUE
FLOW RATE
SENSOR - FLOW
DHW FLOW RATE
VALVE
DHW FLOW RATE
COLD MAINS SUPPLY
F25 FAULT CODE
SAFETY FUSE
BURNER DOES NOT LIGHT
TRAP - SIPHONIC CONDENSATE
GAS VALVE
HARNESS X20
GAS INLET PRESSURE
GAS VALVE INLET PRESSURE
BURNER IGNITION
FLUE
BURNER IGNITION
HEAT EXCHANGER
IGNITION ELECTRODES
ELECTRODE - IGNITION & MONITORING
BURNER IGNITION
BURNER
BURNER DOES NOT ESTABLISH
TRAP - SIPHONIC CONDENSATE
DOES NOT ESTABLISH
GAS VALVE INLET PRESSURE
FLAME SENSE
CABLE - IGNITION
BURNER NOT ESTABLISHING
HEAT EXCHANGER
FLAME SENSE ELECTRODE
ELECTRODE - IGNITION & MONITORING
DHW COOL RADS HOT
HARNESS X2
HEAT EX NOISY
HARNESS X2
HEAT EX NOISY
PCB
CH OP
HARNESS X2
CH OP
PCB
AQUA SENSOR
HARNESS X2
DHW DEMAND
SENSOR - NTC - CH FLOW / CH RETURN
DHW DEMAND
SENSOR - NTC - CH FLOW / CH RETURN
F32 FAULT CODE FAN - SPEED CONTROL
HARNESS X20
F32 FAULT CODE FAN DOES NOT RUN HARNESS FAN
HARNESS X20
FAULT CODE 32
Z DIRECTION CHOICE OR CONTINUE
F32 FAULT CODE - FAN HALL SENSOR
HARNESS X20
EXPANSION VESSEL
EXPANSION VESSEL 10L
PUMP RUNS
SENSOR - NTC - CH FLOW / CH RETURN
PUMP RUNS
SENSOR - NTC - CH FLOW / CH RETURN
PUMP DOES NOT RUN
SYSTEM PRESSURE
WATER PRESSURE SENSOR
HARNESS X2
F62 GAS VALVE
VALVE - GAS
HARNESS OVERHEAT 2
HARNESS X20
F62 GAS VALVE AT IGNITION
VALVE - GAS
F62 - NOT SHUTTING DOWN AT IGNITION
VALVE - GAS
T2 FUSE FAILED
SET - 10 OFF FUSES 2.0 AT
NOISEY DHW
FILTER
NO DISPLAY
PCB
FUSED SPUR FUSE
MAINS FUSE
HEAT EXCHANGER NOISY
PUMP
24 VOLT INPUT
PCB
AQUA SENSOR 2 (SHORTED)
HARNESS X2
EBUS ERROR
PCB
EBUS ERROR 2
PCB
PUMP PULSES ON-OFFF75 FAULT CODE
AIR VENT - AUTOMATIC
F75
FILTER
F75
TUBE - CONNECTION
PUMP PULSES ON-OFF 75 FAULT CODE
EXPANSION VESSEL 10L
PULSES ON_OFF
PUMP
PUMP PULSES ON-OFF
AIR VENT - AUTOMATIC
PUMP PULSES ON-OFF
FILTER
PUMP RUNS
TUBE - CONNECTION
PUMP PULSES ON_OFF
EXPANSION VESSEL 10L
F73 / F74
SYSTEM PRESSURE
PCB
PCB
F73 / F74
HARNESS X2
PUMP PULSES ON-OFFF75 FAULT CODE INTERMITTENT
SYSTEM PRESSURE
PUMP PULSES ON-OFFF75 FAULT CODE INTERMITTENT
AIR VENT - AUTOMATIC
F75 INTERMITTENT
FILTER
F75 INTERMITTENT
TUBE - CONNECTION
PUMP PULSES ON-OFF 75 FAULT CODE INTERMITTENT
EXPANSION VESSEL 10L
RADS DO NOT HEAT
SENSOR - NTC - CH FLOW / CH RETURN
RETURN (CH HOT TOO SOON)
SENSOR - NTC - CH FLOW / CH RETURN
CH OPERATION
BY - PASS
POOR CH
FILTER
SPARKING
CABLE - IGNITION
BURNER DOES NOT LIGHT - FAN HALL SENSOR
HARNESS X20
SPARKING WITH CONDESATE PUMP
CABLE - IGNITION
F77 FAULT CODE
CONDENSATE PUMP (VAILLANT)
BLOWING FUSE 2
PUMP
BLOWING FUSE
PUMP
DHW (TOO HOT)
SENSOR - NTC - CH FLOW / CH RETURN
DHW (TOO HOT)
SENSOR - NTC - CH FLOW / CH RETURN
DHW TOO COOL APP MOD
SENSOR - NTC - CH FLOW / CH RETURN
DHW TOO COOL APP MOD
SENSOR - NTC - CH FLOW / CH RETURN
DHW TOO COOL APP MOD
PUMP
DHW TOO COOL APP MOD
FILTER
DHW TOO COOL APP MOD
TUBE - CONNECTION
DHW HOT COLD
SENSOR - NTC - CH FLOW / CH RETURN
DHW DHW HOT COLD
SENSOR - NTC - CH FLOW / CH RETURN
DHW HOT COLD
PUMP
DHW HOT COLD
FILTER
DHW HOT COLD
TUBE - CONNECTION
POOR HW RADS COOL
EXTERNAL MIXING
DHW (GROK)
SENSOR - NTC - CH FLOW / CH RETURN
F62 - NOT SHUTTING DOWN
VALVE - GAS
BAFFLING
GAS VALVE INLET PRESSURE
BAFFLING
INLET - AIR DUCT
BAFFLING
TRAP - SIPHONIC CONDENSATE
BAFFLING
FLUE
BAFFLING
BURNER
BAFFLING
HEAT EXCHANGER
NO IGNITION
SAFETY FUSE
