Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to Resistance Set meter to measure resistance
Remove the Yellow spaded wires from the Thermostat Sensor.

Measurement:

Measure the resistance across the unconnected terminals of the sensor.
The sensor resistance should be approximately 1 MOhm at 20 °C but will vary depending upon its temperature.
The higher the boiler temperature the lower the resistance.
Temperature °CResistance
20 1.2 Mohms
30780 kohms
40480 kohms
50296 kohms
60183 kohms
70115 kohms
8070 kohms