VITODENS 100-W COMPACT
WARNING - IMPORTA
OBSERVATION BOILER SELF CHECK
BOILER ON/OFF PUSHED IN, ON POSITION
ENSURE NO DEMANDS
LOCATE SYSTEM PUMP IF REQUIRED
TYPE OF DIAGNOSTIC PROCEDURE
PLEASE SELECT FROM O
PRESSURE GAS INLET (BOILER IGNITED)
ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT
DISPLAY CODE 30 38
NOT USED
DISPLAY CODE 60 68
GLOBAL PAGE
DISPLAY CODE A9
GLOBAL PAGE
DISPLAY CODE B0 B8
NOT USED
DISPLAY CODE E5
NOT USED
DISPLAY CODE F0
NOT USED
DISPLAY CODE F1
NOT USED
DISPLAY CODE F2
NOT USED
DISPLAY CODE F3
NOT USED
DISPLAY CODE F8
NOT USED
DISPLAY CODE F9
NOT USED
DISPLAY CODE FD FF
NOT USED
FUSE FURTHER INVESTIGATION
NOT USED
OBSERVATION PUMP RUNS
LOCATE SYSTEM PUMP
ENSURE THAT SEVERAL RADIATORS ARE OPEN TO PROVIDE A CIRCULATION ROUTE
OBSERVATION FAN RUNS
ENSURE BOILER IS COOL
& DISPLAY CODE 10 18
GLOBAL PAGE
& DISPLAY CODE 50 58
GLOBAL PAGE
HOT WATER OPERATION
HW DEMAND
FAN DOES NOT RUN
SENSOR - TEMPERATURE
BURNER DOES NOT IGNITE
ELECTRODE - IGNITION AND IONIZATION
BURNER DOES NOT ESTABLISH 2
ELECTRODE - IGNITION AND IONIZATION
BURNER DOES NOT IGNITE 4
ELECTRODE - IGNITION AND IONIZATION
BURNER DOES NOT ESTABLISH
ELECTRODE - IGNITION AND IONIZATION
BOILER @ TEMP RADS COOL
MOTOR - PUMP
BOIER TEMP LOW RADS COOL 2
SENSOR - TEMPERATURE
SERVICE MODE 2
Z REDIRECT
FAULT CODE E5
ELECTRODE - IGNITION AND IONIZATION
FAULT CODE E5
CONTROL UNIT
FAULT CODE F1 2
CONTROL UNIT
FAULT CODE F2 2
CONTROL UNIT
FAULT CODE F2 3
CONTROL UNIT
FAULT CODE FD FF 2
ELECTRODE - IGNITION AND IONIZATION
FAULT CODE F3
CONTROL UNIT
FAULT CODE 10/18 2
CONTROL UNIT
FAULT CODE 10/18
CONTROL UNIT
FAULT CODE 50 58 2
CONTROL UNIT
FAULT CODE 50 58
CONTROL UNIT
FAULT CODE FD FF
ELECTRODE - IGNITION AND IONIZATION
FAULT CODE FD FF
CONTROL UNIT
FAULT CDOE A9
CONTROL UNIT
FAULT CDOE A9 2
CONTROL UNIT
FUSE FURTHER INVESTIGATION
MOTOR - PUMP
FAN DOES NOT RUN
MOTOR - PUMP
BOILER TEMP LOW RADS COOL
FAN - NRG
FAULT CODE F2 2
THERMOCOUPLE
DISPLAY DOES NOT OPERATE
FUSE 2.5A (SLOW) 250V
CASE REMOVAL
Z REDIRECT
BURNER BAFFLES OR NOISY
CONDENSATE PIPEWORK
BURNER BAFFLES OR NOISY
GAS INLET PRESSURE
BURNER DOES NOT IGNITE 2
CONDENSATE PIPEWORK
BURNER DOES NOT ESTABLISH
GAS INLET PRESSURE
BURNER DOES NOT IGNITE
CONDENSATE PIPEWORK
BURNER DOES NOT IGNITE
GAS VALVE AND CONTROL UNIT
BURNER DOES NOT IGNITE 3
GAS VALVE
GAS INLET DHW DEMAMD
GAS INLET PRESSURE
BOILER TEMP LOW RADS COOL
MOTOR - PUMP
BOILER TEMP LOW RADS COOL
SENSOR - TEMPERATURE
FAULT CODE 30
SENSOR - TEMPERATURE
FAULT CODE 30
CONTROL UNIT
FAULT CODE 51
SENSOR - TEMPERATURE
FAULT CODE 51
CONTROL UNIT
FAULT CODE 80
SENSOR - TEMPERATURE - FLUE GAS
FAULT CODE B0 B8
CONTROL UNIT
FAULT CODE F0
CONTROL UNIT
FAULT CODE F1
SENSOR - TEMPERATURE - FLUE GAS
FAULT CODE F1
CONTROL UNIT
FAULT CODE F1
MOTOR - PUMP
FAULT CODE F1
SENSOR - TEMPERATURE
FAULT CODE F1
HEAT EXCHANGER
FAULT CODE F2
MOTOR - PUMP
FAULT CODE E3
SENSOR - TEMPERATURE
FAULT CODE F2
SENSOR - TEMPERATURE
FAULT CODE F8
GAS VALVE
NO DISPLAY
FUSE (FUSED SPUR)
FAULT CODE F8
ELECTRODE - IGNITION AND IONIZATION
