FLEXICOM 12HX TO 30HX
GLOBALLY REPLACED
CASE OFF
CASE REMOVAL
FAN RUNS
NO DEMAND FOR CH OR
PUMP RUNS
MAKE SURE ALL STATS ARE TURNED UP
BOILER CH TEMPERATURE SET TO MAX
BOILER OPERATION
MAKE SURE ANY STATS ARE CALLING FOR HEAT
F3 FAN FAULT
INTENTIONALLY BLANK, HEADER FOR FAULT CODE
F70 SOFTWARE INCOMPATIBLE
INTENTIONALLY BLANK - HEADER FOR FAULT CODE
FUSE FURTHER INVESTIGATION (DUMMY)
INTENTIONALLY BLANK, HEADER FOR FUSE INVESTIGATION
OBSERVATION BURNER IGNITES AND ESTABLISHES
BOILER CH TEMPERATURE SET TO MAX
ER FAULT
HEADER FOR ER FAULT CODE - OUTSIDE MODEL
HEADER FOR QADAI FLOW THERMISTOR
LEFT BLANK FOR QADAI
HEADER FOR QADAI RETURN THERMISTOR
LEFT BLANK FOR QADAI
HEADER FOR QADAI GAS VALVE VOLTAGE
LEFT BLANK FOR QADAI
HEADER FOR QADAI SPARK GENERATOR VOLTAGE
LEFT BLANK FOR QADAI
QUICK ACCESS AND DATA INFORMATION
THE TABLE BELOW SHOW
LITE DIAGNOSTICS
DIAGNOSIS RELIES ON
HEADER FOR QADAI GAS VALVE RESISTANCE
LEFT BLANK FOR QADAI
HEADER FOR QADAI PUMP VOLTAGE
LEFT BLANK FOR QADAI
FAIL DIAG CODES
DUMMY
FAIL STATUS CODES
DUMMY
_RESET_F5
INTERFACE - APPLIANCE
_OUT OF RANGE_F5
THERMISTOR - THERMOMETRIC
_OUT OF RANGE_F5
THERMISTOR - THERMOMETRIC
_NON ADJUSTABLE_DSN_F5
INTERFACE - APPLIANCE
_RESET_F2
INTERFACE - APPLIANCE
_RESET_F6
INTERFACE - APPLIANCE
_F10
INTERFACE - APPLIANCE
_RESET_F13
INTERFACE - APPLIANCE
_NO CONTINUITY_FLOW_F13
HARNESS - COMBUSTION
_NO CONTINUITY_RETURN_F13
HARNESS - COMBUSTION
NO CONTINUITY_F13
IGNITION LEAD ASSEMBLY
_NO CONTINUITY_F13
HARNESS - ZIG
_NO CONTINUITY_F13
EARTH LEADS
_RESET_F14
INTERFACE - APPLIANCE
_RESTRICTED_F13
VALVE - GAS
_RESTRICTED_F14
GAS VALVE THROTTLE
_RESET_F15
INTERFACE - APPLIANCE
_RESET_F22
INTERFACE - APPLIANCE
_RESET_F43
INTERFACE - APPLIANCE
_ADJUST_F43
DS NUMBER
_OC_F43
HARNESS - APPLIANCE INTERFACE
_RESET_F77
INTERFACE - APPLIANCE
FAIL _FAULT CODES
DUMMY
_RESTRICTED_NOT ENOUGH HEAT_BOILER AT TEMP
HEAT EXCHANGER FLUEWAYS
_OUT OF RANGE_F43
THERMISTOR - THERMOMETRIC
_OUT OF RANGE_F43
THERMISTOR - THERMOMETRIC
_MANF DEFECT_F43
ELECTRODE
FAULT F43
IGNITION LEAD ASSEMBLY
F70 NOT RESETTING
INTERFACE - APPLIANCE
F70 DSN NOT ADJUSTING
INTERFACE - APPLIANCE
F70 STUCK IN FAULT
PCB - MAIN - BMU
FUSE INVESTIGATION
PUMP
_OC_NO DISPLAY
MAIN FUSE FUSED SPUR F1
_OC_NO DISPLAY
FUSE F2
FAULT F22_OC_PUMP RUNS
HARNESS - MAINS - PUMP
FAULT F22
HARNESS - MAINS - PUMP
_RESTRICTED_F22
PUMP
_OUT OF RANGE_F22
THERMISTOR - THERMOMETRIC
_OUT OF RANGE_F22
THERMISTOR - THERMOMETRIC
_OPEN CIRC_POWER UP
HARNESS - APPLIANCE INTERFACE
FUSE INVESTIGATION
IGNITOR - ZIG
NON ADJUSTABLE_SET POINT_BOILER TOO COOL
INTERFACE - APPLIANCE
_NON ADJUSTABLE_DSN_BOILER TOO COOL
INTERFACE - APPLIANCE
_OUT OF RANGE-BOILER TOO COOL
THERMISTOR - THERMOMETRIC
_OUT OF RANGE_BOILER TOO COOL
THERMISTOR - THERMOMETRIC
_GAS METER_TOO LOW
GAS SUPPLY
F5 FAULT CODE_OC_
HARNESS - MAINS - PUMP
F5 FAULT CODE_OC_VOLTAGE AT PUMP_
HARNESS - MAINS - PUMP
_RESTRICTED_F5
PUMP
_OUT OF RANGE_F11STUCK IN FAULT
THERMISTOR - THERMOMETRIC
_OUT OF RANGE_F11STUCK IN FAULT
THERMISTOR - THERMOMETRIC
F11 NO RESET
INTERFACE - APPLIANCE
_OUT OF RANGE_F6
THERMISTOR - THERMOMETRIC
_OUT OF RANGE_F6
THERMISTOR - THERMOMETRIC
F6 DAMAGED
HARNESS - COMBUSTION
F10 DAMAGED
HARNESS - COMBUSTION
F11 DAMAGED
HARNESS - COMBUSTION
F15 DAMAGED
HARNESS - COMBUSTION
F3 FAULT CODE_NO POWER TO FAN_FAN RUNS
PCB - MAIN - BMU
F3 FAULT CODE_HALL SENSE CONNECTION_FAN RUNS TWICE
PCB - MAIN - BMU
F3 FAULT CODE_OPEN CIRC__FAN RUNS THEN STOPS
HARNESS - COMBUSTION
F3 FAULT CODE_PERMANENTLY ON_FAN RUNS
PCB - MAIN - BMU
F3 FAULT CODE_OPEN CIRC_FAN RUNS CONTINUOUSLY
HARNESS - COMBUSTION
F3 FAULT CODE_OPEN CIRC_FAN RUNS
HARNESS - COMBUSTION
F3 FAULT CODE__RESTRICTED_FAN DOESNT RUN
FAN MECHANICAL
F3 FAULT CODE_FROST PROTECTION ON_FAN RUNS
PCB - MAIN - BMU
F43 HALL SENSOR_HALL SENSE CONNECTION_FAN RUNS TWICE
PCB - MAIN - BMU
F43 HALL SENS_OPEN CIRC__FAN RUNS THEN STOPS
