Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Turn CH Temperature to 70°C
Attach temperature probes to flow and return pipework close to the boiler
Attach temperature probes to flow and return pipework close to the boiler
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
On/Off switch on.
Allow fan to run and boiler to fire and allow system to reach a reasonable operating temperature.
Measure the temperature difference between flow and return.
Expected differential approx. 11 to 20 °C
Click on your observation:
1. DIFFERENTIAL OK BUT EXCESSIVE HEAT
2.DIFFERENTIAL NOT OK NOISE LOCAL BOILING
3.DIFFERENTIAL OK SYSTEM PROBLEM
Allow fan to run and boiler to fire and allow system to reach a reasonable operating temperature.
Measure the temperature difference between flow and return.
Expected differential approx. 11 to 20 °C
Click on your observation:
1. DIFFERENTIAL OK BUT EXCESSIVE HEAT
2.DIFFERENTIAL NOT OK NOISE LOCAL BOILING
3.DIFFERENTIAL OK SYSTEM PROBLEM