DHW COOL RADIATORS COOL
INLET - AIR DUCT
PUMP RUNS
SAFETY FUSE
OH STAT
HARNESS X20
OVERHEAT1
SAFETY FUSE
F62 FAULT CODE
SAFETY FUSE
F27
CABLE - IGNITION
F27
ELECTRODE - IGNITION & MONITORING
F27
PCB
DHW OPERATION
FLUE
FAULTY
PCB
SHORTED
HARNESS X20
SHORTED
HARNESS X2
LOW CAUSING POOR IGNITION
GAS VALVE INLET PRESSURE
RESTRICTED OR BLOCKED AFFECTING IGNITION
TRAP - SIPHONIC CONDENSATE
CAUSING POOR SPARK
CABLE - IGNITION
WARPED CAUSING POOR IGNITION
ELECTRODE - IGNITION & MONITORING
DHW OPERATION
GAS VALVE INLET PRESSURE
CH OPERATION
DIVERTER VALVE BRASS
SAFETY CHECKS
Z DIRECTION CHOICE OR CONTINUE
CH MODULATION
SENSOR - NTC - CH FLOW / CH RETURN
PUMP OVERRUN
PCB
FAN HALL SENSOR
HARNESS X20
HARNESS FAN
HARNESS X20
FAN NOT RUNNING
SENSOR - NTC - CH FLOW / CH RETURN
RETURN (FAN NOT RUNNING)
SENSOR - NTC - CH FLOW / CH RETURN
WATER COOL RADS COOL GROK
FILTER
DHW OPERATION GROK
TRAP - SIPHONIC CONDENSATE
DHW (GROK)
SENSOR - NTC - CH FLOW / CH RETURN
RADS DO NOT HEAT999
SENSOR - NTC - CH FLOW / CH RETURN
RETURN SENSOR (CH COOL)
HARNESS X20
CH OPERATION
TRAP - SIPHONIC CONDENSATE
RETURN (CH MODULATION)
SENSOR - NTC - CH FLOW / CH RETURN
PREHEAT (NOT WORKING)
SENSOR - NTC - HEAT EXCHANGER
PUMP PULSES ON-OFF
SYSTEM PRESSURE
PUMP PULSES ON_OFF
HARNESS X2
FOR TYPE DIAG PROCEDURE
Z DIRECTION CHOICE OR CONTINUE
FAULT CODE DUM
Z DIRECTION CHOICE OR CONTINUE
F0/F10 FAULT CODE
SENSOR - NTC - CH FLOW / CH RETURN
F11/1 FAULT CODE
SENSOR - NTC - CH FLOW / CH RETURN
F67 FAULT CODE
PCB
F70 FAULT CODE
RESET TO FACTORY PARAMETERS
HARNESS OVERHEAT1
HARNESS X20
F76
OVERHEAT
OVERHEAT
SYSTEM PRESSURE
OVERHEAT3
PUMP
SYS TEMP3
SENSOR - NTC - CH FLOW / CH RETURN
SYS TEMP3
SENSOR - NTC - CH FLOW / CH RETURN
OVERHEAT3
PCB
OVERHEAT3
SAFETY FUSE
PUMP PULSES ON-OFFF75 FAULT CODE
SYSTEM PRESSURE
PUMP PULSES ON-OFFF75 FAULT CODE
HARNESS X2
BURNER IGNITION
INLET - AIR DUCT
F72 FAULT CODE
SENSOR - NTC - CH FLOW / CH RETURN
F72 FAULT CODE
SENSOR - NTC - CH FLOW / CH RETURN
HEAT EX NOISY
TUBE - CONNECTION
BURNER ESTABLISH
INLET - AIR DUCT
F13 FAULT CODE
SENSOR - NTC - HEAT EXCHANGER
F63 FAULT CODE
PCB
F65 FAULT CODE
PCB
FLOW RATE
FILTER
FLOW RATE
LIMITER
FLOW RATE
HEAT EXCHANGER - PLATE
F25 FAULT CODE
PCB
NO IGNITION - NOT OPENING
VALVE - GAS
NO IGNITION - NOT OPENING FULLY
VALVE - GAS
FLAME SENSE
PCB
DHW COOL RADIATORS HOT
DIVERTER VALVE BRASS
HEAT EX NOISY
DIVERTER VALVE BRASS
CH OP
DIVERTER VALVE BRASS
DHW DEMAND
SENSOR - FLOW
FLOW SENSOR (DHW DEMAND)
HARNESS X20
AQUA SENSOR
PCB
RETURN SENSOR (DHW DEMAND)
HARNESS X20
DHW COOL RADIATORS HOT
DIVERTER VALVE BRASS
FAN RUNS
FAN
FLOW SENSOR
HARNESS X20
RETURN SENSOR
HARNESS X20
PUMP RUNS
SENSOR - WATER PRESSURE
PCB PUMP RUNS
PCB
F62 FAULT CODE
HARNESS X20
F62 FAULT CODE AT IGNITION
HARNESS X20
T2 FUSE FAILED
Z DIRECTION CHOICE OR CONTINUE
FAULTY
DISPLAY
HEAT EXCHANGER NOISY
HEAT EXCHANGER - PLATE
MAINS FUSE FAILED
Z DIRECTION CHOICE OR CONTINUE
PREVENTING HEATING OPERATION
EBUS CONTROLS
SHORTED
SENSOR - FLOW
DHW DEMAND
PCB
GENERATING FAULT CODE
EBUS CONTROLS
F73 / F74
PCB
F22 / F73 / F74
SENSOR - WATER PRESSURE
PUMP PULSING F75 (3)
SENSOR - WATER PRESSURE
PUMP PULSING F75 (2)
SENSOR - WATER PRESSURE
PUMP PULSING F75 INTERMITTENT
SENSOR - WATER PRESSURE
INTERMITTENT FAULT
SENSOR WATER PRESSURE