HARNESS - COMBUSTION
NO DISPLAY
FAN
F22 LOW WATER - CANT CHANGE DSN
INTERFACE - APPLIANCE
BURNER DOES NOT IGNITE
GAS SUPPLY
_NO CONTINUITY_BURNER DOESNT IGNITE
IGNITION LEAD ASSEMBLY
_NO CONTINUITY_BURNER DOESNT IGNITE
HARNESS - ZIG
_DAMAGED_BURNER DOESNT IGNITE
ELECTRODE
_NO POWER TO GAS VALVE_BURNER DOESNT IGNITE
PCB - MAIN - BMU
_RESTRICTED_BURNER DOESN'T IGNITE
GAS VALVE THROTTLE
_RESTRICTED_BURNER DOESNT IGNITE
VALVE GAS (AIR INTAKE)
_RESTRICTED_BURNER DOESNT IGNITE
VALVE GAS (INJECTOR)
_GAS METER_BAFFLES OUT OR NOISY
GAS SUPPLY
NOISY BAFFLES MANU DEF
ELECTRODE
_RESTRICTED_BAFFLES OUT OR NOISY
GAS VALVE THROTTLE
_RETRICTED_BAFFLES OUT OR NOISY
VALVE GAS (AIR INTAKE)
BAFFLES OUT OR IS NOISY
BAFFLE - FLUEWAY - TOP
EXPLOSIVE IGNITION_GAS METER_
GAS SUPPLY
_NO CONTINUITY_EXPLOSIVE IGNITION
IGNITION LEAD ASSEMBLY
_FAN SPEED_ EXPLOSIVE IGNITION
PCB - MAIN - BMU
_NO CONTINUITY_EXPLOSIVE IGNITION
HARNESS - ZIG
EXPLOSIVE IGNITION_MANF DEFECT_
ELECTRODE
EXPLOSIVE IGNITION_RESTRICTED_
GAS VALVE THROTTLE
EXPLOSIVE IGNITION_RETRICTED_
VALVE GAS (AIR INTAKE)
EXPLOSIVE IGNITION
BAFFLE - FLUEWAY - TOP
_GAS METER_BURNER DOESNT ESTABLISH
GAS SUPPLY
_OUT OF RANGE_POWER UP
THERMISTOR - THERMOMETRIC
_OPEN CIRC_FAN RUNS
HARNESS - COMBUSTION
_OUT OF RANGE_FAN RUNS
THERMISTOR - THERMOMETRIC
_OUT OF RANGE_FAN RUNS
THERMISTOR - THERMOMETRIC
NOT ENOUGH HEAT BOILER AT TEMP
SYSTEM PRESSURE
_PERMANENTLY ON_BOILER TOO HOT
PCB - MAIN - BMU
_NOT SET CORRECTLY_TOO HOT
OVERRUN
BOILER NOISY
SYSTEM PRESSURE
_BLOCKED_F5
SUMP
F5
SYSTEM RESTRICTION OR BLOCKAGE
_BLOCKAGE_F5
FLUE
_RESTRICTED_F5
HEAT EXCHANGER FLUEWAYS
_OUT OF RANGE_POWER UP
THERMISTOR - THERMOMETRIC
F5
SYSTEM PRESSURE
F22
SYSTEM PRESSURE
BAFFLES OUT OR NOISY
FLUE
NOISY FAILED COMBUSTION
SIPHON
OPERATION DHW - NOISY
VALVE GAS (AIR INTAKE)
NOISY
VALVE GAS (INJECTOR)
NOISY
HEAT EXCHANGER PRIMARY
NOISY
BURNER
NOISY
SIPHON
NOISY
THERMISTOR - THERMOMETRIC
NOISY
THERMISTOR - THERMOMETRIC
BOILER NOISY - DIFFERENTIAL WRONG
HEAT EXCHANGER PRIMARY
BOILER TOO COOL_RESTRICTED_
BURNER
F22 LOW WATER_RESTRICTED_
BURNER
F22 FAULT
SYSTEM RESTRICTION OR BLOCKAGE
DOES NOT ESTABLISH_NO CONTINUITY_
HARNESS - ZIG
DOES NOT ESTABLISH_OC_
IGNITION LEAD ASSEMBLY (EARTH LEAD)
NOT RECTIFYING
IGNITION LEAD ASSEMBLY
NO RECTIFICATION PATH
IGNITOR - ZIG
DOES NOT ESTABLISH_RESTRICTED_
VALVE GAS (AIR INTAKE)
DOES NOT ESTABLISH_RESTRICTED_
VALVE GAS (INJECTOR)
F13
IGNITOR - ZIG
OBSERVATION DISPLAY ILLUMINATES
HARNESS - MAINS
_NO CONTINUITY_BURNER DOESNT IGNITE
HARNESS - COMBUSTION
F13
ELECTRODE
_NO RESPONSE_BOILER OP
PCB - MAIN - BMU
F22 FAULT CODE
GAS SUPPLY
ER FAULT
PCB - MAIN - BMU
ER FAULT
HARNESS - APPLIANCE INTERFACE
QADAI OUT OF RANGE
THERMISTOR - THERMOMETRIC
QADAI OUT OF RANGE
THERMISTOR - THERMOMETRIC
QADAI NO POWER TO GAS VALVE
PCB - MAIN - BMU
_OC_F14
HARNESS - COMBUSTION
_FAN SPEED_EXPLOVSIVE IGNTION QADAI
PCB - MAIN - BMU
BLANK FOR QADAI
Z DIRECTION
BLANK FOR LITE DIAGNOSTICS
Z DIRECTION
RESISTANCE OUT QADAI
VALVE - GAS
QADAI NO VOLTAGE TO PUMP
PCB - MAIN - BMU
_PERMANENTLY ON_FAN RUNS
PCB - MAIN - BMU
CASE REMOVAL
NULL TESTS
_HALL SENSE CONNECTION_FAN RUNS TWICE
PCB - MAIN - BMU
_OPEN CIRC_FAN RUNS CONTINUOUSLY
HARNESS - COMBUSTION
_OPEN CIRC__FAN RUNS THEN STOPS
HARNESS - COMBUSTION
_NO POWER TO FAN_FAN RUNS
PCB - MAIN - BMU
FOR TYPE DIAG PROCEDURE
NULL TESTS
_OC_VOLTAGE AT PUMP_PUMP RUNS
HARNESS - MAINS - PUMP
_OC_PUMP RUNS
HARNESS - MAINS - PUMP
_OUT OF RANGE_NOT ENOUGH HEAT _BOILER AT TEMP
THERMISTOR - THERMOMETRIC
_OUT OF RANGE_NOT ENOUGH HEAT _BOILER AT TEMP
THERMISTOR - THERMOMETRIC
_NON ADJUSTABLE_DSN_NOT ENOUGH HEAT_BOILER AT TEMP
INTERFACE - APPLIANCE
NON ADJUSTABLE_SET POINT_NOT ENOUGH HEAT_BOILER AT TEMP
INTERFACE - APPLIANCE
NON ADJUSTABLE_SET POINT_BOILER TOO HOT
INTERFACE - APPLIANCE
_NON ADJUSTABLE_DSN_BOILER TOO HOT
INTERFACE - APPLIANCE
_OUT OF RANGE-BOILER TOO HOT
