Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Gain access to PCB (use Insulation Mat as required)
Hot tap ON
Function selector in standby position
Hot tap ON
Function selector in standby position
| WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure |
Measurement:
Function selector to DHW position.
Allow fan to start.
After approximately 5 seconds measure voltage across the blue (neutral) and brown (live) leads on connector marked X17 on the PCB.
Expect mains voltage (240 VAC).
Voltage will only be present for approximately 4 seconds as flame will not prove.
Allow fan to start.
After approximately 5 seconds measure voltage across the blue (neutral) and brown (live) leads on connector marked X17 on the PCB.
Expect mains voltage (240 VAC).
Voltage will only be present for approximately 4 seconds as flame will not prove.

Isolate as per TOPs P4
and refit as necessary