FLOW SENSOR (RADS DO NOT HEAT)
HARNESS X20
RETURN SENSOR (RADS DO NOT HEAT)
HARNESS X20
NO SPARKING
CONDENSATE PUMP (VAILLANT)
F77 FAULT CODE 2
PCB
CON FAULT
PCB - CON FAULT
PUMP RUNS
PUMP
FURTHER INVESTIGATION FUSE F1
HARNESS X20
FUSE BLOWN
PCB FUSE BLOWN
FUSE BLOWN ORIGINAL PUMP
PCB FUSE BLOWN
FURTHER INVESTIGATION PCB FAIL
HARNESS X20
FLOW SENSOR (DHW TOO HOT)
HARNESS X20
DHW TOO HOT
PCB
RETURN SENSOR (DHW TOO HOT)
HARNESS X20
FLOW SENSOR DHW COOL APPL MOD
HARNESS X20
RETURN SENSOR DHW COOL APPL MOD
HARNESS X20
DHW TOO COOL APP MOD
HEAT EXCHANGER - PLATE
DHW TOO COOL APP MODD
HEAT EXCHANGER
FLOW SENSOR DHW HOT COLD
HARNESS X20
RETURN SENSOR DHW HOT COLD
HARNESS X20
DHW HOT COLD
PCB
DHW HOT COLD
HEAT EXCHANGER - PLATE
DHW HOT COLD
HEAT EXCHANGER
RETURN SENSOR (DHW GROK)
HARNESS X20
F61 / F62 RETEST APPLIANCE
Z DIRECTION CHOICE OR CONTINUE
BAFFLING
VALVE - GAS
PUMP RUNS
HARNESS - CABLE TREE
OVERHEAT 1
HARNESS - CABLE TREE
F25 FAULT CODE
HARNESS - CABLE TREE
HIGH SPEED
FAN
F27 RETEST BOILER
Z DIRECTION CHOICE OR CONTINUE
PCB FURTHER INVESTIGATION
Z DIRECTION CHOICE OR CONTINUE
SHORTED
FAN
BLANK DISPLAY
SENSOR - WATER PRESSURE
WEAK SPARK
PCB
WRONG MIX CAUSING POOR IGNITION
VALVE - GAS
MODULATION
VALVE - GAS
FLOW SENSOR (DHW FAN NOT RUNNING)
HARNESS X20
RETURN SENSOR (DHW FAN NOT RUNNING)
HARNESS X20
DHW COOL RADIATORS COOL GROK
HEAT EXCHANGER - PLATE
FLOW SENSOR (DHW GROK)
HARNESS X20
FLOW SENSOR (CH COOL)
HARNESS X20
RETURN SESNOR (CH COOL)
SENSOR - NTC - CH FLOW / CH RETURN
CH MODULATION
PCB
FLOW SENSOR (CH MODULATION)
HARNESS X20
RETURN SENSOR (CH MODULATION)
HARNESS X20
PREHEAT (NOT WORKING)
HARNESS X2
PUMP PULSES ON_OFF
SENSOR - WATER PRESSURE
FAULT CODES DUM
Z DIRECTION CHOICE OR CONTINUE
F10-F0 RETEST BOILER
Z DIRECTION CHOICE OR CONTINUE
SENSOR PRIMARY F0/F10 FAULT CODE
HARNESS X20
F11-F1 RETEST BOILER
Z DIRECTION CHOICE OR CONTINUE
SENSOR TEMP RETURN F11/1 FAULT CODE
HARNESS X20
F67 RETEST BOILER
Z DIRECTION CHOICE OR CONTINUE
F70 RETEST BOILER
Z DIRECTION CHOICE OR CONTINUE
F49 RETEST BOILER
Z DIRECTION CHOICE OR CONTINUE
PUMP PULSING F75
SENSOR - WATER PRESSURE
F72 FAULT CODE
PCB
RETURN SENSOR F72 FAULT CODE
HARNESS X20
PRIMARY SENSOR F72 FAULT CODE
HARNESS X20
HEAT EXCHANGER NOISY
HEAT EXCHANGER
F13 FAULT CODE
PCB
F13 RETEST BOILER
Z DIRECTION CHOICE OR CONTINUE
F13 FAULT CODE
HARNESS X2
CH DEMAND
TIME SWITCH
FURTHER INVESTIGATION FUSE F1 MAIN SOLENOID
HARNESS X20
FURTHER INVESTIGATION MAIN SOLENOIDPCB FAIL
HARNESS X20
F63 RESTEST BOILER
Z DIRECTION CHOICE OR CONTINUE
F65 RETEST BOILER
Z DIRECTION CHOICE OR CONTINUE
INLET FILTER FAULTY
CHARACTERISTIC TEST FROM INLET/FILTER FLOW REG
INLET REGULATOR FAULTY
CHARACTERISTIC TEST FROM INLET/FILTER FLOW REG
DHW TOO COOL, RADIATORS COLD
CHARACTERISTIC TEST FROM DHW OPERATION
DHW TOO HOT
CHARACTERISTIC TEST FROM DHW OPERATION
HEAT EXCHANGER NOISY
CHARACTERISTIC TEST FROM DHW OPERATION
DHW COOL, RADIATORS HOT
CHARACTERISTIC TEST FROM DHW OPERATION
FAN DOES NOT RUN
CHARACTERISTIC TEST FROM FAN RUNS
FAN RUNS CONTINUOUSLY
CHARACTERISTIC TEST FROM FAN RUNS
F61 OR F62 SHOWN AFTER DEMAND
CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH
24 VOLT CONTROLS FITTED
CHARACTERISTIC TEST FROM OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED?