FAULT CODE F8
CONTROL UNIT
FAULT CODE F9 FA FC 2
CONTROL UNIT
FAULT CODE FD FF
EMC FIELD
FUSE FURTHER INVESTIGATION
FAN - NRG
FUSE FURTHER INVESTIGATION
GAS VALVE
FAULT CODE F9
CABLE HARNESS - FAN
FAULT CODE F9 FA FC
HARNESS
FAULT CODE F9
CONTROL UNIT
USER CONTROLS
Z REDIRECT
TYPE OF DIAGNOSTIC PROCEDURE
Z REDIRECT
FAULT CODE 2
Z REDIRECT
BOILER RESET INFORMATION 2
Z REDIRECT
SELF CHECK 2
CONTROL UNIT
SELF CHECK
SENSOR - TEMPERATURE
CH DOES NOT RESPOND
INTERNAL TIMER/PROGRAMMER
PUMP DOES NOT RUN
CONTROL UNIT
FAN DOES NOT RUN
HARNESS
FAN DOES NOT RUN 2
CONTROL UNIT
BURNER DOES NOT IGNITE 4
GAS VALVE
BURNER DOES NOT IGNITE 1
GAS VALVE
BURNER BAFFLES OR NOISEY
GAS VALVE
BURNER DOES NOT IGNITE
GAS VALVE
BURNER DOES NOT IGNITE
BURNER GAUZE ASSEMBLY
BURNER DOES NOT IGNITE
HEAT EXCHANGER
BURNER DOES NOT IGNITE 2
ELECTRODE - IGNITION AND IONIZATION
BURNER DOES NOT ESTABLISH
CONTROL UNIT
BURNER DOES NOT ESTABLISH
BURNER GAUZE ASSEMBLY
BURNER DOES NOT ESTABLISH
HEAT EXCHANGER
BURNER DOES NOT IGNITE 3
ELECTRODE - IGNITION AND IONIZATION
BURNER DOES NOT IGNITE 3
CONTROL UNIT
BOILER TEMP LOW RADS COOL
CONTROL UNIT
SERVICE MODE
Z REDIRECT
BOILER TEMP LOW RADS COOL
EXTENSION - VENTURI
BOILER TEMP LOW RADS COOL
GAS VALVE
FAULT CODE E5
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CODE F1 2
MOTOR - PUMP
FAULT CODE F1
PUMP WIRING
FAULT CODE F2 2
MOTOR - PUMP
FAULT CODE F2
PUMP WIRING
FAULT CODE F2
FAULT CODE F2 - OVERHEAT
FAULT CODE F3
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CODE 10 OR 18
OUTDOOR SENSOR
FAULT CODE 10 OR 18
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CODE 10 OR 18 2
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CODE 50 58
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CODE 50 58 2
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CODE 50 58 2
CYLINDER DEMAND BOX
FAULT CODE FD FF
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CDOE A9 2
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CDOE A9
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CDOE A9
OPEN THERM DEVICE
FUSE FURTHER INVESTIGATION
PUMP WIRING
FAN DOES NOT RUN
SWITCH-FLOW
BOILER TEMP LOW RADS COOL
BURNER GAUZE ASSEMBLY
BOILER TEMP LOW RADS COOL
HEAT EXCHANGER
BOILER TEMP LOW RADS COOL 2
CONTROL UNIT
FAULT CODE F2 4
CONTROL UNIT
FAULT CODE F2
HARNESS
NO DISPLAY
CONTROL UNIT
FUSE FURTHER INVESTIGATION
Z REDIRECT
BURNER BAFFLES OR NOISY
SIPHON
BURNER BAFFLES OR NOISY
EXTENSION - VENTURI
BURNER BAFFLES OR NOISY
GAS VALVE
BURNER BAFFLES OR NOISY
BURNER GAUZE ASSEMBLY
BURNER BAFFLES OR NOISY
HEAT EXCHANGER
BURNER DOES NOT IGNITE 2
SIPHON
BURNER DOES NOT IGNITE
SIPHON
BURNER DOES NOT IGNITE
CONTROL UNIT
BURNER DOES NOT IGNITE
CABLE GAS VALVE AND CONTROL UNIT
BURNER DOES NOT IGNITE
GAS INLET PRESSURE
BURNER DOES NOT IGNITE
CABLE HARNESS - GAS SOLENOID VALVE
BURNER DOES NOT IGNITE
EXTENSION - VENTURI
BURNER DOES NOT IGNITE 2
GAS VALVE
BURNER DOES NOT IGNITE 2
BURNER GAUZE ASSEMBLY
BURNER DOES NOT IGNITE 2
HEAT EXCHANGER
BURNER DOES NOT ESTABLISH 2
CONTROL UNIT
