Set Appliance State:
Mains Power Off
CH Demand
Selector Switch to Hot Water and Heating
| WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure |
Observation:
Does boiler react to CH demand? i.e. pumps run, fan starts.
Note:
There is an re-ignition frequency programme built into the appliance. This is to control the time between ignition cycles - when in heating mode the factory setting is 3 mins. This can be overridden by turning the power to the appliance Off and On again, or turning the function selector to the standby position and back to the heating position.
Note:
There is an re-ignition frequency programme built into the appliance. This is to control the time between ignition cycles - when in heating mode the factory setting is 3 mins. This can be overridden by turning the power to the appliance Off and On again, or turning the function selector to the standby position and back to the heating position.