THERMISTOR - THERMOMETRIC
_OUT OF RANGE_BOILER TOO HOT
THERMISTOR - THERMOMETRIC
_NON ADJUSTABLE_DSN_NOISY
INTERFACE - APPLIANCE
PASS DIAG CODES
DUMMY
PASS STATUS CODES
DUMMY
PASS_SET POINT_AT TEMP
DUMMY
PASS_SET POINT_TOO HOT
DUMMY
_NO CONTINUITY FLOW_F5
HARNESS - COMBUSTION
_NO CONTINUITY RETURN_F5
HARNESS - COMBUSTION
_F13
PCB - MAIN - BMU
_F14
PCB - MAIN - BMU
_BLOCKAGE_F77
CONDENSATE TANK
PASS_FAULT CODES
DUMMY
_BLOCKED_NOT ENOUGH HEAT_BOILER AT TEMP
HEAT EXCHANGER
_NO CONTINUITY FLOW_F43
HARNESS - COMBUSTION
_NO CONTINUITY RETURN_F43
HARNESS - COMBUSTION
F70 INCORRECT
DS NUMBER ADJUSTMENT
F70 RESET
DS NUMBER ADJUSTMENT
FUSE INVESTIGATION
HARNESS - MAINS - PUMP
FUSE INVESTIGATION F1
NULL TESTS
FUSE INVESTIGATION F2
NULL TESTS
FAULT F22
HARNESS - MAINS
FAULT F22 NO POWER TO PUMP
PCB - MAIN - BMU
FAULT F22
PUMP WIRING
_NO CONTINUITY FLOW_F22
HARNESS - COMBUSTION
F22
NO FAULT
_NO CONTINUITY RETURN_F22
HARNESS - COMBUSTION
_NO VOLTAGE_POWER UP
INTERFACE - APPLIANCE
FUSE INVESTIGATION
FUSE BLOWN
FUSE INVESTIGATION
HARNESS - ZIG
PASS_SET POINT_TOO COOL
DUMMY
_NO CONTINUITY FLOW_BOILER TOO COOL
HARNESS - COMBUSTION
_NO CONTINUITY RETURN_BOILER TOO COOL
HARNESS - COMBUSTION
BOILER TOO COOL _FLUEWAYS BLOCKED_
HEAT EXCHANGER PRIMARY
RESTRICTED_TOO LOW
GAS SUPPLY PIPEWORK
F5 FAULT CODE_NO CONTINUITY_
HARNESS - MAINS
F5 FAULT CODE_PUMP NO POWER_
PCB - MAIN - BMU
F5 FAULT CODE_OC_
PUMP WIRING
_SL PERM POWER_F5
PCB - MAIN - BMU
_NO CONTINUITY FLOW_F11STUCK IN FAULT
HARNESS - COMBUSTION
_NO CONTINUITY RETURN_F11STUCK IN FAULT
HARNESS - COMBUSTION
_NO CONTINUITY FLOW_F6
HARNESS - COMBUSTION
_NO CONTINUITY RETURN_F6
HARNESS - COMBUSTION
_F6
PCB - MAIN - BMU
F10_
PCB - MAIN - BMU
_NO POWER TO INTERFACE_POWER UP
PCB - MAIN - BMU
F15
PCB - MAIN - BMU
_F43
PCB - MAIN - BMU
F5
PCB - MAIN - BMU
F5 NO OVERRUN
PCB - MAIN - BMU
F11
PCB - MAIN - BMU
SHORTED NO DISPLAY
HARNESS - COMBUSTION
BOILER OPERATION NOT ENOUGH HEAT
DS NUMBER WRONG NO OTHER FAULT
BOILER OPERATION TOO HOT
DS NUMBER WRONG NO OTHER FAULT
BOILER OPEATION TOO COOL
DS NUMBER WRONG NO OTHER FAULT
BOILER OPERATION NOISY
DS NUMBER WRONG NO OTHER FAULT
F22 LOW WATER_FLUEWAYS BLOCKED_
HEAT EXCHANGER PRIMARY
F22 FAULT
DS NUMBER WRONG NO OTHER FAULT
BURNER DOES NOT IGNITE
GAS SUPPLY PIPEWORK
_FAN SPEED_BURNER DOESNT IGNITE
PCB - MAIN - BMU
_NO SPARK_BURNER DOESNT IGNITE
IGNITOR - ZIG
_RETRICTED_BURNER DOESNT IGNITE
VALVE - GAS
RESTRICTED_BAFFLES OUT OR NOISY
GAS SUPPLY PIPEWORK
BAFFLES OUT OR IS NOISY
VALVE - GAS
EXPLOSIVE IGNITIONRESTRICTED_
GAS SUPPLY PIPEWORK
_NO SPARK_EXPLOSIVE IGNITION
IGNITOR - ZIG
EXPLOSIVE IGNITION_BLOCKED_
SIPHON
_FROST STAT_POWER UP
EXTERNAL FROST STAT CONTROL
EXPLOSIVE IGNITION
VALVE - GAS
RESTRICTED_BURNER DOESN'T ESTABLISH
GAS SUPPLY PIPEWORK
_NO CONTINUITY FLOW_POWER UP
HARNESS - COMBUSTION
_NO CONTINUITY FLOW_FAN RUNS
HARNESS - COMBUSTION
_FROST PROTECTION ON_FAN RUNS
PCB - MAIN - BMU
_NO CONTINUITY RETURN_FAN RUNS
HARNESS - COMBUSTION
EXPLOSIVE IGNITION_FLUEWAYS BLOCKED_
HEAT EXCHANGER PRIMARY
BAFFLES OUT OR IS NOISY_FLUEWAYS BLOCKED_
HEAT EXCHANGER PRIMARY
_FLUEWAYS BLOCKED_BURNER DOESNT IGNITE
HEAT EXCHANGER PRIMARY
BOILER TOO HOT NO OVERRUN
PCB - MAIN - BMU
BOILER TOO HOT
PCB - MAIN - BMU
BOILER AND SYSTEM TOO HOT
PCB - MAIN - BMU
_BLOCKED_F5
SIPHON
F5
NO FAULT
_NO CONTINUITY RETURN_POWER UP
HARNESS - COMBUSTION
_PERMANENTLY ON_POWER UP
PCB - MAIN - BMU
NOISY
VALVE - GAS (ADJUSTMENT)
BOILER NOISY - DIFFERENTIAL OK
HEAT EXCHANGER PRIMARY
BOILER TOO COOL _FLUEWAYS BLOCKED_ GAS RATE LOW
HEAT EXCHANGER PRIMARY
DOES NOT ESTABLISH_BLOCKED_
SIPHON
DOES NOT ESTABLISH_FLUEWAYS BLOCKED_BURNER DOESNT IGNITE
HEAT EXCHANGER PRIMARY
NO RECTIFICATION
PCB - MAIN - BMU
NO IGNITION - SOLENOID FAULT
VALVE - GAS
_STUCK IN ANTICYCLE_NO RESPONSE_BOILER OP
SETTING ADJUSTMENT
F22 LOW WATER_FLUEWAYS BLOCKED_ GAS RATE LOW
HEAT EXCHANGER PRIMARY