FAULT CODE 30
HARNESS
FAULT CODE 30
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CODE 51
HARNESS
FAULT CODE 51
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CODE B0
HARNESS
FAULT CODE B0
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CODE F0
FAULT CODE RESET - RETEST BOILER OPERATION
NO DISPLAY 2
CONTROL UNIT
FAULT CODE F1
BOILER RESET - FAULT CODE F1
FAULT CODE F2
THERMOCOUPLE
FAULT CODE F2
CONTROL UNIT
NO DISPLAY
Z REDIRECT
FAULT CODE F8
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CODE F8 2
GAS VALVE
FAULT CDOE F8
FAULT CODE RESET - RETEST BOILER OPERATION
FAULT CODE F9 FA FC
FAN - NRG
FUSE FURTHER INVESTIGATION
CONTROL UNIT - FUSE BLOWN
FUSE FURTHER INVESTIGATION
CABLE HARNESS - FAN
FUSE FURTHER INVESTIGATION 2
CABLE HARNESS - GAS SOLENOID VALVE
FAULT CODE
Z REDIRECT
BURNER DOES NOT IGNITE 2
EXTENSION - VENTURI
BOILER SELF CHECK
FROST PROTECTION NORMAL OPERATION
SELF CHECK
CONTROL UNIT
DISPLAY DOES NOT OPERATE 2
CONTROL UNIT
PUMP DOES NOT RUN 2
CONTROL UNIT
PUMP DOES NOT RUN 3
CONTROL UNIT
PUMP DOES NOT RUN
MOTOR - PUMP
PUMP DOES NOT RUN
PUMP WIRING
BURNER RESTRICTED AND/OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
HEAT EXCHANGER FLUEWAYS RESTRICTED AND/OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
ELECTRODE GAP TO BURNER SURFACE INCORRECT
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS / ELECTRODE
BURNER RESTRICTED AND/OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
HEAT EXCHANGER FLUEWAYS RESTRICTED AND/OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
ELECTRODE GAP TO BURNER SURFACE INCORRECT
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS / ELECTRODE
HOW TO SET BOILER TO 100% OUTPUT
CHARACTERISTIC TEST FROM BOILER OUTPUT
AIR INTAKE RESTRICTED AND/OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI
VENTURI RESTRICTED AND/OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI
RESISTANCE NOT AS EXPECTED
CHARACTERISTIC TEST FROM RESISTANCE OUTSIDE TEMPERATURE SENSOR AND HARNESS
NO OUTDOOR SENSOR INSTALLED
CHARACTERISTIC TEST FROM RESISTANCE OUTSIDE TEMPERATURE SENSOR AND HARNESS
HW DEMAND NOT RECOGNISED
CHARACTERISTIC TEST FROM HOT WATER OPERATION
HW OPERATION UNSATISFACTORY
CHARACTERISTIC TEST FROM HOT WATER OPERATION
BURNER RESTRICTED AND/OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
HEAT EXCHANGER FLUEWAYS RESTRICTED AND/OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH
BURNER IGNITES BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH
BURNER IGNITES BUT BAFFLES OR IS NOISY
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH
AIR INTAKE RESTRICTED AND/OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI
VENTURI RESTRICTED AND/OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI
BURNER RESTRICTED AND/OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
HEAT EXCHANGER FLUEWAYS RESTRICTED AND/OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
NO PRESSURE DROP OBSERVED
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
PRESSURE DROPS BELOW 17.4MB N.G. / 25MB L.P.G.
