Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
DHW Demand
DHW temperature set to MAX
Attach temperature clamps to flow and return pipes
to secondary heat exchanger
Attach temperature clamps to flow and return pipes
to secondary heat exchanger
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow appliance to operate for hot water.
Monitor the temperature differential across flow and return pipes.
Expected temperature differential approximately 25°C or less.
Note.
Flow rate no greater than 14.5 litres/min.
Monitor the temperature differential across flow and return pipes.
Expected temperature differential approximately 25°C or less.
Note.
Flow rate no greater than 14.5 litres/min.