F22 GAS RATE
PCB - MAIN - BMU
ER FAULT
INTERFACE - APPLIANCE
UNABLE TO RESET
PCB - MAIN - BMU
FLOW THERMISTOR
RESULT AS EXPECTED
RETURN THERMISTOR
RESULT AS EXPECTED
GAS VALVE VOLTAGE
RESULT AS EXPECTED
_NO VOLTAGE_F14
PCB - MAIN - BMU
SPARK GENERATOR
RESULT AS EXPECTED
GAS VALVE RESISTANCE
RESULT AS EXPECTED
PUMP VOLTAGE AT PCB
RESULT AS EXPECTED
_OC_PUMP RUNS
PUMP WIRING
_PUMP NO POWER_FAN RUNS
PCB - MAIN - BMU
_NO CONTINUITY_PUMP RUNS
HARNESS - MAINS
_NO CONTINUITY FLOW_NOT ENOUGH HEAT _BOILER AT TEMP
HARNESS - COMBUSTION
_NO CONTINUITY RETURN_NOT ENOUGH HEAT _BOILER AT TEMP
HARNESS - COMBUSTION
_NO CONTINUITY FLOW_BOILER TOO HOT
HARNESS - COMBUSTION
_NO CONTINUITY RETURN_BOILER TOO HOT
HARNESS - COMBUSTION
NO DISPLAY
CHARACTERISTIC TEST FROM POWER UP
BOILER PERMANENTLY ON
CHARACTERISTIC TEST FROM POWER UP
FAN RUNS FOR APPROX 10 SECONDS THEN STOPS 4 TIMES
CHARACTERISTIC TEST FROM FAN RUNS
FAN DOESN'T RUN
CHARACTERISTIC TEST FROM FAN RUNS
PUMP OVERRUN NOT INDICATED
CHARACTERISTIC TEST FROM PUMP OVERRUN STATUS
PUMP OVERRUN INDICATED BUT PUMP NOT RUNNING
CHARACTERISTIC TEST FROM PUMP OVERRUN STATUS
BURNER IGNITES BUT DOESNT ESTABLISH
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
BURNER IGNITES AND ESTABLISHES BUT WITH EXPLOSIVE IGNITION
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
IGNITES BUT NOISY OR BAFFLES OUT
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
BURNER DOESNT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
PUMP OVERRUN NOT INDICATED
CHARACTERISTIC TEST FROM PUMP OVERRUN STATUS
PUMP OVERRUN INDICATED BUT PUMP NOT RUNNING
CHARACTERISTIC TEST FROM PUMP OVERRUN STATUS
FAN RUNS CONTINUALLY WITH NO DEMAND
CHARACTERISTIC TEST FROM FAN RUNS
FAN RUNS FOR APPROX 10 SECONDS THEN STOPS 4 TIMES
CHARACTERISTIC TEST FROM FAN RUNS
FAN DOESN'T RUN
CHARACTERISTIC TEST FROM FAN RUNS
UNABLE TO GAS RATE - BOILER ENTERS FAULT CODE WHEN SERVICE MODE ACTIVATED
CHARACTERISTIC TEST FROM GAS RATE (FAULT CODE)
GAS RATE UNSATISFACTORY
CHARACTERISTIC TEST FROM GAS RATE (FAULT CODE)
UNABLE TO RESET PCB
CHARACTERISTIC TEST FROM GAS VALVE VOLTAGE
VOLTAGES NOT AS ABOVE
CHARACTERISTIC TEST FROM GAS VALVE VOLTAGE
NOT ENOUGH HEAT TO SYSTEM_BOILER AT TEMPERATURE
CHARACTERISTIC TEST FROM BOILER OPERATION
BOILER AND SYSTEM RUNNING TOO HOT
CHARACTERISTIC TEST FROM BOILER OPERATION
BOILER AND SYSTEM TOO COOL
CHARACTERISTIC TEST FROM BOILER OPERATION
BOILER NOISY
CHARACTERISTIC TEST FROM BOILER OPERATION
05/05/2023 10:56:22 2303_1_50_1 29/11/2023 12:51:39
09/08/2023 13:52:51
RESET (OVERHEAT)
ENSURE BOILER IS COOL
USING A SMALL IMPLEMENT, PRESS THE RESET BUTTON BELOW THE DISPLAY
FLOW THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE THERMISTOR
RETURN THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE RETURN THERMISTOR
RESET (FAN FAULT)
USING A SMALL IMPLEMENT, PRESS THE RESET BUTTON BELOW THE DISPLAY
RESET THERMISTOR FAULT
USING A SMALL IMPLEMENT, PRESS THE RESET BUTTON BELOW THE DISPLAY
RESET THERMISTOR FAULT
USING A SMALL IMPLEMENT, PRESS THE RESET BUTTON BELOW THE DISPLAY
RESET THERMISTOR FAULT
USING A SMALL IMPLEMENT, PRESS THE RESET BUTTON BELOW THE DISPLAY
RESET
USING A SMALL IMPLEMENT, PRESS THE RESET BUTTON BELOW THE DISPLAY
RESET
USING A SMALL IMPLEMENT, PRESS THE RESET BUTTON BELOW THE DISPLAY
RESET
USING A SMALL IMPLEMENT, PRESS THE RESET BUTTON BELOW THE DISPLAY
RESET F22 / F25
USING A SMALL IMPLEMENT, PRESS THE RESET BUTTON BELOW THE DISPLAY
RESET
USING A SMALL IMPLEMENT, PRESS THE RESET BUTTON BELOW THE DISPLAY
RESET
USING A SMALL IMPLEMENT, PRESS THE RESET BUTTON BELOW THE DISPLAY
SUMP
DISCONNECT THE CONDE
FLOW THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE THERMISTOR
RETURN THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE RETURN THERMISTOR
RESET
USING A SMALL IMPLEMENT, PRESS THE RESET BUTTON BELOW THE DISPLAY
DS NUMBER ADJUSTMENT F70