CHARACTERISTIC TEST FROM PRESSURE GAS INLET DROP
AIR INTAKE RESTRICTED AND/OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI
VENTURI RESTRICTED AND/OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI
BURNER RESTRICTED AND/OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
HEAT EXCHANGER FLUEWAYS RESTRICTED AND/OR DAMAGED
CHARACTERISTIC TEST FROM INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
BOILER REACHES TEMPERATURE - RADIATORS DO NOT HEAT OR ONLY GET WARM
CHARACTERISTIC TEST FROM CH OPERATION
BOILER TEMPERATURE AND SYSTEM TEMPERATURE LOW - BOILER REMAINS LIT
CHARACTERISTIC TEST FROM CH OPERATION
PUMP RUNS CONTINUOUSLY OR BOILER ATTEMPTS TO FIRE AFTER SELF CHECK COMPLETE
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
FAULT CODE DISPLAYED
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
BOILER GOES TO FAULT CODE F2 BEFORE MAXIMUM FLOW TEMP REACHED
CHARACTERISTIC TEST FROM OBSERVATION CH - OVERHEAT OCCUR
TEMPERATURE EXCEEDS MAXIMUM FLOW TEMPERATURE 80°C & CONTINUES TO FIRE
CHARACTERISTIC TEST FROM OBSERVATION CH - OVERHEAT OCCUR
DELAY IN RETURNING TO STANDING PRESSURE
CHARACTERISTIC TEST FROM PRESSURE STANDING RETURN
BOILER DOES NOT RESET - FAULT CODE REMAINS THE SAME
CHARACTERISTIC TEST FROM PRESSURE STANDING RETURN
DISPLAY DOES NOT OPERATE CORRECTLY
CHARACTERISTIC TEST FROM OBSERVATION BOILER SELF CHECK
AIR INTAKE RESTRICTED AND/OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI
VENTURI RESTRICTED AND/OR BLOCKED
CHARACTERISTIC TEST FROM INSPECTION AIR INTAKE AND VENTURI
03/01/2018 10:28:57 1801_1_50_1 09/01/2018 08:23:32
04/01/2018 10:48:25
INSPECTION ELECTRODE
REMOVE ELECTRODE ASSEMBLY FROM BOILER
VOLTAGE AT PUMP
EXPOSE WIRING CONNEC
VOLTAGE PUMP AT PCB
{GAINPCBACS}
VOLTAGE AT PUMP
EXPOSE WIRING CONNEC
VOLTAGE PUMP AT PCB
{GAINPCBACS}
VOLTAGE FAN ASSEMBLY (MAINS VOLTAGE)
{GAINPCBACS}
INSPECTION ELECTRODE
REMOVE ELECTRODE ASSEMBLY FROM BOILER
RESISTANCE OUTSIDE TEMPERATURE SENSOR AND HARNESS
IF INSTALLED DISCONN
OBSERVATION CYLINDER DEMAND BOX INSTALLED
{GAINPCBACS}
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
DISCONNECT CYLINDER DEMAND BOX
DISCONNECT CYLINDER DEMAND BOX, CONNECTED TO 2X RED LEADS AS ILLUSTRATED & MAKE SAFE
OBSERVATION OPEN THERM DEVICE INSTALLED
{GAINPCBACS}
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
DISCONNECT OPEN THERM DEVICE
DISCONNECT OPEN THERM DEVICE, CONNECTIONS ARE 1 & 2 OF TERMINAL BLOCK & MAKE SAFE
RESISTANCE OVERHEAT STAT AND HARNESS
ENSURE BOILER IS COOL
REMOVE CONNECTOR X20 FROM PCB
RESISTANCE OVERHEAT STAT
REMOVE 1 X SPADE CONNECTOR FROM OVERHEAT STAT
RESISTANCE FUSE F4 (PCB)
REMOVE PCB FUSE
RESISTANCE GAS VALVE AND HARNESS