EBUS CONTROLS FITTED
CHARACTERISTIC TEST FROM OBSERVATION WHAT TYPE OF EXTERNAL CONTROLS ARE FITTED?
APPLIANCE MODULATES BEFORE GAS RATE CAN BE TAKEN
CHARACTERISTIC TEST FROM GAS RATE
PUMP DOES NOT RUN
CHARACTERISTIC TEST FROM OBSERVATION PUMP BEHAVIOUR F75
PUMP RUNS OR F75 OCCURING INTERMITTENTLY
CHARACTERISTIC TEST FROM OBSERVATION PUMP BEHAVIOUR F75
GAS RATE CORRECT BUT STILL TOO COOL
CHARACTERISTIC TEST FROM GAS RATE
BURNER IGNITES BUT BAFFLES OUT
CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH
BURNER IGNITES BUT IGNITION POOR (HEAVY/DELAYED/EXPLOSIVE/SLOW)
CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH
BOILER AND SYSTEM TEMPERATURE LOW
CHARACTERISTIC TEST FROM CH OPERATION
CH NOISY, DHW OK
CHARACTERISTIC TEST FROM CH OPERATION
BOILER REACHES TEMPERATURE, RADS DO NOT HEAT
CHARACTERISTIC TEST FROM CH OPERATION
FAN DOES NOT RUN
CHARACTERISTIC TEST FROM FAN RUNS
FAN RUNS CONTINUOUSLY
CHARACTERISTIC TEST FROM FAN RUNS
PUMP PULSES ON-OFF_THEN LOCK OUT F75
CHARACTERISTIC TEST FROM PUMP RUNS
DOES NOT RUN
CHARACTERISTIC TEST FROM PUMP RUNS
BURNER LIGHTS BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH
BURNER DOES NOT LIGHT
CHARACTERISTIC TEST FROM DHW BURNER IGNITION & ESTABLISH
DHW COOL, BOILER REACHES TEMP AND MODULATES OR CUTS OUT
CHARACTERISTIC TEST FROM DHW OPERATION
04/08/2021 08:13:04 2108_1_50_1 23/09/2021 09:28:40
25/08/2021 13:37:16
RESISTANCE OVERHEAT STAT AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
VOLTAGE GAS VALVE AT PCB
DISCONNECT PLUG FROM GAS VALVE AND MAKE SAFE
RESISTANCE OVERHEAT STAT AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
PCB VOLTS TO AQUA SENSOR
{USEINSMAT}
AQUA SENSOR HARNESS RESISTANCE
REMOVE THE PLUG FROM X2 ON THE PCB AND THE PLUG FROM THE AQUA FLOW SENSOR
RESISTANCE SENSOR TEMP PRIMARY
REMOVE THE LEADS FROM THE FLOW SENSOR
RESISTANCE SENSOR TEMP RETURN
REMOVE CONNECTOR FROM RETURN SENSOR
FAN RUNS
TURN DHW TEMPERATURE SELECTOR TO MINIMUM AND ENSURE NO CH DEMAND
RESISTANCE SENSOR TEMP PRIMARY AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP PRIMARY
REMOVE THE LEADS FROM THE FLOW SENSOR
RESISTANCE SENSOR TEMP RETURN
REMOVE CONNECTOR FROM RETURN SENSOR
HARNESS PRESSURE SWITCH
DISCONNECT CONNECTOR X2 FROM THE PCB
DISCONNECT CONNECTOR FROM THE LOW WATER PRESSURE SWITCH
RESISTANCE OVERHEAT STAT AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE GAS VALVE SOLENOID MAIN F61
REMOVE THE LEADS FROM THE GAS VALVE
RESISTANCE OVERHEAT HARNESS
DISCONNECT X20 CONNECTOR FROM THE PCB
DISCONNECT THE LEAD TO THE OVERHEAT STAT
RESISTANCE GAS VALVE SOLENOID MAIN F61
REMOVE THE LEADS FROM THE GAS VALVE
VOLTAGE MAINS POWER INPUT TO APPLIANCE
{USEINSMAT}
REMOVE CONTROL BOX COVER
RESISTANCE FUSE F1 (FUSED SPUR)
REMOVE FUSE FROM FUSED SPUR
PRIMARY FLOW FILTER
APPLIANCE DISCHARGED AND DRAINED
VOLTAGE DC TO AQUA SENSOR (SENSOR DISCONNECTED)
REMOVE CONNECTOR FROM AQUA SENSOR AND MAKE SAFE
AQUA SENSOR HARNESS RESISTANCE
REMOVE THE PLUG FROM X2 ON THE PCB AND THE PLUG FROM THE AQUA FLOW SENSOR
OBSERVATION ARE ANY EBUS CONTROLS FITTED
GAIN ACCESS TO THE PCB
PRESSURE SENSOR VOLTAGE (PCB)
{USEINSMAT}
GAIN ACCESS TO PCB
HARNESS PRESSURE SWITCH
DISCONNECT CONNECTOR X2 FROM THE PCB
DISCONNECT CONNECTOR FROM THE LOW WATER PRESSURE SWITCH
RESISTANCE SENSOR TEMP PRIMARY
REMOVE THE LEADS FROM THE FLOW SENSOR
RESISTANCE SENSOR TEMP RETURN
REMOVE CONNECTOR FROM RETURN SENSOR
OBSERVATION CONNECTOR X40 (CONDENSATE PUMP)
GAIN ACCESS TO PCB
DISCONNECT X40 DOES SPARKING OCCUR?