ACCESS LEVEL 2 DIAGNOSTICS AS IN THE PREVIOUS TEST
RESISTANCE PUMP AND HARNESS
DISCONNECT CONNECTOR X14 FROM THE PCB
RESISTANCE PUMP
GAIN ACCESS TO PUMP WIRING CONNECTIONS
DISCONNECT WIRES FROM THE PUMP
FUSE F1 (FUSED SPUR)
REMOVE FUSE FROM FUSED SPUR
PUMP VOLTAGE FROM PCB
GAIN ACCESS TO THE TOP RHS OF THE PCB, CONNECTOR X14
SWITCHED LIVE VOLTAGE AT PCB
APPLY A CH DEMAND, MAKING SURE STATS ARE TURNED UP
SWITCHED LIVE AT MAINS CONNECTION
GAIN ACCESS TO THE M
HOT WATER DEMAND
TURN ON THE HOT WATE
PUMP HARNESS CONTINUITY
GAIN ACCESS TO THE ELECTRIC INTERFACE HOUSING ALSO REMOVE THE X14 PLUG FORM THE RHS OF THE PCB
FLOW THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE THERMISTOR
RETURN THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE RETURN THERMISTOR
FUSE F2 (APPLIANCE)
REMOVE FUSE FROM FUSE AND HOLDER FROM PCB
RESISTANCE SPARK GENERATOR
DISCONNECT THE MAINS INTO THE SPARK GENERATOR
DS NUMBER ADJUSTMENT (INCORRECT OUTPUT)
ACCESS LEVEL 2 DIAGNOSTICS AS IN THE PREVIOUS TEST
FLOW THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE THERMISTOR
RETURN THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE RETURN THERMISTOR
INLET PRESSURE (RUNNING)
ATTACH U-GAUGE TO THE INLET PRESSURE TEST POINT ON THE GAS VALVE
INLET PRESSURE AT METER
ATTACH GAUGE TO INLET PRESSURE TEST POINT OF METER
PUMP VOLTAGE FROM PCB
GAIN ACCESS TO THE TOP RHS OF THE PCB, CONNECTOR X14
SWITCHED LIVE VOLTAGE AT PCB
APPLY A CH DEMAND, MAKING SURE STATS ARE TURNED UP
SWITCHED LIVE AT MAINS CONNECTION
GAIN ACCESS TO THE M
HOT WATER DEMAND
TURN ON THE HOT WATE
PUMP HARNESS CONTINUITY
GAIN ACCESS TO THE ELECTRIC INTERFACE HOUSING ALSO REMOVE THE X14 PLUG FORM THE RHS OF THE PCB
SWITCHED LIVE AT MAINS CONNECTION
GAIN ACCESS TO THE M
FLOW THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE THERMISTOR
RETURN THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE RETURN THERMISTOR
FLOW THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE THERMISTOR
RETURN THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE RETURN THERMISTOR
FAN VOLTAGE AT PCB B
GAIN ACCESS TO THE X20 CONNECTOR ON THE RIGHT HAND SIDE OF THE PCB
OBSERVATION DISCONNECT FAN
REFIT CONNECTOR X20
FROST STAT INPUT TO PCB
MAKE SURE THERE IS NO DEMAND FROM THE EXTERNAL CONTROLS
DS NUMBER ADJUSTMENT F22
ACCESS LEVEL 2 DIAGNOSTICS AS IN THE PREVIOUS TEST
INLET PRESSURE AT METER
ATTACH GAUGE TO INLET PRESSURE TEST POINT OF METER
SPARK ELECTRODE LEAD
DISCONNECT THE SPARK ELECTRODE LEAD
FAN VOLTAGE AT PCB
ACCESS THE X20 CONNECTOR ON THE RIGHT HAND SIDE OF THE PCB
SUMP
DISCONNECT THE CONDE
FLOW THERMISTOR AND HARNESS RESISTANCE
UNPLUG CONNECTOR X20 FROM RIGHT HAND SIDE OF PCB
INLET PRESSURE AT METER
ATTACH GAUGE TO INLET PRESSURE TEST POINT OF METER
SUMP
DISCONNECT THE CONDE
INLET PRESSURE AT METER
ATTACH GAUGE TO INLET PRESSURE TEST POINT OF METER
SPARK ELECTRODE LEAD
DISCONNECT THE SPARK ELECTRODE LEAD
SUMP
DISCONNECT THE CONDE
INLET PRESSURE AT METER
ATTACH GAUGE TO INLET PRESSURE TEST POINT OF METER
FLOW THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE THERMISTOR
FLOW THERMISTOR AND HARNESS RESISTANCE
UNPLUG CONNECTOR X20 FROM RIGHT HAND SIDE OF PCB
FLOW THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE THERMISTOR
RETURN THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE RETURN THERMISTOR
SWITCHED LIVE AT MAINS CONNECTION
GAIN ACCESS TO THE M
SUMP
DISCONNECT THE CONDE
RETURN THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE RETURN THERMISTOR
CONDENSATE TRAP AND SUMP CHECK
DISCONNECT THE PUSH
SUMP
DISCONNECT THE CONDE
GAS VALVE HARNESS CONTINUITY
REMOVE THE PLUG FROM THE GAS VALVE
DISCONNECT CONNECTOR X20 FROM THE PCB
OBSERVATION DISCONNECT FAN (ER FAULT)
REMOVE THE FAN CONNECTOR AND MAKE SAFE
FLOW THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE THERMISTOR
RETURN THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE RETURN THERMISTOR