REMOVE CONNECTOR 35 FROM THE PCB
RESISTANCE GAS VALVE
REMOVE CONNECTOR FROM GAS VALVE
RESISTANCE GAS VALVE
REMOVE CONNECTOR FROM GAS VALVE
VOLTAGE AT SPARK GENERATOR - SPARK ELECTRODE DISCONNECTED
REMOVE SPARK ELECTRODE LEAD FROM SPARK GENERATOR, MAKE SAFE
ENSURE NO DEMANDS
RESISTANCE FLOW TEMPERATURE SENSOR & HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE FLOW TEMPERATURE SENSOR
REMOVE CONNECTORS FROM FLOW SENSOR
RESISTANCE RETURN TEMPERATURE SENSOR & HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE RETURN TEMPERATURE SENSOR
DISCONNECT INLINE CONNECTOR TO RETURN SENSOR
RESISTANCE FLUE TEMPERATURE SENSOR AND HARNESS
REMOVE CONNECTOR X20 FROM THE PCB
RESISTANCE FLUE TEMPERATURE SENSOR
DISCONNECT FLUE SENSOR INLINE CONNECTOR
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESISTANCE FLUE TEMPERATURE SENSOR
DISCONNECT FLUE SENSOR INLINE CONNECTOR
RESET APPLIANCE - FAULT CODE F2
ENSURE NO DEMANDS ARE PRESENT
ENSURE BOILER IS COOL
RESISTANCE FUSED SPUR
REMOVE FUSE FROM FUSED SPUR
VOLTAGE FAN ASSEMBLY (MAINS VOLTAGE)
{GAINPCBACS}
RESISTANCE FAN AND HARNESS
REMOVE CONNECTOR 100 FROM THE PCB
RESISTANCE FAN
REMOVE MAINS VOLTAGE CONNECTOR TO FAN ASSEMBLY
RESISTANCE GAS VALVE (FUSE)
REMOVE CONNECTOR FROM GAS VALVE
RESISTANCE PUMP (FUSE INVESTIGATION)
REMOVE WIRING CONNECTIONS AT PUMP
DISCONNECT EXTERNAL CONTROLS
{GAINPCBACS}
DISCONNECT SWITCHED LIVE (PIN1) FROM TERMINAL BLOCK & MAKE SAFE
NO DEMANDS
RESISTANCE FLOW TEMPERATURE SENSOR
REMOVE CONNECTORS FROM FLOW SENSOR
VOLTAGE SWITCHED LIVE
{GAINPCBACS}
DISCONNECT INTERNAL PROGRAMMER
DISCONNECT INTERNAL
VOLTAGE PUMP AT PCB
{GAINPCBACS}
RESISTANCE FLOW SWITCH
DISCONNECT INLINE CONNECTOR TO FLOW SWITCH
INSPECTION ELECTRODE
REMOVE ELECTRODE ASSEMBLY FROM BOILER
INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS / ELECTRODE
REMOVE BURNER MODULE UNIT ASSEMBLY FROM BOILER
INSPECTION ELECTRODE
REMOVE ELECTRODE ASSEMBLY FROM BOILER
INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS / ELECTRODE
REMOVE BURNER MODULE UNIT ASSEMBLY FROM BOILER
RESISTANCE RETURN TEMPERATURE SENSOR
DISCONNECT INLINE CONNECTOR TO RETURN SENSOR
BOILER OUTPUT
SET BOILER TO 100% OUTPUT
INSPECTION AIR INTAKE AND VENTURI
REMOVE AIR INTAKE MANIFOLD
INSPECTION ELECTRODE
REMOVE ELECTRODE ASSEMBLY FROM BOILER
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
INSPECTION ELECTRODE
REMOVE ELECTRODE ASSEMBLY FROM BOILER
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
REMOVE BURNER MODULE UNIT ASSEMBLY FROM BOILER
INSPECTION FAN - INTERNAL
REMOVE BURNER ASSEMBLY FROM BOILER
SEPARATE FAN ASSEMBLY FROM BURNER ASSEMBLY
INSPECTION CONDENSATE SYPHON