REMOVE CONNECTOR X40 FROM THE PCB AND MAKE SAFE
RESISTANCE HARNESS IGNITION
REMOVE THE LEAD FROM THE SPARK GENERATOR
AND THE IGNITION ELECTRODE
OBSERVATION CONNECTOR X40 (CONDENSATE PUMP)
GAIN ACCESS TO PCB
OBSERVATION F77 RESET (CONDENSATE PUMP DISCONNECTED)
REMOVE CONDENSATE PUMP CONNECTOR FROM X40 AND MAKE SAFE
VOLTAGE TO DISPLAY (AT PCB)
{USEINSMAT}
GAIN ACCESS TO PCB
RESISTANCE FAN
DISCONNECT THE CONNECTOR FROM THE FAN ASSEMBLY
RESISTANCE PUMP AND HARNESS
REMOVE X18 FROM THE PCB
RESISTANCE FAN
DISCONNECT THE CONNECTOR FROM THE FAN ASSEMBLY
RESISTANCE SENSOR TEMP PRIMARY
REMOVE THE LEADS FROM THE FLOW SENSOR
RESISTANCE SENSOR TEMP RETURN
REMOVE CONNECTOR FROM RETURN SENSOR
RESISTANCE SENSOR TEMP PRIMARY
REMOVE THE LEADS FROM THE FLOW SENSOR
RESISTANCE SENSOR TEMP RETURN
REMOVE CONNECTOR FROM RETURN SENSOR
DIFFERENTIAL PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE CLAMPS AS INDICATED
(DO NOT ATTACH CLAMPS TO THE RUBBER HOSE)
PRIMARY FLOW FILTER
APPLIANCE DISCHARGED AND DRAINED
RESISTANCE SENSOR TEMP PRIMARY
REMOVE THE LEADS FROM THE FLOW SENSOR
RESISTANCE SENSOR TEMP RETURN
REMOVE CONNECTOR FROM RETURN SENSOR
DIFFERENTIAL PRIMARY HEAT EXCHANGER
ATTACH TEMPERATURE CLAMPS AS INDICATED
(DO NOT ATTACH CLAMPS TO THE RUBBER HOSE)
PRIMARY FLOW FILTER
APPLIANCE DISCHARGED AND DRAINED
RESISTANCE PUMP AND HARNESS
REMOVE X18 FROM THE PCB
RESISTANCE SENSOR TEMP RETURN
REMOVE CONNECTOR FROM RETURN SENSOR
RESISTANCE OVERHEAT HARNESS
DISCONNECT X20 CONNECTOR FROM THE PCB
DISCONNECT THE LEAD TO THE OVERHEAT STAT
RESISTANCE HARNESS IGNITION
REMOVE THE LEAD FROM THE SPARK GENERATOR
AND THE IGNITION ELECTRODE
VOLTAGE 24 VDC AND 5 VDC X2 AND X20 REMOVED
REMOVE CONNECTORS X2 AND X20 FROM THE PCB
VOLTAGE 24VDC AND 5 VDC FAN REMOVED
BOTH CONNECTOR X2 AND X20 SHOULD BE FITTED TO THE PCB
REMOVE CONNECTOR FROM FAN AND MAKE SAFE
RESISTANCE HARNESS IGNITION
REMOVE THE LEAD FROM THE SPARK GENERATOR
AND THE IGNITION ELECTRODE
RESISTANCE SENSOR TEMP PRIMARY
REMOVE THE LEADS FROM THE FLOW SENSOR
RESISTANCE SENSOR TEMP PRIMARY
REMOVE THE LEADS FROM THE FLOW SENSOR
RESISTANCE SENSOR TEMP RETURN
REMOVE CONNECTOR FROM RETURN SENSOR
RESISTANCE SENSOR TEMP PRIMARY
REMOVE THE LEADS FROM THE FLOW SENSOR
RESISTANCE SENSOR TEMP PRIMARY
REMOVE THE LEADS FROM THE FLOW SENSOR
RESISTANCE SENSOR TEMP RETURN
REMOVE CONNECTOR FROM RETURN SENSOR
RESISTANCE SENSOR TEMP PRIMARY AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP RETURN
REMOVE CONNECTOR FROM RETURN SENSOR
PLATE HEAT EXCHANGER SENSOR & HARNESS
REMOVE THE CONNECTOR X2 FROM THE PCB
PLATE HEAT EXCHANGER SENSOR
REMOVE THE SECONDARY SENSOR FROM THE SECONDARY HEAT EXCHANGER
HARNESS PRESSURE SWITCH
DISCONNECT CONNECTOR X2 FROM THE PCB
DISCONNECT CONNECTOR FROM THE LOW WATER PRESSURE SWITCH
VOLTAGE DIVERTER MOTOR AT PCB
{USEINSMAT}
DISCONNECT THE PLUG FROM THE DIVERTER MOTOR AND MAKE SAFE
NO DEMANDS
RESISTANCE SENSOR TEMP PRIMARY AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP PRIMARY
REMOVE THE LEADS FROM THE FLOW SENSOR
RESISTANCE SENSOR TEMP RETURN AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP RETURN
REMOVE CONNECTOR FROM RETURN SENSOR
LOCKOUT RESET F 70
ON/OFF SWITCH ON
LOCKOUT RESET F 49
ON/OFF SWITCH ON
RESISTANCE OVERHEAT STAT AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE OVERHEAT HARNESS