POWER TO SPARK GENERATOR
ACCESS AND MOVE THE
RESISTANCE GAS VALVE
DISCONNECT LEAD FROM GAS VALVE
PUMP VOLTAGE FROM PCB
GAIN ACCESS TO THE TOP RHS OF THE PCB, CONNECTOR X14
PUMP VOLTAGE FROM PCB
GAIN ACCESS TO THE TOP RHS OF THE PCB, CONNECTOR X14
PUMP HARNESS CONTINUITY
GAIN ACCESS TO THE ELECTRIC INTERFACE HOUSING ALSO REMOVE THE X14 PLUG FORM THE RHS OF THE PCB
SWITCHED LIVE VOLTAGE AT PCB
APPLY A CH DEMAND, MAKING SURE STATS ARE TURNED UP
SWITCHED LIVE AT MAINS CONNECTION
GAIN ACCESS TO THE M
HOT WATER DEMAND
TURN ON THE HOT WATE
DS NUMBER ADJUSTMENT (INCORRECT OUTPUT)
ACCESS LEVEL 2 DIAGNOSTICS AS IN THE PREVIOUS TEST
FLOW THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE THERMISTOR
RETURN THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE RETURN THERMISTOR
DS NUMBER ADJUSTMENT (INCORRECT OUTPUT)
ACCESS LEVEL 2 DIAGNOSTICS AS IN THE PREVIOUS TEST
FLOW THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE THERMISTOR
RETURN THERMISTOR RESISTANCE
REMOVE THE SPADE CONNECTORS FROM THE RETURN THERMISTOR
DS NUMBER ADJUSTMENT (INCORRECT OUTPUT)
ACCESS LEVEL 2 DIAGNOSTICS AS IN THE PREVIOUS TEST
DS NUMBER
DS IS THE DEVICE SPECIFIC NUMBER AND SHOULD
CORRESPOND WITH THE BOILER MODEL
FLOW THERMISTOR AND HARNESS RESISTANCE
UNPLUG CONNECTOR X20 FROM RIGHT HAND SIDE OF PCB
RETURN THERMISTOR AND HARNESS RESISTANCE
DISCONNECT X20 CONNECTOR FROM RHS OF PCB
FLOW THERMISTOR HARNESS CONTINUITY
DISCONNECT THE SPADE CONNECTORS FROM THE THERMISTOR AND THE X20 CONNECTOR FROM THE RHS OF THE PCB
RETURN THERMISTOR HARNESS CONTINUITY
DISCONNECT THE SPADE
SPARK ELECTRODE LEAD
DISCONNECT THE SPARK ELECTRODE LEAD
SPARK GENERATOR LEAD
UNPLUG THE LEAD FROM THE SPARK GENERATOR AND X21 OF THE PCB
EARTH LEADS CONTINUITY
GAIN ACCESS TO THE EARTH LEADS ON THE BOILER
P1 PRESSURE
ATTACH A U-GAUGE TO THE P1 TEST POINT OF THE GAS VALVE
THROTTLE
USING A 2.5MM ALLEN
DS NUMBER
DS IS THE DEVICE SPECIFIC NUMBER AND SHOULD
CORRESPOND WITH THE BOILER MODEL
INTERFACE HARNESS CONTINUITY
REMOVE THE HARNESS FROM THE INTERFACE PCB AND X51 AT THE PCB
CONDENSATE TRAP AND SUMP CHECK
DISCONNECT THE PUSH
HEAT EXCHANGER FLUEWAYS
REMOVE THE FAN/GAS VALVE ASSEMBLY AND BURNER FROM
THE TOP OF THE HEAT EXCHANGER
FLOW AND RETURN TEMPERATURE DIFFERENTIAL
ATTACH TEMPERATURE PROBES TO THE FLOW AND RETURN PIPES NEAR TO THE BOILER
FLOW THERMISTOR AND HARNESS RESISTANCE
UNPLUG CONNECTOR X20 FROM RIGHT HAND SIDE OF PCB
RETURN THERMISTOR AND HARNESS RESISTANCE
DISCONNECT X20 CONNECTOR FROM RHS OF PCB
SPARK ELECTRODE LEAD
DISCONNECT THE SPARK ELECTRODE LEAD
DS NUMBER
DS IS THE DEVICE SPECIFIC NUMBER AND SHOULD
CORRESPOND WITH THE BOILER MODEL
DS NUMBER RESET (F70)
ACCESS LEVEL 2 DIAGNOSTICS AS IN THE PREVIOUS TEST
MAINS POWER INPUT TO APPLIANCE
REMOVE LOWER CONTROL BOX FRONT PANEL
PUMP RUNS
MAKE SURE ALL STATS ARE TURNED UP
BOILER CH TEMPERATURE SET TO MAX
VOLTAGE AT PUMP
REMOVE THE COVER FROM THE PUMP
PUMP HARNESS CONTINUITY
GAIN ACCESS TO THE ELECTRIC INTERFACE HOUSING ALSO REMOVE THE X14 PLUG FORM THE RHS OF THE PCB
FLOW THERMISTOR AND HARNESS RESISTANCE
UNPLUG CONNECTOR X20 FROM RIGHT HAND SIDE OF PCB
RETURN THERMISTOR AND HARNESS RESISTANCE
DISCONNECT X20 CONNECTOR FROM RHS OF PCB
PRESSURE FAN ON IGNITION
ATTACH THE PRESSURE GAUGE TO THE OUTLET PRESSURE TEST POINT
VOLTAGE TO INTERFACE PCB
REMOVE THE INTERFACE HARNESS PLUG FROM X51 OF THE PCB
INTERFACE HARNESS CONTINUITY
REMOVE THE HARNESS FROM THE INTERFACE PCB AND X51 AT THE PCB
RESISTANCE SPARK GENERATOR AND HARNESS
DISCONNECT CONNECTOR X21 FROM THE PCB
BOILER THERMOSTAT SET POINT
PRESS THE MODE BUTTON ON THE DISPLAY
VOLTAGE PCB SWITCHED LIVE
{GAINPCBACS}
TURN OFF ANY DEMAND FROM EXTERNAL CONTROLS E.G. PROGRAMMER, FROST STAT ETC
DS NUMBER
DS IS THE DEVICE SPECIFIC NUMBER AND SHOULD
CORRESPOND WITH THE BOILER MODEL
FLOW THERMISTOR AND HARNESS RESISTANCE
UNPLUG CONNECTOR X20 FROM RIGHT HAND SIDE OF PCB
