Set Appliance State:
Isolate Mains Power to appliance as per TOPs P4
Set the Thermistor-stat to maximum
Set the Thermistor-stat to maximum
Measurement:
Measure the resistance across connection 8 (blue lead) and connection 9 (brown lead) the main terminal block located on the back of the electrical door assembly.
Resistance should be approximately 13kOhms.
Note.
The resistances will change depending on the Thermistor-stat setting.
Resistance should be between 10kOhms (minimum setting)
to 13kOhms (maximum setting).
The resistance should be approximately 27kOhms for the Summer Airflow setting.
Resistance should be approximately 13kOhms.
Note.
The resistances will change depending on the Thermistor-stat setting.
Resistance should be between 10kOhms (minimum setting)
to 13kOhms (maximum setting).
The resistance should be approximately 27kOhms for the Summer Airflow setting.