Set Appliance State:
Isolate Mains Power to appliance as per TOPs P4
Remove connector plug from DHW temperature sensor (green leads)
Remove connector plug from DHW temperature sensor (green leads)
Measurement:
Measure resistance across the exposed terminals of the sensor.
The resistance depends on temperature and should conform to the table below:
The resistance depends on temperature and should conform to the table below:
| Temperature °C | Resistance in kOhms |
| 20 - 30 | 6.1 - 3.8 |
| 30 - 40 | 4.0 - 2.5 |
| 40 - 50 | 2.7 - 1.6 |
| 50 - 60 | 1.8 - 1.0 |
| 60 - 70 | 1.3 - 0.7 |
| 70 - 80 | 0.9 - 0.5 |

Isolate as per TOPs P4
and refit as necessary