RETURN THERMISTOR AND HARNESS RESISTANCE
DISCONNECT X20 CONNECTOR FROM RHS OF PCB
PRESSURE FAN ON IGNITION
ATTACH THE PRESSURE GAUGE TO THE OUTLET PRESSURE TEST POINT
INSPECTION BURNER
REMOVE THE FAN/GAS VALVE ASSEMBLY AND BURNER FROM THE TOP OF THE HEAT EXCHANGER
PUMP RUNS
MAKE SURE ALL STATS ARE TURNED UP
BOILER CH TEMPERATURE SET TO MAX
VOLTAGE AT PUMP
REMOVE THE COVER FROM THE PUMP
PUMP HARNESS CONTINUITY
GAIN ACCESS TO THE ELECTRIC INTERFACE HOUSING ALSO REMOVE THE X14 PLUG FORM THE RHS OF THE PCB
PUMP OVERRUN STATUS
ACCESS THE STATUS CO
FLOW THERMISTOR AND HARNESS RESISTANCE
UNPLUG CONNECTOR X20 FROM RIGHT HAND SIDE OF PCB
RETURN THERMISTOR AND HARNESS RESISTANCE
DISCONNECT X20 CONNECTOR FROM RHS OF PCB
FLOW THERMISTOR AND HARNESS RESISTANCE
UNPLUG CONNECTOR X20 FROM RIGHT HAND SIDE OF PCB
RETURN THERMISTOR AND HARNESS RESISTANCE
DISCONNECT X20 CONNECTOR FROM RHS OF PCB
INSPECTION HARNESS
GAIN ACCESS TO PCB
INSPECTION HARNESS
GAIN ACCESS TO PCB
INSPECTION HARNESS
GAIN ACCESS TO PCB
INSPECTION HARNESS
GAIN ACCESS TO PCB
FAN VOLTAGE AT PCB B
GAIN ACCESS TO THE X20 CONNECTOR ON THE RIGHT HAND SIDE OF THE PCB
FAN VOLTAGE AT PCB
GAIN ACCESS TO X20 CONNECTOR ON THE RIGHT HAND SIDE OF THE PCB
FAN VOLTAGE AT PCB G AND B - NO FAN
ACCESS THE X20 CONNE
FAN HARNESS CONTINUITY
UNPLUG THE HARNESS FROM THE FAN AND X20 AT THE PCB
FAN VOLTAGE AT PCB
GAIN ACCESS TO THE RIGHT HAND SIDE OF THE PCB CONNECTOR X20
FAN HARNESS CONTINUITY
UNPLUG THE HARNESS FROM THE FAN AND X20 AT THE PCB
FAN HARNESS CONTINUITY
UNPLUG THE HARNESS FROM THE FAN AND X20 AT THE PCB
FAN MECHANICAL
REMOVE THE GAS VALVE FROM THE SIDE OF THE FAN
FAN HARNESS CONTINUITY
UNPLUG THE HARNESS FROM THE FAN AND X20 AT THE PCB
OBSERVATION DISCONNECT X20
DISCONNECT CONNECTOR X20 FROM THE PCB AND MAKE SAFE
INSPECTION BURNER
REMOVE THE FAN/GAS VALVE ASSEMBLY AND BURNER FROM THE TOP OF THE HEAT EXCHANGER
DS NUMBER
DS IS THE DEVICE SPECIFIC NUMBER AND SHOULD
CORRESPOND WITH THE BOILER MODEL
INLET PRESSURE
ATTACH U-GAUGE TO THE INLET PRESSURE TEST POINT ON THE GAS VALVE
INLET PRESSURE
ATTACH U-GAUGE TO THE INLET PRESSURE TEST POINT ON THE GAS VALVE
INLET PRESSURE
ATTACH U-GAUGE TO THE INLET PRESSURE TEST POINT ON THE GAS VALVE
INLET PRESSURE
ATTACH U-GAUGE TO THE INLET PRESSURE TEST POINT ON THE GAS VALVE
SPARK TEST
REMOVE THE HT LEAD F
POWER TO SPARK GENERATOR
ACCESS AND MOVE THE
SPARK GENERATOR LEAD
UNPLUG THE LEAD FROM THE SPARK GENERATOR AND X21 OF THE PCB
CONDENSATE TRAP AND SUMP CHECK
DISCONNECT THE PUSH
PRESSURE FAN ON IGNITION
ATTACH THE PRESSURE GAUGE TO THE OUTLET PRESSURE TEST POINT
GAS VALVE BASE SETTINGS
GAS VALVE BASE SETTI
AIR INTAKE
REMOVE THE GAS VALVE
INJECTOR
REMOVE THE GAS VALVE
CONDENSATE TRAP AND SUMP CHECK
DISCONNECT THE PUSH
PRESSURE FAN ON IGNITION
ATTACH THE PRESSURE GAUGE TO THE OUTLET PRESSURE TEST POINT
GAS VALVE BASE SETTINGS BAFFLES
GAS VALVE BASE SETTI
AIR INTAKE
REMOVE THE GAS VALVE
HEAT EXCHANGER BAFFLE
REMOVE THE BURNER FR
SPARK TEST
REMOVE THE HT LEAD F
CONDENSATE TRAP AND SUMP CHECK
DISCONNECT THE PUSH
POWER TO SPARK GENERATOR
ACCESS AND MOVE THE
SPARK GENERATOR LEAD
UNPLUG THE LEAD FROM THE SPARK GENERATOR AND X21 OF THE PCB
PRESSURE FAN ON IGNITION
ATTACH THE PRESSURE GAUGE TO THE OUTLET PRESSURE TEST POINT
GAS VALVE BASE SETTINGS BAFFLES
GAS VALVE BASE SETTI
AIR INTAKE
REMOVE THE GAS VALVE
HEAT EXCHANGER BAFFLE
REMOVE THE BURNER FR
RETURN THERMISTOR AND HARNESS RESISTANCE
DISCONNECT X20 CONNECTOR FROM RHS OF PCB
FAN HARNESS CONTINUITY
UNPLUG THE HARNESS FROM THE FAN AND X20 AT THE PCB
RETURN THERMISTOR AND HARNESS RESISTANCE
DISCONNECT X20 CONNECTOR FROM RHS OF PCB
INSPECTION BURNER
REMOVE THE FAN/GAS VALVE ASSEMBLY AND BURNER FROM THE TOP OF THE HEAT EXCHANGER
INSPECTION BURNER
REMOVE THE FAN/GAS VALVE ASSEMBLY AND BURNER FROM THE TOP OF THE HEAT EXCHANGER
INSPECTION BURNER