DISCONNECT X20 CONNECTOR FROM THE PCB
DISCONNECT THE LEAD TO THE OVERHEAT STAT
HARNESS PRESSURE SWITCH
DISCONNECT CONNECTOR X2 FROM THE PCB
DISCONNECT CONNECTOR FROM THE LOW WATER PRESSURE SWITCH
RESISTANCE SENSOR TEMP PRIMARY AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP RETURN
REMOVE CONNECTOR FROM RETURN SENSOR
RESISTANCE SENSOR TEMP PRIMARY
REMOVE THE LEADS FROM THE FLOW SENSOR
VOLTAGE DIVERTER MOTOR AT PCB
{USEINSMAT}
DISCONNECT THE PLUG FROM THE DIVERTER MOTOR AND MAKE SAFE
NO DEMANDS
DISCONNECT TIMER INTERNAL
DISCONNECT THE INTERNAL PROGRAMMER TO THE RIGHT OF THE DISPLAY BOARD
RESISTANCE WARM START SENSOR AND HARNESS
REMOVE CONNECTOR X2 FROM THE PCB
RESISTANCE WARM START SENSOR
DISCONNECT THE LEADS
VOLTAGE DIVERTER MOTOR AT PCB
{USEINSMAT}
DISCONNECT THE PLUG FROM THE DIVERTER MOTOR AND MAKE SAFE
NO DEMANDS
RESISTANCE GAS VALVE SOLENOID MAIN AND HARNESS
DISCONNECT X20 FROM PCB
RESISTANCE GAS VALVE SOLENOID MAIN
REMOVE THE LEADS FROM THE GAS VALVE
RESISTANCE GAS VALVE SOLENOID MAIN AND HARNESS
DISCONNECT X20 FROM PCB
RESISTANCE GAS VALVE SOLENOID MAIN
REMOVE THE LEADS FROM THE GAS VALVE
EXTERNAL CONTROLS SUPPLY
{USEINSMAT}
ENSURE EXTERNAL CONTROLS ARE CALLING
INLET/FILTER FLOW REGULATOR
DHW SERVICE VALVE OFF
APPLIANCE DRAINED AND DISCHARGED
AQUA SENSOR (FLOW SWITCH)
DHW DISCHARGED AND DRAINED
EXTERNAL CONTROLS OUTPUT (240)
{USEINSMAT}
GAS USAGE
ATTACH PRESSURE GAUG
INLET PRESSURE
ATTACH PRESSURE GAU
HARNESS RESISTANCE GAS VALVE
REMOVE THE PLUG FROM THE GAS VALVE AND UNPLUG THE
CONNECTOR MARKED X20 FROM THE PCB
INSPECTION HEAT EXCHANGER FLUEWAYS
REMOVE FAN AND BURNER ASSEMBLY
INLET PRESSURE
ATTACH PRESSURE GAU
RESISTANCE HARNESS IGNITION
REMOVE THE LEAD FROM THE SPARK GENERATOR
AND THE IGNITION ELECTRODE
INSPECTION HEAT EXCHANGER FLUEWAYS
REMOVE FAN AND BURNER ASSEMBLY
DV HARNESS CONTINUITY
REMOVE THE CONNECTOR X2 FROM THE PCB
REMOVE THE PLUG FROM THE DIVERTER VALVE
DV HARNESS CONTINUITY
REMOVE THE CONNECTOR X2 FROM THE PCB
REMOVE THE PLUG FROM THE DIVERTER VALVE
DV HARNESS CONTINUITY
REMOVE THE CONNECTOR X2 FROM THE PCB
REMOVE THE PLUG FROM THE DIVERTER VALVE
PCB VOLTS FROM AQUA SENSOR
{USEINSMAT}
RESISTANCE SENSOR TEMP PRIMARY AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP RETURN AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
DIVERTER VALVE ACTUATOR OPERATION
REMOVE THE DIVERTER
FAN HARNESS RESISTANCE
REMOVE THE PLUG X20 FROM THE PCB AND
THE CONNECTOR FROM THE FAN
FAN HARNESS RESISTANCE
REMOVE THE PLUG X20 FROM THE PCB AND
THE CONNECTOR FROM THE FAN
VOLTAGE FAN SPEED CONTROL
LEAVE CONNECTOR IN PLACE
FAN VOLTAGE
{USEINSMAT}
DISCONNECT CONNECTOR FROM THE FAN AND MAKE SAFE
DIVERTER VALVE ACTUATOR OPERATION
REMOVE THE DIVERTER
FAN HARNESS RESISTANCE
REMOVE THE PLUG X20 FROM THE PCB AND
THE CONNECTOR FROM THE FAN
VOLTAGE FAN HALL SENSOR
LEAVE CONNECTOR IN PLACE
VOLTAGE FAN SPEED CONTROL
LEAVE CONNECTOR IN PLACE
VOLTAGE PCB DEMAND TO FAN
{USEINSMAT}
TURN
VOLTAGE PCB DEMAND TO FAN
{USEINSMAT}
TURN
RESISTANCE SENSOR TEMP RETURN AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
PRESSURE SENSOR VOLTAGE (PCB)
{USEINSMAT}
GAIN ACCESS TO PCB
VOLTAGE PRESSURE SENSOR (OUT)
{USEINSMAT}
NO DEMAND
GAIN ACCESS TO PCB AS NECESSARY
RESISTANCE OVERHEAT STAT AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS F61/F62
