Set Appliance State:

Mains Power Off
CH Demand
CH temperature set to MAX
Attach temperature clamps as indicated by the red arrows
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow the boiler to run for central heating and the system to heat up.
Measure the temperature differential.
Expect a differential of approx 22°C or less.
Note.
1. Ensure all radiators are open and system is balanced correctly
to provide correct test results.
2.Initial temperature differential may be greater than 22°C when system is heated from cold.