REMOVE THE FAN/GAS VALVE ASSEMBLY AND BURNER FROM THE TOP OF THE HEAT EXCHANGER
PUMP OVERRUN STATUS
ACCESS THE STATUS CO
CONDENSATE TRAP AND SUMP CHECK
DISCONNECT THE PUSH
TEMPERATURE DIFFERENTIAL
ATTACH TEMPERATURE PROBES TO THE FLOW AND RETURN PIPES NEAR TO THE BOILER
HEAT EXCHANGER FLUEWAYS
REMOVE THE FAN/GAS VALVE ASSEMBLY AND BURNER FROM
THE TOP OF THE HEAT EXCHANGER
AIR INTAKE
REMOVE THE GAS VALVE
INJECTOR
REMOVE THE GAS VALVE
HEAT EXCHANGER FLUEWAYS
REMOVE THE FAN/GAS VALVE ASSEMBLY AND BURNER FROM
THE TOP OF THE HEAT EXCHANGER
INSPECTION BURNER
REMOVE THE FAN/GAS VALVE ASSEMBLY AND BURNER FROM THE TOP OF THE HEAT EXCHANGER
CONDENSATE TRAP AND SUMP CHECK
DISCONNECT THE PUSH
FLOW THERMISTOR AND HARNESS RESISTANCE
UNPLUG CONNECTOR X20 FROM RIGHT HAND SIDE OF PCB
RETURN THERMISTOR AND HARNESS RESISTANCE
DISCONNECT X20 CONNECTOR FROM RHS OF PCB
FLOW AND RETURN TEMPERATURE DIFFERENTIAL
ATTACH TEMPERATURE PROBES TO THE FLOW AND RETURN PIPES NEAR TO THE BOILER
FAN MECHANICAL
REMOVE THE GAS VALVE FROM THE SIDE OF THE FAN
INSPECTION BURNER
REMOVE THE FAN/GAS VALVE ASSEMBLY AND BURNER FROM THE TOP OF THE HEAT EXCHANGER
FAN VOLTAGE AT PCB
GAIN ACCESS TO THE RIGHT HAND SIDE OF THE PCB CONNECTOR X20
TEMPERATURE DIFFERENTIAL
ATTACH TEMPERATURE PROBES TO THE FLOW AND RETURN PIPES NEAR TO THE BOILER
FAN VOLTAGE AT PCB B
GAIN ACCESS TO THE X20 CONNECTOR ON THE RIGHT HAND SIDE OF THE PCB
RESISTANCE HARNESS SPARK GENERATOR
UNPLUG THE LEAD FROM THE SPARK GENERATOR AND X21 OF THE PCB
EARTH CONTINUITY
DISCONNECT THE EARTH LEAD FROM THE ELECTRODE
SPARK ELECTRODE LEAD
DISCONNECT THE SPARK ELECTRODE LEAD
RESISTANCE SPARK GENERATOR (RECTIFICATION)
REMOVE WIRES FROM SPARK GENERATOR
CONDENSATE TRAP AND SUMP CHECK
DISCONNECT THE PUSH
PRESSURE FAN ON IGNITION
ATTACH THE PRESSURE GAUGE TO THE OUTLET PRESSURE TEST POINT
INSPECTION BURNER
REMOVE THE FAN/GAS VALVE ASSEMBLY AND BURNER FROM THE TOP OF THE HEAT EXCHANGER
AIR INTAKE
REMOVE THE GAS VALVE
INJECTOR
REMOVE THE GAS VALVE
RESISTANCE SPARK GENERATOR (RECTIFICATION)
REMOVE WIRES FROM SPARK GENERATOR
FAN VOLTAGE AT PCB
GAIN ACCESS TO X20 CONNECTOR ON THE RIGHT HAND SIDE OF THE PCB
RESISTANCE HARNESS INSTALLER INTERFACE TO PCB
GAIN ACCESS TO THE INSTALLER INTERFACE HOUSING
DISCONNECT X10 FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS
DISCONNECT CONNECTOR X20 FROM THE PCB
INLET PRESSURE (RUNNING)
ATTACH U-GAUGE TO THE INLET PRESSURE TEST POINT ON THE GAS VALVE
INSPECTION BURNER
REMOVE THE FAN/GAS VALVE ASSEMBLY AND BURNER FROM THE TOP OF THE HEAT EXCHANGER
VOLTAGE TO INTERFACE PCB
REMOVE THE INTERFACE HARNESS PLUG FROM X51 OF THE PCB
INTERFACE HARNESS CONTINUITY
REMOVE THE HARNESS FROM THE INTERFACE PCB AND X51 AT THE PCB
GAS VALVE HARNESS CONTINUITY
REMOVE THE PLUG FROM THE GAS VALVE
DISCONNECT CONNECTOR X20 FROM THE PCB
FAN HARNESS CONTINUITY
UNPLUG THE HARNESS FROM THE FAN AND X20 AT THE PCB
FAN HARNESS CONTINUITY
UNPLUG THE HARNESS FROM THE FAN AND X20 AT THE PCB
FAN VOLTAGE AT PCB G AND B - NO FAN
ACCESS THE X20 CONNE
VOLTAGE AT PUMP
REMOVE THE COVER FROM THE PUMP
BOILER THERMOSTAT SET POINT
PRESS THE MODE BUTTON ON THE DISPLAY
BOILER THERMOSTAT SET POINT
PRESS THE MODE BUTTON ON THE DISPLAY
DS NUMBER
DS IS THE DEVICE SPECIFIC NUMBER AND SHOULD
CORRESPOND WITH THE BOILER MODEL
PUMP HARNESS CONTINUITY
GAIN ACCESS TO THE ELECTRIC INTERFACE HOUSING ALSO REMOVE THE X14 PLUG FORM THE RHS OF THE PCB
DS NUMBER
DS IS THE DEVICE SPECIFIC NUMBER AND SHOULD
CORRESPOND WITH THE BOILER MODEL
FLOW THERMISTOR AND HARNESS RESISTANCE
UNPLUG CONNECTOR X20 FROM RIGHT HAND SIDE OF PCB
RETURN THERMISTOR AND HARNESS RESISTANCE
DISCONNECT X20 CONNECTOR FROM RHS OF PCB
DS NUMBER
DS IS THE DEVICE SPECIFIC NUMBER AND SHOULD
CORRESPOND WITH THE BOILER MODEL
FLOW THERMISTOR AND HARNESS RESISTANCE
UNPLUG CONNECTOR X20 FROM RIGHT HAND SIDE OF PCB
RETURN THERMISTOR AND HARNESS RESISTANCE
DISCONNECT X20 CONNECTOR FROM RHS OF PCB