DISCONNECT X20 FROM PCB
RESISTANCE GAS VALVE AND HARNESS F61/F62
DISCONNECT X20 FROM PCB
RESISTANCE FUSE T2 ( APPLIANCE)
REMOVE FUSE FROM FUSE HOLDER ON PCB
VOLTAGE TO DISPLAY (AT PCB)
{USEINSMAT}
GAIN ACCESS TO PCB
DISCONNECT EBUS CONTROLS
DISCONNECT EBUS WIRING AND MAKE SAFE
EXTERNAL CONTROLS INPUT( 24)
{USEINSMAT}
ENSURE APPLIANCE IS IN CH MODE
EXTERNAL CONTROLS OUTPUT ( PCB24)
{USEINSMAT}
DISCONNECT EBUS CONTROLS - FAULT CODE
DISCONNECT EBUS WIRING AND MAKE SAFE
CHECK PUMP OPERATION
REMOVE VENT PLUG FRO
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE DISCHARGED AND DRAINED
INSPECT RUBBER HOSES FLOW & RETURN
DISCHARGE THE PRIMARY WATER FROM THE BOILER
EXPANSION VESSEL
FLOW AND RETURN ISOLATION VALVES CLOSED
DISCHARGE THE PRIMARY WATER FROM THE BOILER
CHECK PUMP OPERATION
REMOVE VENT PLUG FRO
AIR INTAKE CLEAR
REMOVE THE AIR INTAKE PIPE
THE AIR INTAKE IS HELD BY ONE SCREW ATTACHED TO THE HEAT EXCHANGER
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE DISCHARGED AND DRAINED
INSPECT RUBBER HOSES FLOW & RETURN
DISCHARGE THE PRIMARY WATER FROM THE BOILER
EXPANSION VESSEL
FLOW AND RETURN ISOLATION VALVES CLOSED
DISCHARGE THE PRIMARY WATER FROM THE BOILER
VOLTAGE PRESSURE SENSOR (OUT)
{USEINSMAT}
NO DEMAND
GAIN ACCESS TO PCB AS NECESSARY
HARNESS PRESSURE SWITCH
DISCONNECT CONNECTOR X2 FROM THE PCB
DISCONNECT CONNECTOR FROM THE LOW WATER PRESSURE SWITCH
PUMP VOLTAGE PCB
DISCONNECT CONNECTOR X18 FROM THE PCB
(PLACE IN A SAFE POSITION)
PRESSURE SENSOR VOLTAGE (PCB)
{USEINSMAT}
GAIN ACCESS TO PCB
VOLTAGE PRESSURE SENSOR (OUT)
{USEINSMAT}
NO DEMAND
GAIN ACCESS TO PCB AS NECESSARY
INSPECTION FILTER PRIMARY CIRCUIT
APPLIANCE DISCHARGED AND DRAINED
INSPECT RUBBER HOSES FLOW & RETURN
DISCHARGE THE PRIMARY WATER FROM THE BOILER
EXPANSION VESSEL
FLOW AND RETURN ISOLATION VALVES CLOSED
DISCHARGE THE PRIMARY WATER FROM THE BOILER
RESISTANCE SENSOR TEMP PRIMARY AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP RETURN AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
AUTO BYPASS
WATER OFF
FLOW AND RETURN VALVES OFF
ENSURE APPLIANCE IS COMPLETELY DISCHARGED AND DRAINED
PRIMARY FLOW FILTER
APPLIANCE DISCHARGED AND DRAINED
RESISTANCE HARNESS IGNITION
REMOVE THE LEAD FROM THE SPARK GENERATOR
AND THE IGNITION ELECTRODE
FAN HARNESS RESISTANCE
REMOVE THE PLUG X20 FROM THE PCB AND
THE CONNECTOR FROM THE FAN
VOLTAGE FAN HALL SENSOR
LEAVE CONNECTOR IN PLACE
FAN HARNESS RESISTANCE
REMOVE THE PLUG X20 FROM THE PCB AND
THE CONNECTOR FROM THE FAN
VOLTAGE FAN HALL SENSOR
LEAVE CONNECTOR IN PLACE
RESISTANCE FAN AND HARNESS
DISCONNECT CONNECTOR X20 FROM THE PCB
OBSERVATION WHICH TYPE OF PUMP IS FITTED
ORIGINALLY VAILLANT
RESISTANCE PUMP AND HARNESS (ORIGINAL PUMP)
REMOVE CONNECTOR X18 FROM THE PCB
RESISTANCE FAN AND HARNESS
DISCONNECT CONNECTOR X20 FROM THE PCB
OBSERVATION WHICH TYPE OF PUMP IS FITTED
ORIGINALLY VAILLANT
RESISTANCE SENSOR TEMP PRIMARY AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP RETURN AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP PRIMARY AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP RETURN AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
DIFFERENTIAL DHW HEAT EXCHANGER
ATTACH TEMPERATURE CLAMPS AS INDICATED
(DO NOT ATTACH CLAMPS TO THE RUBBER HOSE)