GAIN ACCESS TO CONDENSATE SYPHON
INSPECTION CONDENSATE SYPHON
GAIN ACCESS TO CONDENSATE SYPHON
INSPECTION CONDENSATE SYPHON
GAIN ACCESS TO CONDENSATE SYPHON
PRESSURE GAS INLET
ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT
INSPECTION AIR INTAKE AND VENTURI
REMOVE AIR INTAKE MANIFOLD
INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
REMOVE BURNER MODULE UNIT ASSEMBLY FROM BOILER
PRESSURE GAS INLET
ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT
VOLTAGE RECTIFICATION AT SPARK GENERATOR (NO DEMAND)
{GAINPCBACS}
ENSURE NO DEMANDS
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
PRESSURE GAS INLET DROP
ATTACH U-GAUGE TO GAS INLET PRESSURE TEST POINT
OBSERVATION SPARKING OCCURS
REMOVE ELECTRODE LEA
RESISTANCE GAS VALVE AND HARNESS
REMOVE CONNECTOR 35 FROM THE PCB
INSPECTION AIR INTAKE AND VENTURI
REMOVE AIR INTAKE MANIFOLD
INSPECTION BURNER / HEAT EXCHANGER FLUEWAYS
REMOVE BURNER MODULE UNIT ASSEMBLY FROM BOILER
RESISTANCE FLOW TEMPERATURE SENSOR
REMOVE CONNECTORS FROM FLOW SENSOR
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
VOLTAGE MAINS INPUT PCB
{GAINPCBACS}
RESET APPLIANCE - FAULT CODE F1
ENSURE NO DEMANDS ARE PRESENT
ENSURE BOILER IS COOL
RESISTANCE FLOW TEMPERATURE SENSOR
REMOVE CONNECTORS FROM FLOW SENSOR
OBSERVATION FLUE GAS TEMPERATURE
INSERT TEMPERATURE PROBE INTO FLUE GAS TEST POINT
OBSERVATION PUMP RUNS
LOCATE SYSTEM PUMP
ENSURE THAT SEVERAL RADIATORS ARE OPEN TO PROVIDE A CIRCULATION ROUTE
RESISTANCE FLOW TEMPERATURE SENSOR
REMOVE CONNECTORS FROM FLOW SENSOR
RESISTANCE RETURN TEMPERATURE SENSOR
DISCONNECT INLINE CONNECTOR TO RETURN SENSOR
PRESSURE STANDING RETURN
ATTACH U-GAUGE TO IN
INSPECTION ELECTRODE
REMOVE ELECTRODE ASSEMBLY FROM BOILER
RESET APPLIANCE - FAULT CODE
ENSURE NO DEMANDS ARE PRESENT
VOLTAGE FAN CONTROL
REMOVE 1 CONNECTOR F
RESISTANCE FAN CONTROL HARNESS
REMOVE FAN CONTROL CONNECTOR FROM FAN ASSEMBLY
RESISTANCE POWER CABLE FAN ASSEMBLY
REMOVE FAN POWER CONNECTOR TO FAN ASSEMBLY
RESISTANCE PUMP AND HARNESS
REMOVE CONNECTOR 20 FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS (FUSE)
REMOVE CONNECTOR 35 FROM THE PCB
INSPECTION AIR INTAKE AND VENTURI
REMOVE AIR INTAKE MANIFOLD
OBSERVATION PUMP RUNS
LOCATE SYSTEM PUMP
ENSURE THAT SEVERAL RADIATORS ARE OPEN TO PROVIDE A CIRCULATION ROUTE
OBSERVATION FAN RUNS (NO DISPLAY)
REMOVE 1 CONNECTOR FROM OVERHEAT STAT AND MAKE SAFE
TEMPERATURE FLOW PIPE (FROST PROTECTION)
ATTACH FGA TEMPERATURE SENSOR TO PRIMARY HEAT EXCHANGER FLOW CONNECTION
VOLTAGE AT PUMP
EXPOSE WIRING CONNEC
RESISTANCE FLOW SWITCH HARNESS
DISCONNECT INLINE CONNECTOR TO FLOW SWITCH
RESISTANCE FLOW TEMPERATURE SENSOR
REMOVE CONNECTORS FROM FLOW SENSOR