INSPECT RUBBER HOSES FLOW & RETURN
DISCHARGE THE PRIMARY WATER FROM THE BOILER
RESISTANCE SENSOR TEMP PRIMARY AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP RETURN AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
DIFFERENTIAL DHW HEAT EXCHANGER
ATTACH TEMPERATURE CLAMPS AS INDICATED
(DO NOT ATTACH CLAMPS TO THE RUBBER HOSE)
INSPECT RUBBER HOSES FLOW & RETURN
DISCHARGE THE PRIMARY WATER FROM THE BOILER
RESISTANCE PUMP AND HARNESS (ORIGINAL PUMP)
REMOVE CONNECTOR X18 FROM THE PCB
TEMPERATURE COMPARISON OF HOT WATER - EXTERNAL MIXING TEST
TURN HOT WATER TAP ON
INLET PRESSURE
ATTACH PRESSURE GAU
AIR INTAKE CLEAR
REMOVE THE AIR INTAKE PIPE
THE AIR INTAKE IS HELD BY ONE SCREW ATTACHED TO THE HEAT EXCHANGER
INSPECTION HEAT EXCHANGER FLUEWAYS
REMOVE FAN AND BURNER ASSEMBLY
RESISTANCE OVERHEAT STAT
REMOVE THE AIR INTAK
FAN SPEED ( PRESSURE)
ATTACH PRESSURE GAU
RESISTANCE OVERHEAT STAT
REMOVE THE AIR INTAK
RESISTANCE OVERHEAT STAT
REMOVE THE AIR INTAK
INLET PRESSURE
ATTACH PRESSURE GAU
VOLTAGE 24 VDC AND 5 VDC X2 REMOVED
REMOVE CONNECTOR X2 FROM THE PCB
REFIT CONNECTOR X20 TO THE PCB
VOLTAGE 24VDC AND 5 VDC X2 REFITTED PRESSURE SENSOR REMOVED
REFIT CONNECTOR X2 TO THE PCB
REMOVE CONNECTOR FROM PRESSURE SENSOR AND MAKE SAFE
INLET PRESSURE
ATTACH PRESSURE GAU
OBSERVATION SPARK QUALITY
REMOVE THE SPARK IGN
DIVERTER VALVE ACTUATOR OPERATION
REMOVE THE DIVERTER
DIVERTER VALVE ACTUATOR OPERATION
REMOVE THE DIVERTER
FAN HARNESS RESISTANCE
REMOVE THE PLUG X20 FROM THE PCB AND
THE CONNECTOR FROM THE FAN
RESISTANCE SENSOR TEMP PRIMARY AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
FAN HARNESS RESISTANCE
REMOVE THE PLUG X20 FROM THE PCB AND
THE CONNECTOR FROM THE FAN
FAN VOLTAGE
{USEINSMAT}
DISCONNECT CONNECTOR FROM THE FAN AND MAKE SAFE
RESISTANCE SENSOR TEMP RETURN AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
PRIMARY FLOW FILTER
APPLIANCE DISCHARGED AND DRAINED
RESISTANCE SENSOR TEMP PRIMARY AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP RETURN AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP PRIMARY AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP RETURN AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP RETURN AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
PUMP VOLTAGE PCB
DISCONNECT CONNECTOR X18 FROM THE PCB
(PLACE IN A SAFE POSITION)
PRESSURE SENSOR VOLTAGE (PCB)
{USEINSMAT}
GAIN ACCESS TO PCB
VOLTAGE PRESSURE SENSOR (OUT)
{USEINSMAT}
NO DEMAND
GAIN ACCESS TO PCB AS NECESSARY
AIR INTAKE CLEAR
REMOVE THE AIR INTAKE PIPE
THE AIR INTAKE IS HELD BY ONE SCREW ATTACHED TO THE HEAT EXCHANGER
DHW DOES SPARKING OCCUR
REMOVE THE SPARK IGN
AIR INTAKE CLEAR
REMOVE THE AIR INTAKE PIPE
THE AIR INTAKE IS HELD BY ONE SCREW ATTACHED TO THE HEAT EXCHANGER
RESISTANCE SENSOR TEMP PRIMARY AND HARNESS
REMOVE THE CONNECTOR X20 FROM THE PCB
RESISTANCE SENSOR TEMP RETURN AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE OVERHEAT STAT AND HARNESS AT TEMP F76
BOILER TEMPERATURE M
PRESSURE SENSOR VOLTAGE (PCB)
{USEINSMAT}
GAIN ACCESS TO PCB
VOLTAGE PRESSURE SENSOR (OUT)
{USEINSMAT}
NO DEMAND
GAIN ACCESS TO PCB AS NECESSARY
RESISTANCE SENSOR TEMP RETURN AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
INSPECT RUBBER HOSES FLOW & RETURN
DISCHARGE THE PRIMARY WATER FROM THE BOILER